Plan Review Details - Permit 14060500
Plan Review Stops For Permit 14060500
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-04 Cont ID  
Sent By rmcdouga Date 2014-08-04 Time 18:49 Rev Time 0.00
Received By rmcdouga Date 2014-08-04 Time 18:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-08 Cont ID  
Sent By rmcdouga Date 2014-07-08 Time 17:47 Rev Time 0.00
Received By rmcdouga Date 2014-07-08 Time 17:47 Sent To  
Notes
2014-07-08 17:46:562010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENGINEERING IN YOUR EMAIL REQUIRES THE POSITIVE
 AND NEGATIVE PRESSURES SPECIFIC TO THE SITE TO BE
 DETERMINED BY OTHERS. SEE GENERAL NOTE 2 AND THE
 ALLOWABLE DESIGN PRESSURE NOTES IN THE UPPER RIGHT HAND
 CORNER. THIS STRUCTURE IS LOCATED IN A 170 MPH VULT
 WIND SPEED AND THE EXPOSURE CATEGORY IS C. THE
 ALLOWABLE PRESSURE FOR THE 20 KW GENERATOR PAD FROM THE
 ENGINEERING IS 35.39 PSF. THIS WILL NOT MEET THE
 REQUIRED WIND LOAD PRESSURES. FS 471.025 AND FAC
 61G15-23.002 REQUIRE ORIGINAL SIGNED AND SEALED
 DOCUMENTS WHEN SUBMITTED FOR PUBLIC RECORD.
 THE ENGINEERING THAT WAS ORIGINALLY SUBMITTED WOULD BE
 ACCEPTABLE IF IT DID NOT SPECIFY SPECIFIC MODEL NUMBERS
 OR IF THE MODELS 006244-0, 006250-0 FOR THE 20 KW
 GENERATOR PAPER WORK THAT WAS PROVIDED WERE LISTED.
  
 2) SUBMIT TWO COPIES OF INSTALLATION INSTRUCTIONS FOR
 THE GENERATOR. FBCR G2408.1
  
 3) SPECIFY THE LOCATION OF THE GENERATOR IN RELATION TO
 OPENINGS IN THE WALLS AND OVERHANG OF THE DWELLING.
 FBCR G2408.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-19 Cont ID  
Sent By rmcdouga Date 2014-06-19 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2014-06-19 Time 10:51 Sent To E
Notes
2014-06-19 11:03:292010 FBC
  
 DENIED BY BUILDING
  
 1) THE GENERAC MODEL NUMBERS SPECIFIED ON THE CONCRETE
 PAD PLAN DO NOT CORRESPOND WITH THE MODEL NUMBERS ON
 THE GENERATOR PAPER WORK THAT WAS SUBMITTED. FBCR
 G2404.6
  
 2) SUBMIT TWO COPIES OF INSTALLATION INSTRUCTIONS FOR
 THE GENERATOR. FBCR G2408.1
  
 3) SPECIFY THE LOCATION OF THE GENERATOR IN RELATION TO
 OPENINGS IN THE WALLS AND OVERHANG OF THE DWELLING.
 FBCR G2408.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-20 Cont ID  
Sent By albarran Date 2014-06-20 Time 12:20 Rev Time 0.00
Received By albarran Date 2014-06-20 Time 11:13 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-06-19 Cont ID  
Sent By rmcdouga Date 2014-06-19 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2014-06-19 Time 10:51 Sent To  
Notes
2014-06-19 10:53:00500 GALLON PROPANE TANK AND PIPING ARE UNDER SEPARATE
 PERMIT #14060501.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-04 Cont ID  
Sent By rmcdouga Date 2014-08-04 Time 18:49 Rev Time 0.00
Received By rmcdouga Date 2014-08-04 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-20 Cont ID  
Sent By albarran Date 2014-06-20 Time 12:30 Rev Time 0.00
Received By albarran Date 2014-06-12 Time 08:08 Sent To  
Notes
2014-06-20 12:30:05SMALL DENIED "A"
2014-06-16 08:08:43SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-16 Cont ID  
Sent By sgraham Date 2014-06-16 Time   Rev Time  
Received By sgraham Date 2014-06-16 Time   Sent To P
Notes
***NONE***