Plan Review Details - Permit 14060484
Plan Review Stops For Permit 14060484
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-08-19 Cont ID  
Sent By wjolin Date 2014-08-13 Time 14:43 Rev Time 0.00
Received By jwitmer Date 2014-08-19 Time 07:32 Sent To  
Notes
2014-08-19 12:25:48BUILDING PLAN REVIEW
 PERMIT: 14060484
 ADD: 900 FLORIDA AVENUE
 CONT: COSTAL
 TEL: (561)659-5919
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUESDAY AUG. 19/2014
 ACTION: BUILDING PROVISO
  
 1) THE ARCHITECTURAL SHEETS FOR THE STAIRS AND RAMP
 WILL NEED TO SHOW COMPLIANCE WITH THE 2010 FBC-B
 HANDRAIL EXTENSIONS IN COMPLIANCE WITH 505.10 FIGURE
 505.10.1 AND PROTRUDING LIMITS 307.2.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 07:30 Sent To  
Notes
2014-07-01 07:57:13BUILDING PLAN REVIEW
 PERMIT: 14060484
 ADD: 900 FLORIDA AVENUE
 CONT: COSTAL
 TEL: (561)659-5919
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY JULY 01/2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE REQUIREMENTS:
 SITE PLAN, LOCATION OF MODULAR BUILDING ON LOT.
 PARKING
  
 2) THE STATE APPROVED PLANS INDICATE ITEMS THAT ARE
 SITE INSTALLED:
 2A) ACCESSIBLE RAMP HANDRAIL /GUARDRAIL, & STAIRS 1009:
 STAIRS, 1010: RAMPS, 1012 HANDRAILS & 1013 GAURDS.
 2B) BUILDING DRAINAGE AND CLEAN OUT 107.3.5.1.3 (4)
 SANITARY DRAINAGE
 2C) STORM SHUTTERS
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(E)
 STORM SHUTTERS
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-08-27 Cont ID  
Sent By dhayes Date 2014-08-27 Time 10:12 Rev Time 0.00
Received By dhayes Date 2014-08-27 Time 10:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-08-05 Cont ID  
Sent By dhayes Date 2014-08-05 Time 07:40 Rev Time 0.00
Received By dhayes Date 2014-08-05 Time 07:40 Sent To  
Notes
2014-08-05 07:41:48DATE: 8/5/2014
 PROJECT: CONSTRUCTION TRAILER
 PERMIT#: 14060484
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ACCORDING TO THE CONTRACTOR'S RESPONSE LETTER TO THE
 PREVIOUS ELECTRICAL COMMENTS THE PLANS SUBMITTED ON
 PERMIT #14070239 HAVE THE INFORMATION REQUESTED.
 THE LOAD CALCULATION SUBMITTED INDIACTES A LOAD OF 63.4
 AMPS ON PANEL A AND 60.5 AMPS AN PANEL B. I PULLED THE
 PLANS FROM PERMIT #14070239 AND DETERMINED THAT THE
 RISER DIAGRAM ON THAT PERMIT INDICATE A 60AMP FEEDER TO
 EACH PANEL WHICH WOULD BE UNDERSIZED FOR THE LOAD.
 EITHER SUBMIT A REVISION TO PERMIT #14070239 WITH A
 CORRECTED RISER DIAGRAM WITH ADAQUATE AMPACITY TO
 SUPPORT THE LOAD TO BE SERVED OR RE-SUBMIT THIS PERMIT
 APPLICATION WITH A RISER DIAGRAM WITH ADAQUATE AMPACITY
 TO SUPPORT THE LOAD TO BE SERVED.
  
 2) ACCORDING TO THE CONTRACTORS RESPONSE LETTER UNDER
 THE PLUMBING REVIEW COMMENTS DRINKING FOUNTAINS WILL BE
 PROVIDED. THE CUT SHEET SUBMITTED WITH THE RE-SUBMITTAL
 ARE FOR ELECTRICAL DRINKING FOUNTAINS THAT REQUIRE A
 GFI PROTECTED OUTLET. SEE NEC 422.52 ELECTRIC DRINKING
 FOUNTAINS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-07 Cont ID  
Sent By dhayes Date 2014-07-07 Time 14:42 Rev Time 0.00
Received By dhayes Date 2014-07-07 Time 14:42 Sent To  
Notes
2014-07-07 15:03:22DATE: 7/7/2014
 PROJECT: HILTON HOTEL
 PERMIT#: 14060484
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 ELECTRICAL PLANS REQUIRED FOR THE FOLLOWING:
  
 1) LOAD CALCULATION TO INDICATE THE TOTAL CONNECTED
 LOAD AT TRAILER.
 2) SITE TO SHOW LOCATION OF TRAILER RELATIVE TO UTILITY
 SOURCE AND SERVICE EQUIPMENT REQUIRED TO FEED TRAILER.
 3) A ONE LINE RISER DIAGRAM TO INDICATE SIZE AND TYPE
 OF PIPE AND WIRE FROM UTILITY TO MAIN SERVICE
 DISCONNECT TO DISTRIBUTION TO TRAILER. CONFIRM AMPACITY
 OF CONDUCTORS ARE ADAQUATE TO SUPPORT TOTAL CONNECTED
 LOAD COMPUTED IN LOAD CALCULATION.
 4) A PANEL SCHEDULE TO INDICATE OCP AND CIRCUITS
 INVOLVED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-08-13 Cont ID  
Sent By wjolin Date 2014-08-13 Time 11:29 Rev Time 0.00
Received By wjolin Date 2014-08-13 Time 11:01 Sent To B
Notes
2014-08-13 11:29:05900 FLORIDA AVENUE - CONSTRUCTION TRAILERS
 PERMIT #14060484
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****PROVISO****
  
 NEED A #131 FIRE FINAL INSPECTION BEFORE OCCUPYING THE
 MODULAR BUILDINGS.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS/LETTERS SHALL
 BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES
 IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 COULD NOT LOCATE ANY EXTERIOR LIGHTING ILLUMINATING THE
 EXIT DISCHARGE TO THE PUBLIC WAY.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-06-12 Cont ID  
Sent By pleduc Date 2014-06-12 Time   Rev Time 0.00
Received By pleduc Date 2014-06-12 Time 16:20 Sent To  
Notes
2014-06-12 16:33:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PERMIT APPLICATION DID NOT INCLUDE A SITE PLAN. A
 SITE PLAN SHALL INDICATED THE LOCATION AND SEPARATION
 DIMENSIONS OF THE TRAILER IN REFENCE TO PROPERTY LINES,
 BUILDINGS, OTHER TRAILERS AND OTHER IMPORTANT
 STRUCTURES.
  
 SEPARATION DISTANCES SHALL COMPLY WITH NFPA 241

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-27 Cont ID  
Sent By dhayes Date 2014-08-27 Time 10:13 Rev Time 0.00
Received By dhayes Date 2014-08-20 Time 18:02 Sent To  
Notes
2014-08-20 18:02:49SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-20 Cont ID  
Sent By eschneid Date 2014-08-20 Time 14:16 Rev Time 0.00
Received By eschneid Date 2014-08-04 Time 07:21 Sent To  
Notes
2014-08-14 14:34:26B14
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-07 Cont ID  
Sent By dhayes Date 2014-07-07 Time 15:03 Rev Time 0.00
Received By dhayes Date 2014-06-11 Time 12:23 Sent To  
Notes
2014-06-12 12:23:16B01

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-10-21 Cont ID  
Sent By hmoser Date 2014-10-21 Time 08:20 Rev Time 0.00
Received By hmoser Date 2014-10-21 Time 08:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-19 Cont ID  
Sent By jwitmer Date 2014-08-19 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2014-08-19 Time 07:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 08:04 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 07:57 Sent To  
Notes
2014-07-01 08:04:34PLUMBING PLAN REVIEW
 PERMIT: 14060484
 ADD: 900 FLORIDA AVENUE
 CONT: COSTAL
 TEL: (561)659-5919
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY JULY 01/2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
  
 (2) FIXTURE REQUIEMENTS ACCESSIBLE DRINKING FOUNTAINS,
 2010 FL ACC CODE. 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7
  
 (4) SANITARY DRAINAGE
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-08-20 Cont ID  
Sent By eschneid Date 2014-08-20 Time 14:10 Rev Time 0.25
Received By eschneid Date 2014-08-20 Time 14:10 Sent To  
Notes
2014-08-20 14:11:24THE DRIVE AISLE BEHIND THE ADA SPACE SHALL BE A MINIMUM
 OF 24 FEET WIDE.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By eschneid Date 2014-07-01 Time 10:10 Rev Time 0.25
Received By eschneid Date 2014-07-01 Time 10:10 Sent To  
Notes
2014-07-01 10:11:21FAILED
  
 1) PROVIDE A SITE PLAN FOR THE TRAILER LOCATION AND FOR
 THE PARKING TO SUPPORT THE CONSTRUCTION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-06-13 11:34:286/13/14