Plan Review Details - Permit 14060384
Plan Review Stops For Permit 14060384
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-26 Cont ID  
Sent By rmcdouga Date 2014-07-26 Time 07:53 Rev Time 0.00
Received By rmcdouga Date 2014-07-26 Time 07:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-06-11 Cont ID  
Sent By rmcdouga Date 2014-06-11 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2014-06-11 Time 08:31 Sent To  
Notes
2014-06-11 10:43:44THE WINDOW IN THE SECOND FLOOR BATHROOM WHERE THE
 CLOSET IS CONVERTED TO A SHOWER WILL BE REQUIRED TO
 HAVE SAFETY GLAZING PER FBC R308.4.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-26 Cont ID  
Sent By rmcdouga Date 2014-07-26 Time 07:53 Rev Time 0.00
Received By rmcdouga Date 2014-07-26 Time 07:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-06-11 Cont ID  
Sent By rmcdouga Date 2014-06-11 Time 08:49 Rev Time 0.00
Received By rmcdouga Date 2014-06-11 Time 08:49 Sent To  
Notes
2014-06-11 08:51:28NO ELECTRICAL WORK IS SHOWN ON THE PLANS AND NO
 ELECTRICAL PERMIT APPLICATION WAS SUBMITTED. A SEPARATE
 PERMIT, APPLICATION, PLANS AND REVIEW IS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2014-07-26 Time   Rev Time 0.00
Received By shill Date 2014-07-22 Time 12:55 Sent To  
Notes
2014-07-23 12:49:25TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-11 Cont ID  
Sent By rmcdouga Date 2014-06-11 Time 12:55 Rev Time  
Received By rmcdouga Date 2014-06-10 Time   Sent To  
Notes
2014-06-11 10:12:29SENT TO ZONING BOX FOR REVIEW OF RELOCATED CONDENSING
 UNIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-07-26 Cont ID  
Sent By rmcdouga Date 2014-07-26 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2014-07-26 Time 07:52 Sent To  
Notes
2014-07-26 07:53:14APPROVED WITH EXCEPTIONS. MAKE CORRECTIONS NOTED ON
 PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-06-11 Cont ID  
Sent By rmcdouga Date 2014-06-11 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2014-06-11 Time 10:11 Sent To Z
Notes
2014-06-11 08:54:352010 FBC
  
 DENIED BY MECHANICAL
  
 THE MECHANICAL PLANS SHOW NEW DUCT WORK AND THE SCOPE
 OF WORK SPECIFIES THE EXISTING A/C UNIT IS TO BE
 REPLACED AND RELOCATED.
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AND
 AHRI CERTIFICATIONS FOR THE NEW A/C EQUIPMENT. FBCR
 M1401.3
  
 2) SPECIFY THE CFMS AT EACH SUPPLY OUTLET. CITY
 AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE SIZE OF THE SUPPLY DUCT FROM THE A/H TO
 THE DISTRIBUTION BOX BY THE FIREPLACE AND THE SIZE OF
 THE SUPPLY DUCT TO THE PANTRY ON THE PLANS. CITY
 AMENDMENTS 107.3.5.3
  
 4) LABEL THE ROOM TYPES ON THE PLANS. (IE BEDROOM,
 MASTER SUITE, ETC.) CITY AMENDMENTS 107.2.1 & 107.3.5.3
  
 5) SPECIFY THE SIZE OF THE RETURN AIR DUCT. CITY
 AMENDMENTS 107.3.5.3
  
 6) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR.
  
 7) THE PLANS HAVE WHAT APPEARS TO BE A DISCONNECT IN
 THE ROOM IN FRONT OF THE FIREPLACE. PLEASE CLARIFY.
 CITY AMENDMENTS 107.2.1
  
 8) A DISCONNECT AND APPLIANCE SERVICE RECEPTACLE OUTLET
 WILL BE REQUIRED FOR THE RELOCATED CONDENSING UNIT. NEC
 440.11 & 210.63
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-07-26 Cont ID  
Sent By rmcdouga Date 2014-07-26 Time 06:43 Rev Time 0.00
Received By rmcdouga Date 2014-07-26 Time 06:43 Sent To  
Notes
2014-07-26 06:45:14APPROVED WITH EXCEPTIONS. MAKE CORRECTIONS NOTED ON
 PLANS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-11 Cont ID  
Sent By rmcdouga Date 2014-06-11 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2014-06-11 Time 08:31 Sent To  
Notes
2014-06-11 10:45:58REDLINED PLANS

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-11 Cont ID  
Sent By sgraham Date 2014-06-11 Time 11:40 Rev Time 0.00
Received By sgraham Date 2014-06-11 Time 11:40 Sent To  
Notes
***NONE***