| Notes |
| 2014-06-16 09:27:04 | DATE: 6/16/2014 | | | PROJECT: TEMP POLE 101 CHURCHILL | | | PERMIT#: 14060340 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO. | | | | | | 1) AMPACITY FOR CONDUCTORS RATED 0-2000 VOLTS SHALL BE | | | AS SPECIFIED IN THE ALOWABLE AMACITY TABLE 310.16. | | | TABLE 310.15(B)(6) DOES NOT APPLY FOR TEMPORARY | | | CONSTRUCTION SERVICES. THIS CHART IS DESIGNED SOLELY | | | FOR 120/240VOLT 3-WIRE, SINGLE PHASE DWELLING SERVICES | | | AND FEEDERS ONLY. | | | | | | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER. PX3421, | | | 561-805-6717, [email protected] |
|
|