| 2014-06-16 11:23:57 | DATE: 6/16/2014 |
| | PROJECT: ADAM - SUN ROOM |
| | PERMIT#: 14060303 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO. |
| | |
| | 1) ALL 120V SINGE PHASE 15 AND 20AMP BRANCH CIRCUITS |
| | SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER |
| | COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF |
| | THE BRANCH CIRCUIT. NEC 210.12(B) SEE ALSO 406.11 |
| | |
| | 2) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES, WITH ELECTRIC POWER AT LEAST AT LEAST ONE WALL |
| | SWITCH CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO |
| | PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR |
| | ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. NEC |
| | 210.70(2)(B) |
| | |
| | 3) FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT |
| | GRADE LEVEL AND LOCATED NOT MORE THAN 61/2FT ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND THE BACK OF |
| | THE DWELLING. UNLESS THERE IS ALREADY AN EXISTING |
| | RECEPTACLE OUTLET AT THE REAR OF THE DWELLING. NEC |
| | 210.52(E)(1) SEE ALSO 210.8(A)(3), 406.8(B), 406.11 |
| | |
| | 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 |
| | |