Plan Review Details - Permit 14060286
Plan Review Stops For Permit 14060286
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-09-18 Cont ID  
Sent By jwitmer Date 2014-09-18 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2014-09-18 Time 08:30 Sent To  
Notes
2014-09-18 09:07:50BUILDING PLAN REVIEW
 PERMIT: 14060286
 ADD: 1220 ORTEGA RD
 CONT: WILBUR HOBGOOD CONST.
 TEL: (561)691-9686
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS,
 AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SEPT. 18/ 2014
 ACTION: BUILDING PROVISO
  
 A SEPARATE ROOFING PERMIT & REVIEW REQUIRED.
 ROOFING PRODUCT APPROVAL : 13-0529.14
 JOHN MANVILLE MODIFIED BITUMEN OVER WOOD DECK
 NO SUB-SYSTEM WAS IDENTIFIED, WILL NEED TO SELECT A
 SUB-SYSTEM BETWEEN
 PAGES 10-26. NOTE PRESSURES ARE GOOD FOR ZONE # 1 BUT
 WILL REQUIRE
 ENHANCED FASTENING IN ZONES 2 & 3. SEE IF LIMITATION 7
 OR 9 APPLIES.
  
 PAGE 27 LIMITATION # 7 REQUIRES RAS 117 CALCULATIONS TO
 BE COMPLETED BY
 EITHER AN ARCHITECT OR ENGINEER REGISTERED WITH THE
 STATE OF FLORIDA.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-08-18 Cont ID  
Sent By jdariton Date 2014-08-18 Time 15:21 Rev Time 0.00
Received By jdariton Date 2014-08-18 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 07:22 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 06:01 Sent To  
Notes
2014-07-01 07:22:52BUILDING PLAN REVIEW
 PERMIT: 14060286
 ADD: 1220 ORTEGA RD
 CONT: WILBUR HOBGOOD CONST.
 TEL: (561)691-9686
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 01/ 2014
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) SHEET A-5:
 2A) 2010 FBC-B 1008.1.6 OR 1009.5 STAIRWAY LANDINGS.
 THE RIGHT SIDE OF THE SHEET DOORWAY FROM STORAGE THE
 DOOR SWINGS OUT OVER THE STAIRS FROM SHEET A2 THE
 LANDING APPEARS TO HAVE BEEN LENGHTENED BUT NOT TO CODE
 COMPLIANCE. THE OTHER ISSUE WITH THIS STAIR IS THAT IT
 MAY NOT REGUIRE A GAURDRAIL THESE STAIRS DO REQUIRE A
 HANDRAIL PER SECTION 2010 FBC-B 1009.12.
  
 2B) THE NEW ACCESS RAMP SHOWS A FOOTER DETAIL SHEET A7
 AS (F4) THIS DETAIL SHOWS EDGE PROTECTION BUT NOT A
 HANDRAIL NOR GAURD RAIL AS REQUIRED BY FBC-B 1010.8 AND
 1010.10. NOTE FLOOR ELEVATIONS IN REGARDS TO GRADE ARE
 NOT GIVEN. THE EXISING STAIR HAS 6 RISERS @ 7 IN= 42
 INCHES IN HEIGHT. NOTE SHEET A6 SHOWS THE NEW
 ACCESSIBLE RAMP AT A LOWER LEVEL THAN THE EXISTING
 STRUCTURE WHERE AS SHEET A7 FOOTER DETAIL F2 SHOWS THE
 FLOORS AT THE SAME LEVEL. DISCREPANCY IN PLANS.
  
 2C) THE NEW ACCESSIBLE RESTROOM DOES NOT MEET THE
 ACCEESSIBLE RESTROOMDIMENSIONAL REQUIREMENTS. THERE IS
 A DISCREPANCY IN THE PLANS SHEET A5 SHOWS A DIMENTION
 OF 6'-10" SHEET DETAIL ON SHEET A9 SHOWS THIS SAME WALL
 5'-9". THE MINIMUM DIMENSION FOR THE FIXTURE SET WALL
 IS 7'-01/2". 2010 FBC- ACCESSIBILITY CODE 604.2 &
 604.3.2 & FIGURE 604.8.1.6.
  
  
 3) SHEET A7 PLEASE REVIEW BEAM TAG C, IS THIS BEAM 84
 INCHES DEEP OR IS THIS A TYPO? 107.2.1.3. ADITIONAL
 INFORMATION IS REQUIRED.
  
 4) SHEET A-8 ADDITIONAL INFORMATION REQUIRED A8 VERSES
 A6, THE PLANS DO NOT PROVIDE EITHER AN INTERMEDIATE TIE
 BEAM OR LINTEL.
 5 DOORS ARE DRAWN TO A 7'-0" ELEVATION
 1 DOOR IS INDICATED TO BE AT ELEVATION 10'-0" TOP OF
 BEAM
 ROOF ELEVATION IS INDICATED AT 12'-0" TOP OF BEAM OR
 12'-9" APPPROX.
 SECTION THROUGH ROOF A-8 MIN ABOVE 14'-0" ABOVE
 LANDING, THERE IS A DISCREPANCY IN THE DETAIL AND
 ELEVATION SHEET A6.
  
 5) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 6A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 MISSING REPORTS:
 (31)(B) WINDOW REPORT ONLY COVER SHEET SUBMITTED.
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 7) NO MEP PLANS SUBMITTED!!! OLD SHEETS SHEET SHEET M-1
 INDICATE THE USE OF ROOF STANDS, M2 INDICATES THE ROOF
 STANDS BEING TIED DOWN TO A CONCRETE DECK PLEASE
 PROVIDE LOCATION OR ARE THEY BEING PLACED ON THE NEW
 WOOD DECKS? ADDITIONAL INFORMATION REQUIRED. 107.2.1.3.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2014-06-27 Cont ID  
Sent By jsaez Date 2014-06-25 Time 14:07 Rev Time 0.00
Received By skennedy Date 2014-06-25 Time 14:01 Sent To  
Notes
2014-06-25 14:10:321.NO MECHANICAL PLANS, ENERGY CAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-10-17 Cont ID  
Sent By dhayes Date 2014-10-17 Time 14:20 Rev Time 0.00
Received By dhayes Date 2014-10-17 Time 14:20 Sent To M
Notes
2014-10-17 14:24:19PROVISO
  
 VERIFY GROUNDING ELECTRODE SYSTEM IS INSTALLED PER NEC
 250.50
 VERIFY GROUNDING ELECTRODE CONDUCTOR IS ADAQUATE FOR
 SERVICE ENTRANCE CONDUCTORS PER NEC 250.66.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-09-08 Cont ID  
Sent By sciard Date 2014-09-08 Time 13:03 Rev Time 0.00
Received By sciard Date 2014-09-08 Time 13:03 Sent To  
Notes
2014-09-08 13:05:42WPB CHAPTER 1 107.3.5.1.2 N.E.C. 215.5. PROVIDE FEEDER
 DIAGRAM TO PANEL "A" AND LOAD CALCULATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-30 Cont ID  
Sent By dhayes Date 2014-06-30 Time 16:24 Rev Time 0.00
Received By dhayes Date 2014-06-30 Time 16:24 Sent To  
Notes
2014-06-30 17:03:28DATE: 6/30/2014
 PROJECT: ERNESTON
 PERMIT#: 14060236
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 THE ADDITION INDICATES NO ELECTRICAL WORK AT ALL. BUT
 THE FLOOR PLAN INDICATES THE INSTALLATION OF NEW OFFICE
 AND BATHROOM AREAS.
  
 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. FBC 107.2.1
  
 2) INDICATE ALL LIGHTS AND RECEPTACLE OUTLETS PROPOSED
 FOR THE NEW CONSTRUCTION AREA. FBC 107.2.1
  
 3) A SWITCHED LIGHT OUTLET IS REQUIRED AT THE ATTIC
 ENTRANCE. FBC 306.3.1
  
 4) AN ILLUMINATED MEANS OF EGRESS SHALL BE PROVIDED FOR
 ALL BUILDINGS OR STRUCTURES REQUIRED IN CHAPTERS 11
 THROUGH 43. NFPA 101 SECTION 7.9
  
 5) MEANS OF EGRESS SHALL BE MARKED WHERE REQUIRED IN
 CHAPTERS 11 THROUGH 43. NFPA 101 SECTION 7.10
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-07-11 Cont ID  
Sent By mgonzale Date 2014-07-11 Time   Rev Time  
Received By mgonzale Date 2014-07-11 Time   Sent To  
Notes
2014-07-11 15:11:52NO OBJECTION:
  
 PLANS FOR ROW IMPROVEMENTS AND UTILTIIES CONNECTIONS
 WILL BE PERMITTED THRU ENGINEERING SERVICES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-11 Cont ID  
Sent By pleduc Date 2014-06-11 Time   Rev Time 0.00
Received By pleduc Date 2014-06-11 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-20 Cont ID  
Sent By hmoser Date 2014-10-20 Time 14:40 Rev Time 0.00
Received By hmoser Date 2014-10-16 Time 14:20 Sent To  
Notes
2014-10-17 14:41:10TO H.M'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-08 Cont ID  
Sent By sciard Date 2014-09-08 Time 13:33 Rev Time 0.00
Received By sciard Date 2014-08-08 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-11 Cont ID  
Sent By skennedy Date 2014-07-11 Time 17:13 Rev Time 0.00
Received By skennedy Date 2014-06-09 Time 12:40 Sent To  
Notes
2014-06-10 12:40:44C25
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-09-18 Cont ID  
Sent By jwitmer Date 2014-09-18 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2014-09-18 Time 08:30 Sent To  
Notes
2014-09-18 08:31:32BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 07:29 Sent To  
Notes
2014-07-01 07:30:29BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-10-20 Cont ID  
Sent By hmoser Date 2014-10-20 Time 14:39 Rev Time 0.00
Received By hmoser Date 2014-10-20 Time 14:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-08-18 Cont ID  
Sent By jdariton Date 2014-08-18 Time 15:20 Rev Time 0.00
Received By jdariton Date 2014-08-18 Time 15:20 Sent To  
Notes
2014-08-18 15:20:088/18/14.
 NOTES:
 1.PROVIDE OUTSIDE AIR BASED ON THE TOTAL OCCUPANT LOAD
 AND AS REQUIRED BY FMC, TABLE 403.3 OR ASHRAE
 62.1-2004.USE EQUATION 4-1 AS REQUIRED BY SEC.403.1.1.
 2.SHOW DISCHARGE LOCATION OF THE CONDENSATE DRAIN AS
 REQUIRED BY SEC.307 OF THE FMC AND SEC.1503.7 OF THE
 FBC.
 3.PROVIDE ON PLANS COMPLETE DETAIL OF THE INSTALLATION
 OF THE AIR HANDLING UNIT AND THE CONDENSING UNIT.
 4.SHOW ON PLANS HOW THE CONDENSING UNIT STAND IS
 ATTACHED TO ROOF STRUCTURE AND THE UNIT TO THE STAND.
 5.SHOW ON PLANS AUTOMATIC SHUTOFF DAMPER AS REQUIRED BY
 FEC SEC.503.2.4.4 AND 503.2.5.4.
 6.PROVIDE ON PLANS COMPLETE A/C SCHEDULE WITH ALL THE
 INFORMATION.
 7.SELECT HVAC SYSTEMS AND EQUIPMENT IN ACCORDANCE WITH
 FEC SEC.503.2.1 AND 503.2.2.
 8.PROVIDE FLOAT SWITCH AS REQUIRED BY FMC SEC. 307.2.3.
 9.SHOW ON PLANS THE LOCATION OF EF-2.
 10.SHOW ON PLANS COMPLIANCE TO INTAKE OPENINGS AS
 REQUIRED BY FMC,SEC.401.4 AND THE EXHAUST OUTLETS AS
 PER FMC,SEC.501.2.1.
  
 REVIEWED BY JOHN ARITON. PLEASE CALL HAROLD MOSER AT
 561-805-6732 IF YOU NEED ASSISTANCE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-06-25 Cont ID  
Sent By jsaez Date 2014-06-25 Time 14:07 Rev Time 0.00
Received By jsaez Date 2014-06-25 Time 14:03 Sent To  
Notes
2014-06-25 14:05:071.NO MECHANICAL PLANS, ENERGY CAL.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-01 Cont ID  
Sent By tklarge Date 2014-09-01 Time 10:13 Rev Time 0.00
Received By tklarge Date 2014-09-01 Time 10:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 06:01 Sent To  
Notes
2014-07-01 07:24:11PLUMBING PLAN REVIEW
 PERMIT: 14060286
 ADD: 1220 ORTEGA RD
 CONT: WILBUR HOBGOOD CONST.
 TEL: (561)691-9686
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 01/ 2014
 ACTION: DENIED
  
 1) THE NEW ACCESSIBLE RESTROOM DOES NOT MEET THE
 ACCEESSIBLE RESTROOMDIMENSIONAL REQUIREMENTS. THERE IS
 A DISCREPANCY IN THE PLANS SHEET A5 SHOWS A DIMENTION
 OF 6'-10" SHEET DETAIL ON SHEET A9 SHOWS THIS SAME WALL
 5'-9". THE MINIMUM DIMENSION FOR THE FIXTURE SET WALL
 IS 7'-01/2". 2010 FBC- ACCESSIBILITY CODE 604.2 &
 604.3.2 & FIGURE 604.8.1.6.
  
 2) 2010 WEST PALM BEACH CHAPTER 1 ADMINISTRATION LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 6. VENTS
 13. PLUMBING RISER
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-16 Cont ID  
Sent By dkittred Date 2014-06-16 Time 13:46 Rev Time 0.00
Received By jroach Date 2014-06-13 Time 11:46 Sent To  
Notes
2014-06-13 11:23:086/13/14