Plan Review Details - Permit 14060247
Plan Review Stops For Permit 14060247
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-23 Cont ID  
Sent By jgomez Date 2014-07-22 Time 16:48 Rev Time 0.00
Received By jgomez Date 2014-07-22 Time 16:48 Sent To  
Notes
2014-07-22 16:55:45 
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-02 Cont ID  
Sent By jgomez Date 2014-07-01 Time 14:34 Rev Time 0.00
Received By jgomez Date 2014-07-01 Time 14:33 Sent To  
Notes
2014-07-01 14:33:57RESIDENTIAL (R2) ALTERATION/ADDITION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SHEET A-2:
 A) ENGINEER TO CORRECT ALL THE CODE INFORMATION. *THIS
 IS A MULTIFAMILY RESIDENTIAL BUILDING WITH 4 UNITS
 (R2). THIS IS NOT AN ENCLOSED SINGLE FAMILY ADDITION,
 THEREFORE, THE FLORIDA RESIDENTIAL CODE DOESN'T APPLY.
 ** THIS IS NOT R3 OCCUPANCY. *** THIS IS NOT AN
 ALTERATION LEVEL 2. SEE CHAPTER 4 OF FBC-EXISTING
 BUILDING AND IDENTIFY CORRECT ALTERATION LEVEL. ALSO,
 CONSIDER THAT THERE IS AN ADDITION SHOWN ON THE PLANS
 SUBMITTED. REVISE ALL THE INFORMATION AS REQUIRED.
  
 B) ENGINEER TO PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR THE NEW PROPOSED ENTRY DOOR AND THE
 NEW PROPOSED SLIDING GLASS DOORS (INCLUDING THE DOOR
 STRUCTURAL BUCK INFORMATION) . SEC. 1403.3 AND SEC.
 1715.5.4 OF 2010 FBC.
  
 2- ENGINEER TO REVISE THE BALCONY GUARDRAIL HEIGHT
 SPECIFICATIONS ON ALL FLOOR PLANS AND ELEVATIONS.
 MINIMUM HEIGHT IS 42" AS REQUIRED BY SEC. 1013.2 OF
 2010 FBC.
 ***NOTE: TAKE THIS HEIGHT IN CONSIDERATION AT THE NEW
 ENTRY AREA WHERE 2 NEW STEPS WERE ADDED TO ALLOW FOR
 THE COVERED ENTRY HEADROOM CLEARANCE ON FIRST FLOOR.
  
 3- ENGINEER TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE WEATHER PROTECTION OF THE ROOF
 DECK (BALCONY) AS REQUIRED BY SEC. 1503 OF 2010 FBC.
 SPECIFY DECK APPROVED COVERING, FLASHING, DRAINAGE AND
 SECONDARY EMERGENCY DRAINS OR SCUPPERS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) THE ROOF DECK APPROVED COVERING. NOTE: COORDINATE
 WITH ITEM # 3 ABOVE.
  
 B) ENTRY DOOR. PROVIDE COMPLETE DRAWINGS FOR FLORIDA
 PRODUCT APPROVAL FL16537 SUBMITTED. NO DRAWINGS
 SUBMITTED THIS TIME
  
 C) HORIZONTAL SLIDING WINDOWS. PROVIDE COMPLETE
 DRAWINGS. DRAWINGS ON NOA 12-0127.08 SUBMITTED ARE
 SPLICED IN DIFFERENT PAGES, THEREFORE, ARE NOT
 READABLE. SUBMIT COMPLETE DRAWINGS.
  
 D) FIXED WINDOWS. NOA 12-0307.06 SUBMITTED. SAME
 COMMENT AS ABOVE. NEED COMPLETE DRAWINGS.
  
 E) SLIDING GLASS DOORS. NOA 12-1204.12 SUBMITTED. SAME
 COMMENT AS ABOVE. NEED COMPLETE DRAWINGS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2014-07-18 Cont ID  
Sent By jgomez Date 2014-07-22 Time 17:06 Rev Time 0.00
Received By dhayes Date 2014-07-18 Time 10:17 Sent To B
Notes
2014-07-18 10:21:32DATE: 7/18/2014
 PROJECT: 5015 N. FLAGLER DR. ENTRY FOYER RENNOVATION
 PERMIT#: 14060247
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
  
 THERE ARE NO ELECTRICAL PLANS OR DETAILS IN THIS
 SUBMITTAL PACKAGE.
  
 A SEPARATE ELECTRICAL PERMIT APPLICATION ACCOMPANIED BY
 A CLEARLY DEFINED SCOPE OF WORK AND AN ELECTRICAL PLAN
 SHALL BE SUBMITTED PRIOR TO THE COMMENCEMENT OF ANY
 ELECTRICAL WORK.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-06-23 Cont ID  
Sent By skennedy Date 2014-06-23 Time 13:49 Rev Time 0.00
Received By skennedy Date 2014-06-23 Time 13:49 Sent To  
Notes
2014-06-23 13:49:33BY SEPARATE SUBMITTAL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-12 Cont ID  
Sent By albarran Date 2014-06-12 Time 11:32 Rev Time 0.00
Received By albarran Date 2014-06-12 Time 10:09 Sent To  
Notes
2014-06-12 11:41:56THE ELECTRICAL PLANS REVIEW FAILED AS INDICATED BELOW:
 1. THE SCOPE OF WORK IS NOT CLEARLY DEFINED.
 2. THERE IS NO ELECTRICAL PAGE.
  
 PLEASE BE MORE SPECIFIC AS TO THE SCOPE OF WORK SO THAT
 MINIMAL ELECTRICAL REQUIREMENTS CAN BE ESTABLISHED.
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-07-24 Cont ID  
Sent By fmittner Date 2014-07-24 Time 15:20 Rev Time 0.00
Received By fmittner Date 2014-07-24 Time 15:20 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-06-06 Cont ID  
Sent By fmittner Date 2014-06-06 Time 13:47 Rev Time 0.00
Received By fmittner Date 2014-06-06 Time 13:47 Sent To  
Notes
2014-06-06 13:48:37APPROVED BY HPB CASE NO. 14-31 FOR 5015 NORTH FLAGLER
 DRIVE FOR ADDITIONS / ALTERATIONS TO THE PORCH AND THE
 WINDOW AS PRESENTED ON THE PLANS PRESENTED TO THE
 BOARD. THIS MOTION IS BASED UPON THE APPLICATION
 SUBMITTED AS WELL AS THE STAFF RECOMMENDATION AND THE
 STAFF REPORT WHICH CONSTITUTE COMPETENT, SUBSTANTIAL
 EVIDENCE. THE APPLICATION IS IN COMPLIANCE WITH THE
 SECRETARY OF THE INTERIOR?S STANDARDS, SPECIFICALLY
 STANDARDS 9 AND 10, AS WELL AS THE CITY OF WEST PALM
 BEACH ZONING CODE. THIS MOTION IS BASED UPON THE
 CONDITION THAT:
 1) THE GLASS AND THE SLIDERS SHALL BE A CLEAR GLASS OR
 A LOW E GLASS, AND NOT A TINTED GLASS, WITH THE GLASS
 TO BE APPROVED BY STAFF, WITH THE TINTING PERHAPS ON
 THE LOW E EITHER THE GREEN OR THE BLUE, AT STAFF?S
 DISCRETION.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-22 Cont ID  
Sent By jwitmer Date 2014-07-22 Time 17:06 Rev Time 0.00
Received By jgomez Date 2014-07-17 Time 06:28 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-01 Cont ID  
Sent By jgomez Date 2014-07-01 Time 14:34 Rev Time 0.00
Received By jgomez Date 2014-06-06 Time 15:44 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-06-23 Cont ID  
Sent By skennedy Date 2014-06-23 Time 13:46 Rev Time 0.00
Received By skennedy Date 2014-06-23 Time 13:46 Sent To  
Notes
2014-06-23 13:48:35BY SEPARATE SUBMITTAL

Review Stop Z ZONING
Rev No 2 Status P Date 2014-07-24 Cont ID  
Sent By fmittner Date 2014-07-24 Time 15:20 Rev Time 0.00
Received By fmittner Date 2014-07-24 Time 15:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-06 Cont ID  
Sent By fmittner Date 2014-06-06 Time 13:48 Rev Time 0.00
Received By fmittner Date 2014-06-06 Time 13:48 Sent To  
Notes
***NONE***