| 2014-07-01 14:33:57 | RESIDENTIAL (R2) ALTERATION/ADDITION, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- SHEET A-2: |
| | A) ENGINEER TO CORRECT ALL THE CODE INFORMATION. *THIS |
| | IS A MULTIFAMILY RESIDENTIAL BUILDING WITH 4 UNITS |
| | (R2). THIS IS NOT AN ENCLOSED SINGLE FAMILY ADDITION, |
| | THEREFORE, THE FLORIDA RESIDENTIAL CODE DOESN'T APPLY. |
| | ** THIS IS NOT R3 OCCUPANCY. *** THIS IS NOT AN |
| | ALTERATION LEVEL 2. SEE CHAPTER 4 OF FBC-EXISTING |
| | BUILDING AND IDENTIFY CORRECT ALTERATION LEVEL. ALSO, |
| | CONSIDER THAT THERE IS AN ADDITION SHOWN ON THE PLANS |
| | SUBMITTED. REVISE ALL THE INFORMATION AS REQUIRED. |
| | |
| | B) ENGINEER TO PROVIDE COMPLETE FRAMING DETAILS AND |
| | SPECIFICATIONS FOR THE NEW PROPOSED ENTRY DOOR AND THE |
| | NEW PROPOSED SLIDING GLASS DOORS (INCLUDING THE DOOR |
| | STRUCTURAL BUCK INFORMATION) . SEC. 1403.3 AND SEC. |
| | 1715.5.4 OF 2010 FBC. |
| | |
| | 2- ENGINEER TO REVISE THE BALCONY GUARDRAIL HEIGHT |
| | SPECIFICATIONS ON ALL FLOOR PLANS AND ELEVATIONS. |
| | MINIMUM HEIGHT IS 42" AS REQUIRED BY SEC. 1013.2 OF |
| | 2010 FBC. |
| | ***NOTE: TAKE THIS HEIGHT IN CONSIDERATION AT THE NEW |
| | ENTRY AREA WHERE 2 NEW STEPS WERE ADDED TO ALLOW FOR |
| | THE COVERED ENTRY HEADROOM CLEARANCE ON FIRST FLOOR. |
| | |
| | 3- ENGINEER TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE WEATHER PROTECTION OF THE ROOF |
| | DECK (BALCONY) AS REQUIRED BY SEC. 1503 OF 2010 FBC. |
| | SPECIFY DECK APPROVED COVERING, FLASHING, DRAINAGE AND |
| | SECONDARY EMERGENCY DRAINS OR SCUPPERS. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) THE ROOF DECK APPROVED COVERING. NOTE: COORDINATE |
| | WITH ITEM # 3 ABOVE. |
| | |
| | B) ENTRY DOOR. PROVIDE COMPLETE DRAWINGS FOR FLORIDA |
| | PRODUCT APPROVAL FL16537 SUBMITTED. NO DRAWINGS |
| | SUBMITTED THIS TIME |
| | |
| | C) HORIZONTAL SLIDING WINDOWS. PROVIDE COMPLETE |
| | DRAWINGS. DRAWINGS ON NOA 12-0127.08 SUBMITTED ARE |
| | SPLICED IN DIFFERENT PAGES, THEREFORE, ARE NOT |
| | READABLE. SUBMIT COMPLETE DRAWINGS. |
| | |
| | D) FIXED WINDOWS. NOA 12-0307.06 SUBMITTED. SAME |
| | COMMENT AS ABOVE. NEED COMPLETE DRAWINGS. |
| | |
| | E) SLIDING GLASS DOORS. NOA 12-1204.12 SUBMITTED. SAME |
| | COMMENT AS ABOVE. NEED COMPLETE DRAWINGS. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |