Plan Review Details - Permit 14060196
Plan Review Stops For Permit 14060196
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-29 Cont ID  
Sent By jwitmer Date 2014-08-29 Time 09:24 Rev Time 0.00
Received By jwitmer Date 2014-08-29 Time 05:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-26 Cont ID  
Sent By jwitmer Date 2014-07-26 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2014-07-26 Time 09:30 Sent To  
Notes
2014-07-26 11:09:08BUILDING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. JULY 26/2014
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3)2ND REQUEST. SHEET A0.08 LIFE SAFETY PLANS:MISSING
 PLAN REVIEW CRITERIA:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS OR NET TABLE FBC-B 1004.1.1. PER FLOOR
  
 4) THE STRUCTURAL WORK ON THIS BUILDING ISCLASSIFYING
 IT AS A :THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 4A) COMPLIED.
  
 4B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. A THRESHOLD AGREEMENT WILL NEED TO BE SIGNED BY
 ALL PARTIES, PLEASE PROVIDE A E-MAIL ADDRESS THAT WE
 CAN SEND ALL THE REQUIRED DOCUMENTS.
  
 4C) COMPLIED.
  
  
 4D) CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 OR [email protected] FOR FURTHER
 INFORMATION:
  
 4D) (1) COMPLIED. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4D) (2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 5) COMPLIED.
  
 6) SHEET 015 A1.10 LEVEL 15:
  
 6A) DOOR # 1502 APPEARS TO HAVE ONLY 16 1/2 INCHES ON
 THE LATCH SIDE OF THE DOOR, SEE 2010 FL ACC CODE FIGURE
 404.2.4.1. (A).
  
 6B) COMPLIED.
  
 6C) COMPLIED.
  
 7) 2ND REQUEST ,RESPONSE INDICATES DETAILS FOR FIRE
 RESISTANCE IS FOUND ON SHEET A0.04. THERE ARE NO
 DETAILS SHOWING CODE COMPLIANCE.
 STRUCTURAL SHEETS SHOW STEEL FRAMING MEMBERS, THIS IS A
 TYPE 1A BUILDING SHOW COMPLIANCE WITH TABLE 603 WITH
 REQUIRED FIRE RESISTANCE RATING REQUIREMENTS FOR
 BUILDING ELEMENTS (HOURS) PROVIDE THICKENESS AND HOUR
 RATING.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 NOTE THERE ARE ALOT OF THE REQUIRED DOCUMENTS PRODUCT
 APPROVALS AND MANUFACTURERS SPECIFICATIONS THAT WERE
 LOADED INTO THE RESPONSE FOLDER RATHER THAN A SEPARATE
 DOCUMENT FOLDER. I'LL BE CHECKING IF OUR LIBRIAN WILL
 BE ABLE TO TRANSFER THESE ITEMS INTO THE CORRECT
 FOLDER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-07 Cont ID  
Sent By jwitmer Date 2014-07-07 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2014-07-07 Time 11:51 Sent To  
Notes
2014-07-07 12:33:58BUILDING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 07/2014
 ACTION: DENIED
  
 1) THE PLANS DO NOT PROVIDE THE ADDRESS WHERE THE WORK
 IS TO OCCUR. FL S 61G-16.004(3) LOCATION OF PROJECT.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) THE SCOPE OF THIS PROJECT WILL NEED SOME EXPLAINING.
 THE PERMIT APPLICATION INDICATES WORK TO BE
 ACCOMPLISHED UNDER THIS PERMIT ON THE 12TH & 13TH
 FLOORS. WHERE AS PLANS INDICATE 007-A0.07 12-14 FLOORS,
 011-A1.04 DEMO 15TH FLOOR & 015-A1.10 CONSTRUCTION
 PLANS FOR THE 15TH LEVEL. IS THIS A PHASED PERMIT OR IS
 THE SCOPE OF WORK TO INCLUDE ALL THESE FLOORS?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET A0.08 LIFE SAFETY PLANS:MISSING PLAN REVIEW
 CRITERIA:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS OR NET TABLE FBC-B 1004.1.1. PER FLOOR
  
 4) THE STRUCTURAL WORK ON THIS BUILDING ISCLASSIFYING
 IT AS A :THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 4A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 4B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. A THRESHOLD AGREEMENT WILL NEED TO BE SIGNED BY
 ALL PARTIES, PLEASE PROVIDE A E-MAIL ADDRESS THAT WE
 CAN SEND ALL THE REQUIRED DOCUMENTS.
  
 4C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
  
 4D) CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 OR [email protected] FOR FURTHER
 INFORMATION:
 4D) (1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 4D) (2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 4E) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 4F) A COLLOR COPY OF THE PLANS WILL BE REQUIRED AT THE
 JOBSITE FOR CITY INSPECTORS & A SECOND COLOR COPY FOR
 THE THRESHOLD INSPECTOR.
  
 4G) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 5) SHEET 013 A1.09:
 5A) ROOM 1405, THE PRIVATE EXECUTIVE RESTROOM, IT
 APPEARS THERE ARE CURVED WALLS WITH A POCKET DOOR, IT
 APPEARS THE POCKET IS OUTSIDE OF THE WALL. 107.2,1,3
 ADDITIONAL INFORMATION REQUIRED.
  
 5B) PRIVATE ELEVATOR SWING DOOR 1406 ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE
 HALF OF THE REQUIRED WIDTH OF THE PASSAGEWAY. 2010
 FBC-B 1008.1.9.11.
  
 5C) EXTERIOR BALCONY 1450A NOTE FOR NEW BALCONIES SHALL
 BE AMERICAN HYDROTECH CONCRETE PAVER SYSTEM NOA
 08-0422.12 NOTE THIS IS NOT A PAVER SYSTEM BUT A
 WATERPROOFING SYSTEM. THIS IS A EXPIRED NOA . PLEASE
 PROVIDE A CURRENT APPROVAL AND TYPE OF DECKING SYSSTEM
 THAT WILL BE APPLIED ON TOP OF THE WATERPROOFING
 SYSTEM.
  
 5D) SHOWER ROOMS 1432 (MENS) & 1433 (LADIES) BOTH SHOW
 SHOWERS BUT THE PLANS DO NOT INDICATE SIZE OF THE
 SHOWER NOR A SEAT DETAIL AS REQUIRED BY 2010 FL ACC
 CODE 608.2.1.
  
 5E) THE PLANS INDICATE A EXTERIOR DINING AREA (1426)
 PLEASE PROVIDE COMPLIANCE WITH THE 2010 FL
 ACCESSIBILITY CODE 404.2.5 THRESHOLDS.
  
 5F) THE NEW MONUMENTAL STAIRS WILL NEED TO PROVIDE
 DETAILS THAT WILL SHOW COMPLIANCE WITH THE 2010 FBC-B
 708.2 EXCEPTION 2.1 WHERE THE AREA OF THE FLOOR OPENING
 BETWEEN STORIES DOES NOT EXCEED TWICE THE HORIZONTAL
 PROJECTED AREA OF THE ESCALATOR OR STAIRWAY AND THE
 OPENING IS PROTECTED BY A DRAFT CURTAIN AND CLOSELY
 SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13. IN OTHER
 THAN GROUPS B AND M, THIS APPLICATION IS LIMITED TO
 OPENINGS THAT DO NOT CONNECT MORE THAN FOUR STORIES.
  
 6) SHEET 015 A1.10 LEVEL 15:
  
 6A) DOOR # 1502 APPEARS TO HAVE ONLY 16 1/2 INCHES ON
 THE LATCH SIDE OF THE DOOR, SEE 2010 FL ACC CODE FIGURE
 404.2.4.1. (A).
  
 6B) THE GYM IS ON THE 15 FLOOR LEVEL AND ONLY 1 MEANS
 OF EGRESS. PLEASE SEE 2010 FBC-B TABLE 1021.2.
  
 6C) A/C EQUIPMENT HATCH DETAIL # 1 A5.03 PROVIDE THE
 MANUFACTURERS SPECIFICATIONS ON THE ACUDOOR FLOOR DOOR
 PROVIDE FLOOR LOADING TABLE 1607(LBS) AND FIRE RATING
 TABLE 715.4. FOR THE FLOOR DOOR.
  
 7) STRUCTURAL SHEEETS SHOW STEEL FRAMING MEMBERS, THIS
 IS A TYPE 1A BUILDING SHOW COMPLIANCE WITH TABLE 603
 WITH REQUIRED FIRE RESISTANCE RATING REQUIREMENTS FOR
 BUILDING ELEMENTS (HOURS) PROVIDE THICKENESS AND HOUR
 RATING.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-08-27 Cont ID  
Sent By dhayes Date 2014-08-27 Time 15:01 Rev Time 0.00
Received By dhayes Date 2014-08-27 Time 13:34 Sent To  
Notes
2014-08-27 15:01:25DATE: 7/9/2014
 PROJECT: AMG PHILLIPS POINT EXPANSION
 PERMIT#: 14060196
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) BOXES, CONDUIT BODIES, AND HANDHOLE ENCLOSURES SHALL
 BE INSTALLED SO THAT THE WIRING CONTAINED IN THEM CAN
 BE RENDERED ACCESSIBLE WITHOUT REMOVING ANY PART OF THE
 BUILDING OR, IN UNDERGROUND CIRCUITS, WITHOUT
 EXCAVATING SIDEWALKS, PAVING, EARTH, OR OTHER SUBSTANCE
 THAT IS TO BE USED TO ESTABLISH THE FINISHED GRADE. NEC
 314.29. THE POWER PACKS FOR MOTION SENSORS APPEAR TO BE
 LOCATED IN AREAS WITH DRYWALL CEILINGS. ALL
 TRANSFORMERS, LED DRIVERS JUNCTION BOXES, POWER PACK
 AND THE LIKE SHALL BE INSTALLED SO AS TO REMAIN
 ACCESSIBLE AFTER INSTALLATION AND CONSTRUCTION IS
 COMPLETE.
  
 2) PROVIDE PRODUCT APPROVALS FOR ALL FIXTURES. LISTING
 AND LABELING REQUIRED BY AN APPROVED TESTING LAB. IN
 JUDGING EQUIPMENT, CONSIDERATION SUCH AS THE FOLLOWING
 SHALL BE EVALUATED: SUITABILITY FOR INSTALLATION AND
 USE IN CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8)
  
 3) PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR FLOOR
 BOXES TO SHOW CODE COMPLIANCE WITH FIRE RATING FROM
 FLOOR TO FLOOR. ADDITIONAL INFORMATION REQUIRED. FBC
 107.2.1.3
  
 4) PROVIDE MANUFACTURER DATA SHEETS ON THE CEO
 ELEVATOR.
  
 5) WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE AHJ
 SHALL BE NOTIFIED, AND THE BUILDING SHALL BE EVACUATED
 OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL
 PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE
 ALARM SYSTEM HAS BEEN RETURNED TO SERVICE.
 [101:9.6.1.6] NFPA-1, CHAPTER 13 SECTION 13.7.1.4.4
  
 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP
 DRAWINGS AS REQUIRED FOR, FIRE ALARM, SECURITY, ACCESS
 CONTROL, CCTV, DATA/COM, NETWORK, STRUCTURED CABLING,
 AUDIO/VIDEO, AND SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-07-31 Cont ID  
Sent By dhayes Date 2014-07-31 Time 13:06 Rev Time 0.00
Received By dhayes Date 2014-07-31 Time 13:06 Sent To  
Notes
2014-07-31 13:41:27DATE: 7/31/2014
 PROJECT: AMG PHILLIPS POINT EXPANSION
 PERMIT#: 14060196
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE THE LOCATION OF ELEVATOR MACHINE ROOM.
 INDICATE ALL CIRCUITRY AND DISCONNECT FOR MOTOR AND
 CONTROLS AND FIRE ALARM DEVICES REQUIRED IN THE
 ELEVATOR MACHINE ROOM FOR THE PERSONAL CEO ELEVATOR.
  
 2) CLEAR WORKING ACCESS REQUIRED FOR ELECTRICAL
 EQUIPMENT, FEEDING MECHANICAL EQUIPMENT.
  
 6) WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE AHJ
 SHALL BE NOTIFIED, AND THE BUILDING SHALL BE EVACUATED
 OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL
 PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE
 ALARM SYSTEM HAS BEEN RETURNED TO SERVICE.
 [101:9.6.1.6] NFPA-1, CHAPTER 13 SECTION 13.7.1.4.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-10 Cont ID  
Sent By dhayes Date 2014-07-10 Time 16:04 Rev Time 0.00
Received By dhayes Date 2014-07-10 Time 12:27 Sent To  
Notes
2014-07-10 15:03:04DATE: 7/9/2014
 PROJECT: AMG PHILLIPS POINT EXPANSION
 PERMIT#: 14060196
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) BOXES, CONDUIT BODIES, AND HANDHOLE ENCLOSURES SHALL
 BE INSTALLED SO THAT THE WIRING CONTAINED IN THEM CAN
 BE RENDERED ACCESSIBLE WITHOUT REMOVING ANY PART OF THE
 BUILDING OR, IN UNDERGROUND CIRCUITS, WITHOUT
 EXCAVATING SIDEWALKS, PAVING, EARTH, OR OTHER SUBSTANCE
 THAT IS TO BE USED TO ESTABLISH THE FINISHED GRADE. NEC
 314.29. THE POWER PACKS FOR MOTION SENSORS APPEAR TO BE
 LOCATED IN AREAS WITH DRYWALL CEILINGS. ALL
 TRANSFORMERS, LED DRIVERS JUNCTION BOXES, POWER PACK
 AND THE LIKE SHALL BE INSTALLED SO AS TO REMAIN
 ACCESSIBLE AFTER INSTALLATION AND CONSTRUCTION IS
 COMPLETE.
  
 2) PROVIDE PRODUCT APPROVALS FOR ALL FIXTURES. LISTING
 AND LABELING REQUIRED BY AN APPROVED TESTING LAB. IN
 JUDGING EQUIPMENT, CONSIDERATION SUCH AS THE FOLLOWING
 SHALL BE EVALUATED: SUITABILITY FOR INSTALLATION AND
 USE IN CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8)
  
 3) PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR FLOOR
 BOXES TO SHOW CODE COMPLIANCE WITH FIRE RATING FROM
 FLOOR TO FLOOR. ADDITIONAL INFORMATION REQUIRED. FBC
 107.2.1.3
  
 4) IDENTIFY ALL NEW FEEDERS ON THE RISER DIAGRAM.
 ADDITIONAL INFORMATION REQUIRED. FBC 107.2.1.3
  
 5) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3), ALL 15
 AND 20AMP, 125V AND 250V RECEPTACLES INSTALLED IN IN A
 WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS
 WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS
 INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT
 NON-LOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE. NEC 406.8(B)(1)
  
 6) WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE AHJ
 SHALL BE NOTIFIED, AND THE BUILDING SHALL BE EVACUATED
 OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL
 PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE
 ALARM SYSTEM HAS BEEN RETURNED TO SERVICE.
 [101:9.6.1.6] NFPA-1, CHAPTER 13 SECTION 13.7.1.4.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-09-05 Cont ID  
Sent By wjolin Date 2014-09-05 Time 11:37 Rev Time 0.00
Received By wjolin Date 2014-09-05 Time 08:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-07-30 Cont ID  
Sent By wjolin Date 2014-07-30 Time 11:14 Rev Time 0.00
Received By wjolin Date 2014-07-30 Time 09:51 Sent To  
Notes
2014-07-30 11:13:58777 SOUTH FLAGLER DRIVE
 PERMIT #14060196
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: THE ARCHITECTURAL RESPONSE TO PROTECT
 THE VERTICAL OPENING WITH SPRINKLERS IS TAKEN FROM
 CHAPTER 39 (EXISTING BUSINESS) SECTION 39.3.1.1(3). IF
 A MONUMENTAL STAIR WAS EXISTING, THIS WOULD BE
 PERMITTED TO REMAIN; HOWEVER, BECAUSE THIS IS A NEW
 STAIR INSTALLATION THE DESIGN NEEDS TO COMPLY WITH
 CHAPTER 38 (NEW BUSINESS) WHICH REFERENCES SECTION
 8.6.8.2. ALLOWING AN UNPROTECTED STAIR TO BE
 CONSTRUCTED WOULD CREATE A NONCONFORMITY THAT DID NOT
 PREVIOUSLY EXIST. MONUMENTAL STAIR COMMUNICATES
 DIRECTLY WITH CORRIDOR B, CORRIDOR C AND EXIT STAIR
 DOOR. I HAVE SERIOUS CONCERNS THAT SMOKE COULD AFFECT
 OCCUPANTS ABILITY TO EGRESS SAFELY.
  
 ORIGINAL COMMENT: SHEET A1.09: MONUMENTAL STAIR SHALL
 COMPLY WITH SECTION 8.6.8.2 (CONVENIENCE OPENINGS)
 WHEREBY THE FLOOR-TO-FLOOR OPENING IS REQUIRED TO BE
 SEPARATED FROM CORRIDORS AND EXIT ACCESS INTO EXISTING
 EXIT STAIR #1.
  
 RESPONSE COMMENT: DOORS TIED INTO THE FIRE ALARM SYSTEM
 ONLY COMPLIES WITH 1 OF 15 REQUIREMENTS LIST BELOW.
 ORIGINAL COMMENT: SHEET A1.21: ELEVATOR LOBBY DOORS ARE
 EQUIPPED WITH CARD READERS. PER SECTION 7.2.1.6.3, EACH
 ELEVATOR LANDING AND LOBBY SHALL HAVE ACCESS TO AT
 LEAST ON EXIT. EXIT ACCESS SHALL NOT REQUIRE THE USE OF
 A KEY, TOOL, SPECIAL KNOWLEDGE, OR SPECIAL EFFORT.
 DOORS SEPARATING THE ELEVATOR LOBBY FROM THE EXIT
 ACCESS SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED
 IN ACCORDANCE WITH SECTION 7.2.1.6.3 ELEVATOR LOBBY
 EXIT ACCESS DOOR ASSEMBLIES LOCKING: DOOR ASSEMBLIES
 SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS
 SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED,
 PROVIDED THAT ALL THE FOLLOWING CRITERIA ARE MET:
 (1) THE ELECTRONIC SWITCH FOR RELEASING THE LOCK IS
 LISTED IN ACCORDANCE WITH UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE
 ALARM SYSTEM
 (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY
 7.2.1.6.3(3) IS ARRANGED TO INITIATE THE BUILDING FIRE
 ALARM SYSTEM.
 (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED,
 SUPERVISED SMOKE DETECTION SYSTEM
 (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED
 BY 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING
 FIRE ALARM SYSTEM.
 (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY
 OTHER THAN MANUAL FIRE ALARM BOXES UNLOCKS THE ELEVATOR
 LOBBY DOOR ASSEMBLY.
 (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK
 SYSTEM UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (9) THE ELEVATOR LOBBY ELECTRONIC LOCK SYSTEM IS NOT
 SUPPLIED WITH EMERGENCY OR STANDBY ELECTRICAL POWER.
 (10) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES
 REMAIN UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM
 HAS BEEN MANUALLY RESET.
 (11) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN
 LATCHED AFTER BEING UNLOCKED, LATCH-RELEASING HARDWARE
 IS AFFIXED TO THE DOOR LEAVES.
 (12) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR
 COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL
 CONTROL POINT THAT IS CONSTANTLY STAFFED.
 (13) THE CENTRAL CONTROL POINT STAFF REQUIRED BY
 7.2.1.6.3(12) IS CAPABLE, TRAINED, AND AUTHORIZED TO
 PROVIDE EMERGENCY ASSISTANCE.
 (14) THE PROVISIONS OF DELAYED-EGRESS LOCKING SYSTEMS
 ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (15) THE PROVISIONS OF ACCESS-CONTROLLED EGRESS DOOR
 ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-07-02 Cont ID  
Sent By wjolin Date 2014-07-02 Time 13:48 Rev Time 0.00
Received By wjolin Date 2014-06-27 Time 15:47 Sent To  
Notes
2014-06-27 16:31:17777 SOUTH FLAGLER DRIVE
 PERMIT #14060196
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 SHEET A1.09: MONUMENTAL STAIR SHALL COMPLY WITH SECTION
 8.6.8.2 (CONVENIENCE OPENINGS) WHEREBY THE
 FLOOR-TO-FLOOR OPENING IS REQUIRED TO BE SEPARATED FROM
 CORRIDORS AND EXIT ACCESS INTO EXISTING EXIT STAIR #1.
  
 SHEET A1.21: ELEVATOR LOBBY DOORS ARE EQUIPPED WITH
 CARD READERS. PER SECTION 7.2.1.6.3, EACH ELEVATOR
 LANDING AND LOBBY SHALL HAVE ACCESS TO AT LEAST ON
 EXIT. EXIT ACCESS SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, SPECIAL KNOWLEDGE, OR SPECIAL EFFORT. DOORS
 SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS
 SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED IN
 ACCORDANCE WITH SECTION 7.2.1.6.3 ELEVATOR LOBBY EXIT
 ACCESS DOOR ASSEMBLIES LOCKING: DOOR ASSEMBLIES
 SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS
 SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED,
 PROVIDED THAT ALL THE FOLLOWING CRITERIA ARE MET:
 (1) THE ELECTRONIC SWITCH FOR RELEASING THE LOCK IS
 LISTED IN ACCORDANCE WITH UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE
 ALARM SYSTEM
 (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY
 7.2.1.6.3(3) IS ARRANGED TO INITIATE THE BUILDING FIRE
 ALARM SYSTEM.
 (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED,
 SUPERVISED SMOKE DETECTION SYSTEM
 (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED
 BY 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING
 FIRE ALARM SYSTEM.
 (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY
 OTHER THAN MANUAL FIRE ALARM BOXES UNLOCKS THE ELEVATOR
 LOBBY DOOR ASSEMBLY.
 (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK
 SYSTEM UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (9) THE ELEVATOR LOBBY ELECTRONIC LOCK SYSTEM IS NOT
 SUPPLIED WITH EMERGENCY OR STANDBY ELECTRICAL POWER.
 (10) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES
 REMAIN UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM
 HAS BEEN MANUALLY RESET.
 (11) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN
 LATCHED AFTER BEING UNLOCKED, LATCH-RELEASING HARDWARE
 IS AFFIXED TO THE DOOR LEAVES.
 (12) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR
 COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL
 CONTROL POINT THAT IS CONSTANTLY STAFFED.
 (13) THE CENTRAL CONTROL POINT STAFF REQUIRED BY
 7.2.1.6.3(12) IS CAPABLE, TRAINED, AND AUTHORIZED TO
 PROVIDE EMERGENCY ASSISTANCE.
 (14) THE PROVISIONS OF DELAYED-EGRESS LOCKING SYSTEMS
 ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (15) THE PROVISIONS OF ACCESS-CONTROLLED EGRESS DOOR
 ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
  
 SHEET A6.01: PLAN INDICATES WOOD VENEER TO BE APPLIED
 TO EXISTING STAIR DOORS. EXISTING FIRE RATED STAIR
 DOORS ARE NOT PERMITTED TO BE ALTERED UNLESS
 SPECIFICALLY LISTED.
  
 FS1.1: PROVIDE ORDINARY HAZARD SPRINKLER DENSITIES FOR
 12TH FLOOR STORAGE ROOM AND 14TH FLOOR STORAGE #1418.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-09-08 Cont ID  
Sent By skennedy Date 2014-09-08 Time 11:53 Rev Time 0.00
Received By skennedy Date 2014-08-18 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-12 Cont ID  
Sent By hmoser Date 2014-08-12 Time 10:56 Rev Time 0.00
Received By hmoser Date 2014-07-23 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-14 Cont ID  
Sent By hmoser Date 2014-07-14 Time 15:55 Rev Time 0.00
Received By hmoser Date 2014-06-13 Time 10:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-08-12 Cont ID  
Sent By hmoser Date 2014-08-12 Time 10:55 Rev Time 0.00
Received By hmoser Date 2014-08-12 Time 08:37 Sent To  
Notes
2014-08-12 10:53:51HOOD AND COOLERS REQUIRE SEPARATE APPLICATION, PLANS
 AND PERMIT
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 5614-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-14 Cont ID  
Sent By hmoser Date 2014-07-14 Time 15:54 Rev Time 0.00
Received By hmoser Date 2014-07-02 Time 12:57 Sent To  
Notes
2014-07-14 15:54:32PLAN DENIED
 1) SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED FOR
 HOOD
 AND GREASE DUCT. 107 FBC 2010
 2) PAGE M3.0 12TH. FLOOR MISSING DUCT SIZE. 107 FBC
 2010
 3) PAGE M3.2 14TH FL. TWO SEPARATE VAV BOXES SERVING
 ONE GRILL
 IN TWO OR MORE LOCATIONS, SIZE RETURN AIR DUCT FROM VAV
 BOXES
 4) PAGE M3.3 SAME AS M3.2
 5) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROL
 2010 FLORIDA ENERGY CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX-561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-08-29 Cont ID  
Sent By jwitmer Date 2014-08-29 Time 06:04 Rev Time 0.00
Received By jwitmer Date 2014-08-29 Time 05:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-07-26 Cont ID  
Sent By jwitmer Date 2014-07-26 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2014-07-26 Time 09:40 Sent To  
Notes
2014-07-26 11:06:39PLUMBING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. JULY 26/2014
 ACTION: DENIED
  
 1) 2ND REQUEST, NOTE THAT THIS SAME QUESTION BEING
 ASKED THE 2ND TIME UNDER THE BUILDING REVIEW SINCE THE
 OCCUPANT LOAD COUNT IS NOT FOUND ON THE ARCHITECTURAL
 PLANS. WHERE THE COMMON RESTROOMS ARE BEING DEMOLISHED
 AND REBUILT THE PLANS DO NOT HAVE A OCCUPANT LOAD COUNT
 PER FLOOR NOR DOES P0.1 SHOW COMPLIANCE WITH 2010
 FBC-PLUMBING TABLE 403.1.
  
 2) 2ND REQUEST, RESPONSE COMMENT INDICATES THE
 ACCESIBLE SHOWER DETAIL IS FOUND UNDER SHEET A0.06, NOT
 THERE EITHER. SHEET P2.2:
 2A) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW
 DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE 608.2.1. 36"X36". TRANSFER TYPE
 SHOWER COMPARTMENTS.
  
 2B) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW
 DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS.
  
 2C) COMPLIED>
  
 2D) 2ND REQUEST, THE RESPONCE COMMENT INDICATES SEE
 SHEET P8.1 DETAIL # 11. NOTE THIS DETAIL SHOWS A GREASE
 INTERCEPTOR GT 2701-20 OR EQUAL. SUBMIT THE
 MANUFACTURERS SPECIFICATION SHEETS FOR REVIEW FOR CODE
 COMPLIANCE
 .
 USE OF THE WORD EQUAL SEE 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 THE OTHER ISSUE WITH THIS DETAIL SHOWS THE USE OF AIR
 ADMITTANCE VALVES. THE AIR ADMITTANCE VALVES CAN ONLY
 BE USED:
 917.3.1 LOCATION OF BRANCH.
 THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE
 DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK.
 917.3.2 RELIEF VENT.
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR
 EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE
 STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED
 TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL
 BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL
 BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.
  
 2E) COMPLIED.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-07-08 Cont ID  
Sent By jwitmer Date 2014-07-08 Time 14:39 Rev Time 0.00
Received By jwitmer Date 2014-07-07 Time 11:51 Sent To  
Notes
2014-07-07 16:30:50PLUMBING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 07/2014
 ACTION: DENIED
  
 1) WHERE THE COMMON RESTROOMS ARE BEING DEMOLISHED AND
 REBUILT THE PLANS DO NOT HAVE A OCCUPANT LOAD COUNT PER
 FLOOR NOR DOES P0.1 SHOW COMPLIANCE WITH 2010
 FBC-PLUMBING TABLE 403.1.
  
 2) SHEET P2.2:
 2A) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW
 DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE 608.2.1. 36"X36". TRANSFER TYPE
 SHOWER COMPARTMENTS.
  
 2B) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW
 DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS.
  
 2C) THE 2 SINGLE USER BATHROOMS (SHOWERS) ON THIS SHEET
 AND P5.1 THE SANITARY ISOMETRIC ARE DRAWN AS A
 HORIZONTAL WET WENT. HORIZONTAL WET VENTS ARE TO BE
 USED ONLY IN SINGLE FAMILY RESIDENCE 909.1 AND
 COMMENTARY & BOAF 2007 INFORMAL INTERPRETATION 6090.
 THE OTHER ISSUE WITH THE SHOWER FIXTURE ARM IT EXCEEDS
 THE ALLOWABLE DISTANCE FROM FIXTURE TRAP TO VENT TABLE
 906.1.
  
 2D) THE REMODELING OF THE KITCHEN AND SANITARY DRAINAGE
 THERE IS A COMMERCIAL KITCHEN 3 COMPARTMENT SINK AND NO
 GREASE INTERCEPTOR.
 FBC-P 1003.1 WHERE REQUIRED. INTERCEPTORS AND
 SEPARATORS SHALL BE PROVIDED TO PREVENT THE DISCHARGE
 OF OIL, GREASE, SAND AND OTHER SUBSTANCES HARMFUL OR
 HAZARDOUS TO THE BUILDING DRAINAGE SYSTEM, THE PUBLIC
 SEWER,
 003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS.
  
 2E) PLEASE INDICATE THE EXISTANCE OF A SERVICE SINK
 INCOMPLIANCE WITH FBC-P TABLE 403.1.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-09-17 Cont ID  
Sent By skennedy Date 2014-09-17 Time 16:41 Rev Time 0.00
Received By skennedy Date 2014-09-16 Time 11:32 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2014-09-05 Cont ID  
Sent By kconrad Date 2014-09-05 Time 09:50 Rev Time 0.00
Received By kconrad Date 2014-09-05 Time 09:48 Sent To  
Notes
2014-09-05 09:50:33REVIEWED SPECIAL INSPECTOR AGREEMENT: APPROVED AS
 STATED.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2014-08-29 Cont ID  
Sent By jwitmer Date 2014-08-29 Time 09:23 Rev Time 0.00
Received By jwitmer Date 2014-08-29 Time 09:23 Sent To  
Notes
2014-08-29 09:24:09BUILDING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE:FRI. 29/2014
 ACTION: DENIED
  
 4B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. A THRESHOLD AGREEMENT WILL NEED TO BE SIGNED BY
 ALL PARTIES, PLEASE PROVIDE A E-MAIL ADDRESS THAT WE
 CAN SEND ALL THE REQUIRED DOCUMENTS.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2014-08-29 Cont ID  
Sent By jwitmer Date 2014-08-29 Time 09:23 Rev Time 0.00
Received By jwitmer Date 2014-08-29 Time 09:23 Sent To  
Notes
2014-08-29 09:23:41BUILDING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE:FRI. 29/2014
 ACTION: DENIED
  
 4B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. A THRESHOLD AGREEMENT WILL NEED TO BE SIGNED BY
 ALL PARTIES, PLEASE PROVIDE A E-MAIL ADDRESS THAT WE
 CAN SEND ALL THE REQUIRED DOCUMENTS.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2014-08-29 Cont ID  
Sent By jwitmer Date 2014-08-29 Time 09:18 Rev Time 0.00
Received By jwitmer Date 2014-08-29 Time 06:25 Sent To  
Notes
2014-08-29 09:19:51BUILDING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE:FRI. 29/2014
 ACTION: DENIED
  
 4B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. A THRESHOLD AGREEMENT WILL NEED TO BE SIGNED BY
 ALL PARTIES, PLEASE PROVIDE A E-MAIL ADDRESS THAT WE
 CAN SEND ALL THE REQUIRED DOCUMENTS.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-25 Cont ID  
Sent By ajones Date 2014-06-25 Time 11:30 Rev Time 0.00
Received By ajones Date 2014-06-25 Time 11:30 Sent To  
Notes
***NONE***