Plan Review Details - Permit 14060174
Plan Review Stops For Permit 14060174
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-22 Cont ID  
Sent By jwitmer Date 2014-07-22 Time 10:49 Rev Time 0.00
Received By jwitmer Date 2014-07-22 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-15 Cont ID  
Sent By jwitmer Date 2014-06-15 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2014-06-15 Time 13:10 Sent To  
Notes
2014-06-15 13:13:25BUILDING PLAN REVIEW
 REVISION: 14060174
 PERMIT: 130906958
 ADD: 1865 PALM BEACH LAKES SHELL BUILDING C
 CONT: EMJ
 TEL: (561)348-4805
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JUNE 15/ 2014
 ACTION: DENIED
  
 1) THE REVISION # D DEPICTS WHAT APPEARS TO BE FIRE
 WALLS SEPARATING BUILDING C & B2 INTO SEPARATE
 BUILDINGS.SHEET A121. UNDER THE 2010 FBC-B 507.3 ONE
 STORY MERCANTILE OCCUPANCIES HAVE UNLIMITED AREA WHEN
 FIRE SPRINKLERED. PLEASE PROVIDE A NARATIVE TO EXPLAIN
 WHAT REVISION # D CONSIST OF. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. REVISION # D AT THE FRONT OF
 THE BUILDING, NDICATES ALSO A 1 HOUR WALL IS BEING
 BUILT BACK AWAY FORM THE 3 HR RATED WALL BUT THE PLANS
 DO NOT INDICATE ANY WALLS BEING BUILT THERE?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-07-28 Cont ID  
Sent By scaldero Date 2014-07-28 Time 13:53 Rev Time 0.00
Received By scaldero Date 2014-07-28 Time 13:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By wjolin Date 2014-06-27 Time 09:56 Rev Time 0.00
Received By wjolin Date 2014-06-27 Time 09:48 Sent To  
Notes
2014-06-27 09:56:00DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL BUILDING PLAN REVIEWER
 COMMENTS HAVE BEEN SATISFIED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-20 Cont ID  
Sent By cpuell Date 2014-07-29 Time 08:16 Rev Time 0.00
Received By skennedy Date 2014-07-15 Time 14:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-27 Cont ID  
Sent By skennedy Date 2014-06-27 Time 10:37 Rev Time 0.00
Received By skennedy Date 2014-06-06 Time 21:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-08-20 Cont ID  
Sent By skennedy Date 2014-08-20 Time 14:46 Rev Time 0.00
Received By skennedy Date 2014-08-20 Time 14:46 Sent To  
Notes
***NONE***