Plan Review Details - Permit 14060167
Plan Review Stops For Permit 14060167
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-06-14 Cont ID  
Sent By shill Date 2014-06-14 Time 17:03 Rev Time 0.00
Received By shill Date 2014-06-14 Time 17:03 Sent To  
Notes
2014-06-15 14:48:36***PROVISO***
 ***ISSUED AT CONTRACTOR'S RISK****
  
 1. FBC R310, FBC EB 604.1. FOR SLEEPING ROOM WINDOWS,
 THE CLEAR EMERGENCY ESCAPE AND RESCUE OPENING CANNOT BE
 REDUCED BY MORE THAN 5%.
  
 2. DOOR PRODUCT APPROVAL WAS SUBMITTED WITH PAGES OUT
 OF ORDER. COLLATE PAGES FOR INSPECTION.
  
 3. DOOR PRODUCT APPROAL WAS SUBMITTED WITHOUT THE
 FLORIDA STATE PRODUCT APPROVAL COVER SHEET
 (WWW.FLORIDABUILDING.ORG). PROVIDE AT INSPECTION.
  
 4. THE WINDOW EVALUATION REPORT WAS SUBMITTED WITHOUT
 THE FLORIDA STATE PRODUCT APPROVAL COVER SHEET. PROVIDE
 THIS AT INSPECTION.
  
 5. SEPARATE SUB PERMIT REQUIRED FOR ROOF REPAIR, FBC
 107, FS 489.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-14 Cont ID  
Sent By shill Date 2014-06-14 Time 17:03 Rev Time 0.00
Received By shill Date 2014-06-04 Time 18:26 Sent To  
Notes
2014-06-04 18:26:52SENT TO BLDG BOX <$5K. JW