Plan Review Details - Permit 14051109
Plan Review Stops For Permit 14051109
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-06-03 Cont ID  
Sent By skennedy Date 2014-06-03 Time 06:14 Rev Time 0.00
Received By skennedy Date 2014-06-03 Time 06:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-04 Cont ID  
Sent By skennedy Date 2014-06-05 Time 07:49 Rev Time 0.00
Received By dhayes Date 2014-06-04 Time 16:29 Sent To  
Notes
2014-06-04 16:31:27PROJECT: 3010 N. FLAGLER DR.
  
 2ST REVIEW ELECTRICAL.
 ACTION: PROVISO ATTACHED WITH COMMENTS FROM CONTRACTOR.
  
 CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FLORIDA BUILDING CODE.
  
 1) INDICATE CIRCUITRY ON FLOOR PLAN. FBC 107.2.1
 ACCORDING TO THE MECHANICAL PLANS THE AHU IS BEING
 RELOCATED TO THE ATTIC. PLEASE INDICATE THE ELECTRICAL
 CIRCUITRY THAT WILL FEED THE AHU IN IT'S NEW LOCATION.
  
 2) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT
 ETC.. NEC 440.14
  
 3) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63
  
 4) INDICATE REQUIRED BATHROOM OUTLET PER NEC 210.52(D),
 210.8
  
 5) INDICATE A SMOKE DETECTION SYSTEM AS REQUIRED PER
 FBC-R 314, 315
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-03 Cont ID  
Sent By dhayes Date 2014-06-03 Time 07:18 Rev Time 0.00
Received By dhayes Date 2014-06-02 Time 08:53 Sent To Z
Notes
2014-06-02 09:03:45PROJECT: 3010 N. FLAGLER DR.
  
 1ST REVIEW ELECTRICAL.
 ACTION: DENIED
  
 CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FLORIDA BUILDING CODE.
  
 COMMENTS:
  
 1) INDICATE CIRCUITRY ON FLOOR PLAN. FBC 107.2.1
 ACCORDING TO THE MECHANICAL PLANS THE AHU IS BEING
 RELOCATED TO THE ATTIC. PLEASE INDICATE THE ELECTRICAL
 CIRCUITRY THAT WILL FEED THE AHU IN IT'S NEW LOCATION.
  
 2) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT
 ETC.. NEC 440.14
  
 3) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63
  
 4) INDICATE REQUIRED BATHROOM OUTLET PER NEC 210.52(D),
 210.8
  
 5) INDICATE A SMOKE DETECTION SYSTEM AS REQUIRED PER
 FBC-R 314, 315
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-06-05 Cont ID  
Sent By skennedy Date 2014-06-05 Time 07:48 Rev Time 0.00
Received By skennedy Date 2014-06-05 Time 07:32 Sent To  
Notes
2014-06-05 16:58:52OK TO PASS PER S KENNEDY

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-06-03 Cont ID  
Sent By skennedy Date 2014-06-03 Time 06:15 Rev Time 0.00
Received By skennedy Date 2014-06-03 Time 06:15 Sent To  
Notes
2014-06-03 06:19:171ST REVIEW:
  
 PLEASE PROVIDE THE SPECIFICATION SHEET FOR THE TANKLESS
 WATER HEATER. THIS IS NEEDED TO VERIFY THE GAS BTU
 DEMAND AND FOR ELECTRICAL REQUIREMENTS. NOTE, THE
 ELECTRICAL REVIEW FAILED FOR LACK OF INFOMATION. THE
 ELECTRICAL RE-SUBMITTAL SHOULD ADDRESS ANY ELECTRICAL
 REQUIREMENT FOR THE TANKLESS WATER HEATER.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-05 Cont ID  
Sent By skennedy Date 2014-06-05 Time 07:49 Rev Time 0.00
Received By skennedy Date 2014-06-04 Time 15:38 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-03 Cont ID  
Sent By skennedy Date 2014-06-03 Time 06:22 Rev Time 0.00
Received By skennedy Date 2014-05-30 Time 08:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-06-05 Cont ID  
Sent By skennedy Date 2014-06-05 Time 07:48 Rev Time 0.00
Received By skennedy Date 2014-06-05 Time 07:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-06-03 Cont ID  
Sent By skennedy Date 2014-06-03 Time 06:14 Rev Time 0.00
Received By skennedy Date 2014-06-03 Time 06:14 Sent To  
Notes
2014-06-03 06:22:301ST REVIEW:
  
 PROVIDE INFORMATION AS FOLLOWS FOR THE AHU TO BE
 RELOCATED INTO THE ATTIC:
  
 FBC-R M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-03 Cont ID  
Sent By skennedy Date 2014-06-03 Time 06:15 Rev Time 0.00
Received By skennedy Date 2014-06-03 Time 06:15 Sent To  
Notes
***NONE***