| 2014-05-30 12:07:53 | ELECTRICAL. 1ST REVIEW DENIED. BASED ON THE 2008 |
| | EDITION OF THE NEC AND THE 2010 FBC. SEE COMMENTS |
| | BELOW: |
| | |
| | 1) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. FBC R314, 315 |
| | |
| | 2) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED |
| | AT A READILY ACCESSIBLE LOCATION INSIDE OR OUTSIDE THE |
| | BUILDING NEAREST THE POINT OF SERVICE ENTRANCE. NEC |
| | 230.70 |
| | |
| | 3) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94 |
| | |
| | 4) BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER |
| | OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS |
| | SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. NEC 210.11 (C)(3) |
| | |
| | 5) NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER |
| | RESISTANT RECEPTACLES. NEC 406.11 |
| | |
| | 6) AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL |
| | BE PROVIDED ON THE EXTERIOR SIDE OF THE SIDE ENTRANCE. |
| | NEC 210.70 (A) (2) (B). |
| | |
| | 7) AT LEAST ONE LIGHTING OUTLET SHALL BE PROVIDED IN |
| | UTILITY ROOMS AND BASEMENTS WHERE SUCH SPACES ARE USED |
| | FOR STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICE. |
| | FBC-EXISTING 708.3.6, NEC 210.70 |
| | |
| | 8) PROVIDE A RECEPTACLE OUTLET IN THE HALLWAY. NEC |
| | 210.52(H) |
| | |
| | 9) INDICATE ALL CIRCUITRY ON FLOOR PLAN AND COMPLETE |
| | PANEL SCHEDULE INCLUDING ALL CIRCUITRY INDICATED ON |
| | FLOOOR PLAN. FBC 107.3.5.3 (WPB) |
| | |
| | 10) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC |
| | 406.11 THOSE OUTLETS IN WET LOCATIONS SHALL BE WEATHER |
| | RESISTANT NEC 406.8(B)(1) |
| | |
| | 11) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. NEC 210.8 |
| | |
| | 12) GFCI PROTECTED OUTLETS ARE REQUIRED FRONT AND BACK |
| | AT EACH RESIDENTIAL BUILDING AND AT THE LOCATION OF THE |
| | MECHANICAL EQUIPMENT. NEC 210-52 (E) (1), 210-63 |
| | |
| | |