Plan Review Details - Permit 14051065
Plan Review Stops For Permit 14051065
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-11 Cont ID  
Sent By dhayes Date 2014-09-15 Time 09:04 Rev Time 0.00
Received By shill Date 2014-09-11 Time 15:56 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-03 Cont ID  
Sent By shill Date 2014-07-03 Time 13:42 Rev Time 0.00
Received By shill Date 2014-07-03 Time 13:42 Sent To  
Notes
2014-07-03 14:02:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FAC61G15-23, FS 471, ALL DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. ALL DOCUMENTS
 SUBMITTED ARE PHOTOCOPIES.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. PERMIT VALUE IS TO INCLUDE LABOR, MATERIALS,
 OVERHEAD, PROFIT, ENGINEERING.
  
 3. CALCULATIONS TO BE IN A FORMAT DETERMINED BY FBPE,
 SEE FAC 61G15-23. ADDITIONALLY, THEY ARE NOT SIGNED AND
 SEALED. REVISE AND SIGN, SEAL & DATE.
  
 4. SOME SHEETS INCLUDE THE LANGUAGE "CERTIFICATE OF
 AUTHORITY" - DO YOU MEAN CERTIFICATE OF AUTHORIZATION?
 PLEASE CLARIFY OR REVISE FBC 107.
  
 5. MOUNT CALCULATIONS STATE THIS IS EXPOSURE B; THIS IS
 EITHER EXPOSURE C OR D, PLEASE HAVE ENGINEER SEE
 AERIALS AND REVISE AS APPLICABLE, FBC 1609.
  
 6. WIND DESIGN CRITERIA TO BE INCLUDED ON THE PLAN FBC
 1603.1.4.
2014-06-19 11:20:20BLDG. MISC. 2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-15 Cont ID  
Sent By dhayes Date 2014-09-15 Time 09:04 Rev Time 0.00
Received By dhayes Date 2014-09-15 Time 09:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-19 Cont ID  
Sent By albarran Date 2014-06-19 Time 11:17 Rev Time 0.00
Received By albarran Date 2014-06-19 Time 09:50 Sent To B
Notes
2014-06-19 11:19:43ON PAGE E4 I NOTICED A SPACE ON THE PANEL SCHEDULE AS
 "NOT LABELED", SO I MADE THE FOLLOWING NOTE:
 PER NEC 408.4, ALL CIRCUITS SHALL BE LABELED AND
 IDENTIFIED. SPARE SPACES CONTAINING UN-USED BREAKERS
 SHALL BE DESCRIBED ACCORDINGLY. THERE SHALL BE NO
 UNLABELED OCPD'S.
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME
 AT (561) 805-6718 OR EMAIL: [email protected], OR
 DAVID HAYES AT: [email protected], OR (561) 805-6717.
 THANK YOU.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-15 Cont ID  
Sent By dhayes Date 2014-09-15 Time 09:04 Rev Time 0.00
Received By dhayes Date 2014-08-25 Time 16:52 Sent To B
Notes
2014-08-25 16:52:33TO S.HILLS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-03 Cont ID  
Sent By shill Date 2014-07-03 Time 14:51 Rev Time 0.00
Received By shill Date 2014-05-29 Time 08:55 Sent To  
Notes
2014-06-02 08:55:56SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-18 Cont ID  
Sent By ajones Date 2014-06-18 Time 14:17 Rev Time 0.00
Received By ajones Date 2014-06-18 Time 14:17 Sent To E
Notes
2014-06-02 14:34:516/2/14 ZONIG SENT TO JR.SG