| 2014-06-05 11:42:17 | PLUMBING PLAN REVIEW |
| | PERMIT: 14060141 |
| | ADD: 1106 FLORIDA AVE. |
| | CONT: GANNAWAY INC |
| | TEL: (561)557-3596 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 05/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLAN DOES NOT SHOW ENOUGH DETAIL TO |
| | DETERMINE CODE COMPLIANCE. THE REVISION FORM INDICATES |
| | THE RENOVATION OF A BATHROOM WITH THE RELOCATION OF THE |
| | WATER CLOSET AND SHOWER. NO FLOOR PLAN WAS SUBMITTED |
| | WITH THIS REVISION. 2010 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | PLEASE PROVIDE DOMENSIONS OF THE ROOM AS WELL AS FROM |
| | THE WALL TO THE CENTER OF FIXTURES. 2010 FBC-R 307.1 |
| | AND FIGURE R307.1 MINIMUM FIXTURE CLEARANCES CAN NOT BE |
| | DETERMINED. |
| | |
| | 2) COMPLIANCE WITH MINIMUM SHOWER COMPARTMENT SIZES CAN |
| | NOT BE DETERMINED 2010 FBC-P2708.1 |
| | |
| | 3) COMPLIANCE WITH 2010 FBC-P2709.2 LINING REQUIRED, |
| | PLEASE PROVIDE SHOWER PAN LINING MATERIALS. |
| | |
| | 4) PROVIDE COMPLIANCE WITH 2010 FBC-P BATHTUB AND |
| | SHOWER SPACES. SHOWER WALLS SHALL BE FINISHED IN |
| | ACCORDANCE WITH SECTION R307.2. R307.2 BATHTUB AND |
| | SHOWER SPACES. BATHTUB AND SHOWER FLOORS AND WALLS |
| | ABOVE BATHTUBS WITH INSTALLED SHOWER HEADS AND IN |
| | SHOWER COMPARTMENTS SHALL BE FINISHED WITH A |
| | NONABSORBENT SURFACE. SUCH WALL SURFACES SHALL EXTEND |
| | TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM) ABOVE THE |
| | FLOOR. |
| | |
| | 5) THE REVISION SUBMITTED WITH A PLUMBING SANITARY |
| | ISOMETRIC SHOWS A DRY VENT WITH THE WASTE DEAD ENDING |
| | INTO THE STUDOR VENT. P3108.2 DRY VENT CONNECTION. |
| | THE REQUIRED DRY-VENT CONNECTION FOR WET-VENTED SYSTEMS |
| | SHALL COMPLY WITH SECTIONS P3108.2.1 AND P3108.2.2. |
| | |
| | P3108.2.1 HORIZONTAL WET VENT. |
| | THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT |
| | SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR |
| | ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR |
| | DRAIN. WHERE THE DRY VENT CONNECTS TO A WATER CLOSET |
| | FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO |
| | THE HORIZONTAL WET VENT SYSTEM. NOT MORE THAN ONE |
| | WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF |
| | THE DRY-VENTED FIXTURE DRAIN CONNECTION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |