Plan Review Details - Permit 14051048
Plan Review Stops For Permit 14051048
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-16 Cont ID  
Sent By albarran Date 2014-06-16 Time 13:39 Rev Time 0.00
Received By albarran Date 2014-06-16 Time 13:31 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-02 Cont ID  
Sent By albarran Date 2014-06-02 Time 17:02 Rev Time 0.00
Received By albarran Date 2014-06-02 Time 16:58 Sent To  
Notes
2014-06-02 17:09:16NOT ENOUGH DETAIL ON THE SUBMITTED DRAWING TO
 ACCURATELY DETERMINE THE WORK BEING DONE.
  
 I WILL NEED THE FOLLOWING ADDED TO THE DRAWINGS FOR A
 SUCCESSFUL ELECTRICAL REVIEW:
  
 1. IDENTIFY WHICH IS BLDG. FORTON AND BLDG.SANDER
 2. PROVIDE A DETAIL DESCRIPTION OF THE PROPOSED FEEDER.
 3. SUBMIT A LOAD CALC TO DETERMINE THAT PROPER SIZE OF
 THE FEEDER.
 4. INCLUDE ON THE DRAWING CONDUCTOR SIZING AND
 INSULATION.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-16 Cont ID  
Sent By albarran Date 2014-06-16 Time 13:39 Rev Time 0.00
Received By albarran Date 2014-05-29 Time 08:57 Sent To PC
Notes
2014-06-02 08:58:12SENT TO ELECTRICAL UNDER $5000 SHELF FOR REVIEW. JG.