Plan Review Details - Permit 14050989
Plan Review Stops For Permit 14050989
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-27 Cont ID  
Sent By jwitmer Date 2014-06-27 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2014-06-27 Time 15:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-13 Cont ID  
Sent By jwitmer Date 2014-06-13 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2014-06-13 Time 11:31 Sent To  
Notes
2014-06-13 15:00:43BUILDING PLAN REVIEW
 PERMIT: 14050989
 ADD: 207 6TH ST
 CONT: FINE LINE CONSTRUCTION
 TEL: (561)582-7880
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 13/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SURVEY OF THE PROPERTY, THE SITE
 PLAN DOES NOT MATCH TTHE LOT CONFIGURATION FOUND WITH
 THE PROPERTY APPRAISERS WEB SITE.
 THE SECOND ISSUE IS TO DETERMINE IF THIS BUILDING IS IN
 A A5 FLOOD ZONE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. IF FLOOD ZONE THEN FLOOD ZONE CERTIFICATES
 WILL BE REQUIRED AND THE FLOOR ELEVATION OF THE 1ST
 FLOOR.
  
 2) SHEET A-1.0:
 2A) BOTH THE MENS(125) & WOMENS (126) RESTROOMS HAVE
 WITHIN THEM ACCESSIBLE TOLIET COMPARTMENTS (STALLS)
 PLEASE SEE 2010 FBC-ACCESSIBLITY CODE SECTION 604.8.1.2
 FOR DOOR SWING. TOILET COMPARTMENT DOORS SHALL NOT
 SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. THE
 DOORS SWING IN OVER THE REQUIED CLEAR AREA FOR THE LAV.
  
 2B) NO ACTION TO BE TAKEN. THE PLANS DO NOT PROVIDE
 VERTICAL ACCESSIBILITY TO THE MEZZANINE AREA. 201.1.1,
 IT APPEARS THE EXCEPTIONS , EXCEPTION # 2 FOR STORAGE
 AND EXCEPTION # 3 FOR OCCUPIABLE SPACES AND PRIVATE
 OFFICE.
  
 3) SHEET S-4.1 SHOWS THE DESIGN LOADS BUT THERE ARE NO
 DESIGN LOADS FOR THE STAIRS OR MEZZANINE FOR THE OFFICE
 OR THE STORAGE PORTION OF THE MEZZANINE, WILL THE
 MEZZANINE BEDESIGNED FOR LIGHT OR HEAVY? FBC-B TABLE
 1607.1.
  
 4) PLANS DO NOT SHOW CODE COMPLIANCE WITH 2010 FL
 ACCESSIBILTY 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 NOTE NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-26 Cont ID  
Sent By dhayes Date 2014-06-26 Time 07:35 Rev Time 0.00
Received By dhayes Date 2014-06-26 Time 07:35 Sent To  
Notes
2014-06-26 07:37:42BACK TO C01 FOR ADDITIONAL REVIEWS.
2014-06-23 11:03:51NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-09 Cont ID  
Sent By dhayes Date 2014-06-09 Time 16:35 Rev Time 0.00
Received By dhayes Date 2014-06-09 Time 15:20 Sent To  
Notes
2014-06-09 16:24:566/9/14.
 PROJECT: HOPKINS MARINE.
 PERMIT#: 14050989
 CODE: 2008 EDITION OF THE NEC AND THE 2010 EDITION OF
 THE FBC
 ACTION: APPROVED WITH PROVISO:
  
 1) PARTITIONS OF THE FREESTANDING TYPE (NOT FIXED)
 SHALL BE PERMITTED TO BE CONNECTED TO THE BUILDING
 ELECTRICAL SYSTEM BY ONE OF THE WIRING METHODS OF
 CHAPTER 3. MULTIWIRE BRANCH CIRCUITS SUPPLYING POWER TO
 PERMANENTLY CONNECTED FREESTANDING PARTITIONS SHALL BE
 PROVIDED WITH A MEANS TO DISCONNECT SIMULTANEOUSLY ALL
 UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE
 BRANCH CIRCUIT ORIGINATES. NEC 605.7
  
 2) EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH
 A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL
 UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH
 CIRCUIT ORIGINATES. 210.4(B)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By pleduc Date 2014-06-30 Time   Rev Time 0.00
Received By pleduc Date 2014-06-30 Time 10:56 Sent To PC
Notes
2014-06-23 11:05:17NEW SHEETS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-04 Cont ID  
Sent By pleduc Date 2014-06-04 Time   Rev Time 0.00
Received By pleduc Date 2014-06-04 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-30 Cont ID  
Sent By pleduc Date 2014-06-30 Time   Rev Time 0.00
Received By pleduc Date 2014-06-19 Time 11:05 Sent To PC
Notes
2014-06-23 11:06:18RESUBMITTAL SENT TO C1 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-13 Cont ID  
Sent By jwitmer Date 2014-06-13 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2014-05-28 Time 11:05 Sent To  
Notes
2014-05-29 11:06:51INCOMING SENT TO C01 . JW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-06-26 Cont ID  
Sent By hmoser Date 2014-06-26 Time 08:46 Rev Time 0.00
Received By hmoser Date 2014-06-26 Time 08:24 Sent To  
Notes
2014-06-23 11:06:43NEW SHEETS SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-06-06 Cont ID  
Sent By hmoser Date 2014-06-06 Time 15:39 Rev Time 0.00
Received By hmoser Date 2014-06-06 Time 15:05 Sent To  
Notes
2014-06-06 15:39:20PASS PROVISO
 1) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE
 2) PROVIDE A DETAIL FROM THE ENGINEER ON WHAT TYPE
 ANCHOR AND SIZE ANCHOR USED FOR ANCHORING CURB TO ROOF
 AND RTU TO CURB AT FIRST INSPECTION.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 3) PROVIDE A DETAIL SHOWING THE TYPE AND SIZE ANCHOR
 USED FOR CONDENSER STAND TO ROOF. PER SECTION 301.12
 WIND RESISTANCE. 2010 FBC (M) AT FIRST INSPECTION
 PLAN REVIEW BY HAROLD MOSER
 HMOSER @WPB.ORG
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-06-18 Cont ID  
Sent By jsaez Date 2014-06-05 Time 09:58 Rev Time 0.00
Received By hmoser Date 2014-06-06 Time 15:03 Sent To  
Notes
2014-06-05 10:17:231. INDICATE ON DWGS. FIRE-DAMPERS ON ALL SUPPLY, ROUND
 SHEETMETAL DUCTWORK PENETRATIONS THRU FLOOR.
 2. PROVIDE FIRE- DAMPER DETAIL

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-27 Cont ID  
Sent By jwitmer Date 2014-06-27 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2014-06-27 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-13 Cont ID  
Sent By jwitmer Date 2014-06-13 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2014-06-13 Time 11:31 Sent To  
Notes
2014-06-13 15:15:41PLUMBING PLAN REVIEW
 PERMIT: 14050989
 ADD: 207 6TH ST
 CONT: FINE LINE CONSTRUCTION
 TEL: (561)582-7880
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 13/2014
 ACTION: DENIED
  
 1) THE SANITARY ISOMETRIC IS DRAWN WITH THE RESTROOMS
 USING HORIZONTAL WET VENTS. PLEASE SEE THE CODE SECTION
 INDICATES WET VENTS ARE TO BE INSTALLED IN BATHROOMS (1
 & 2 FAMILY) ALSO SEE BOAF INFORMAL INTERPRETATION.
  
 DATE: MON APR 13 2009
 REPORT: 6090
 CODE: PLUMBING CODE YEAR: 2007
 SECTION: 909
 QUESTION:
 IS IT THE INTENT OF THE FLORIDA BUILDING CODE -
 PLUMBING SECTION 909 TO ALLOW A URINAL TO WET VENT A
 SINGLE COMMERCIAL
 WATER CLOSET OR TO DRAIN INTO THAT WATER CLOSET?S
 INDIVIDUAL VENT?
 COMMENT:
 ANSWER:
 NO. ONLY FIXTURES IN BATHROOM GROUPS AS DEFINED IN
 FLORIDA BUILDING CODE - PLUMBING CHAPTER 2 ARE
 PERMITTED TO
 CONNECT TO THE WET VENT. ANY ADDITIONAL FIXTURES MUST
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 COMMENTARY:
 A URINAL IS NOT INCLUDED IN THE DEFINITION OF A
 BATHROOM GROUP.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2014-06-26 Cont ID  
Sent By aaponte Date 2014-06-26 Time 16:06 Rev Time 0.00
Received By aaponte Date 2014-06-26 Time 16:06 Sent To  
Notes
2014-06-26 16:08:22PROVISO: 1. PERMIT FOR SURFACE PARKING LOT, LANDSCAPE
 AND IRRIGATION SHALL BE SUBMITTED, APPROVED, AND WORK
 COMPLETED BEFORE FINAL CO FOR BUILDING.
 2. LIGHTING PLAN FOR SURFACE PARKING SHALL BE
 SUBMITTED.
 3. AWNING NOT INCLUDED WITH THIS PERMIT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-12 Cont ID  
Sent By aaponte Date 2014-06-12 Time 16:12 Rev Time 0.00
Received By aaponte Date 2014-06-12 Time 16:12 Sent To  
Notes
2014-06-12 16:35:071. ADDITIONAL WORK SHALL BE DONE WITH THE PARKING
 LAYOUT TO MAKE THE PARKING AREA IN COMPLIANCE WITH THE
 REGULATIONS AS MUCH AS POSSIBLE. THE PROPOSED LAYOUT IS
 NOT ACCEPTABLE.
 2. LANDSCAPE AND IRRIGATION DRAWINGS SHALL BE
 SUBMITTED.
 3. WINDOW ON EAST SIDE OF MAIN ENTRANCE DOOR SHALL
 INCLUDE APPLIED HORIZONTAL MULLS AS THE ORIGINAL
 OPENING, AS DISCUSSED WITH THE HISTORIC PRESERVATION
 PLANNER.
 4. PROPOSED AWNING ON NORTH ELEVATION IS NOT CONSISTENT
 WITH THE BUILDING DESIGN.
 5. PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 6. PLEASE INCLUDE LIGHTING PROPOSAL FOR PARKING LOT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
2014-06-05 16:41:246/5/14