Plan Review Details - Permit 14050976
Plan Review Stops For Permit 14050976
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-05 Cont ID  
Sent By jwitmer Date 2014-07-05 Time 06:37 Rev Time 0.00
Received By jwitmer Date 2014-07-05 Time 06:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-05 Cont ID  
Sent By jwitmer Date 2014-06-05 Time 19:44 Rev Time 0.00
Received By jwitmer Date 2014-06-05 Time 19:29 Sent To  
Notes
2014-06-05 19:44:30BUILDING PLAN REVIEW
 PERMIT: 14050976
 ADD: 529 S FLAGLER DR # 31G
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561) 784-3722
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY JUNE 5/ 2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN;
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 FLOOR PLANS AREAS TO BE DEMOLISHED AND NEW LAY OUT OF
 KITCHEN AND BATHROOMS.
  
 2) THE LIST OF ITEMS TO BE DEMOLISHED SOUNDS LIKE WALLS
 IN AND AROUND TUBS AND SHOWERS, NO INFORMATION WAS
 PROVIDED FOR INDICATING CODE COMPLIANCE WITH :
 2010 FBC-B 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
  
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
  
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-07-07 Cont ID  
Sent By dhayes Date 2014-07-07 Time 11:43 Rev Time 0.00
Received By dhayes Date 2014-07-07 Time 11:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-07-01 Cont ID  
Sent By dhayes Date 2014-07-01 Time 16:16 Rev Time 0.00
Received By dhayes Date 2014-07-01 Time 16:16 Sent To  
Notes
2014-07-01 16:23:39DATE: 7/1/2014
 PROJECT: NUSSDORF, PENTHOUSE 2G.
 PERMIT#: 14050976
 CODE: 2008 EDITION OF THE NEC
 2010 FLORIDA BUILDING CODE W
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 FBC
 SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY,
 INSERT CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS. TWO SETS REQUIRED.
  
 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. FBC 107.3.5.3
  
 2) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. FBC R314, 315
  
 3) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE
 SERVICE. SEE SECTION III OF NEC 250.50
  
 4) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC
 250.94
  
 SEPARATE PERMITS REQUIRED FOR STRUCTURED CABLING,
 NETWORK, SECURITY, AUDIO/VIDEO, CCTV
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-10 Cont ID  
Sent By dhayes Date 2014-06-10 Time 16:34 Rev Time 0.00
Received By dhayes Date 2014-06-10 Time 16:30 Sent To  
Notes
2014-06-10 16:45:05DATE: 6/10/2014
 PROJECT: NUSSDORF, PENTHOUSE 2G.
 PERMIT#: 14050976
 CODE: 2008 EDITION OF THE NEC
 2010 FLORIDA BUILDING CODE W
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 FBC
 SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 ELECTRICAL PLAN REVIEW
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. FBC 107.3.5.3
  
 2) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. FBC R314, 315

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By pleduc Date 2014-06-30 Time   Rev Time 0.00
Received By pleduc Date 2014-06-30 Time 12:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-06-04 Cont ID  
Sent By pleduc Date 2014-06-04 Time   Rev Time 0.00
Received By pleduc Date 2014-06-04 Time 10:54 Sent To  
Notes
2014-06-04 12:29:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 NO FLOOR PLANS, ROOM DETAILS WERE PROVIDED WITH THIS
 PERMIT.
  
 PLEASE NOTE ON RESUBMITTAL:
  
 1. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 2. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 3. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-07 Cont ID  
Sent By dhayes Date 2014-07-07 Time 11:43 Rev Time 0.00
Received By dhayes Date 2014-07-07 Time 11:26 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-05 Cont ID  
Sent By jwitmer Date 2014-07-05 Time 06:37 Rev Time 0.00
Received By jwitmer Date 2014-06-19 Time 10:10 Sent To  
Notes
2014-06-19 10:10:39RESUBMITTAL SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-10 Cont ID  
Sent By dhayes Date 2014-06-10 Time 16:45 Rev Time 0.00
Received By dhayes Date 2014-05-29 Time 12:51 Sent To  
Notes
2014-05-29 12:51:59INCOMING SENT TO B-08. JW

Review Stop P PLUMBING
Rev No 2 Status N Date 2014-07-05 Cont ID  
Sent By jwitmer Date 2014-07-05 Time 06:37 Rev Time 0.00
Received By jwitmer Date 2014-07-05 Time 06:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-05 Cont ID  
Sent By jwitmer Date 2014-06-05 Time 19:53 Rev Time 0.00
Received By jwitmer Date 2014-06-05 Time 19:29 Sent To  
Notes
2014-06-05 19:49:35PLUMBING PLAN REVIEW
 PERMIT: 14050976
 ADD: 529 S FLAGLER DR # 31G
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561) 784-3722
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY JUNE 5/ 2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN;
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 FLOOR PLANS AREAS TO BE DEMOLISHED AND NEW LAY OUT OF
 KITCHEN AND BATHROOMS.
  
 2) WITHOUT THE EXISTING LAYOUT OF THE UNIT AND PROPOSED
 NEW LAYOUT PLAN REVIEW CAN NOT DETERMINE IF THE
 PLUMBING FIXTURES ARE BEING MOVED, WHERE THE EXISTING
 STACKS (VENTS) ARE LOCATED AND IF CODE COMPLIANCE WITH
 2010 FBC-P TABLE 906.1 MAXIMUM DISTANCE FROM FIXTURE
 TRAP FROM VENT CAN BE ACHIEVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]