Plan Review Details - Permit 14050974
Plan Review Stops For Permit 14050974
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-07-17 Cont ID  
Sent By jwitmer Date 2014-07-17 Time 11:52 Rev Time 0.00
Received By jwitmer Date 2014-07-17 Time 11:52 Sent To  
Notes
2014-07-17 11:54:05BUILDING PLAN REVIEW
 PERMIT: 14050974
 ADD: 525 S FLAGLER DR # GPH3
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)284-3722
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURSDAY JULY17/2014
 ACTION:
  
 BUILDING PROVISO:
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 1C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS
  
 FBC-B 2010
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-08 Cont ID  
Sent By jwitmer Date 2014-07-08 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2014-07-08 Time 10:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-05 Cont ID  
Sent By jwitmer Date 2014-06-05 Time 19:00 Rev Time 0.00
Received By jwitmer Date 2014-06-05 Time 18:39 Sent To  
Notes
2014-06-05 18:59:41BUILDING PLAN REVIEW
 PERMIT: 14050974
 ADD: 525 S FLAGLER DR # GPH3
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)284-3722
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY JUNE 05/2014
 ACTION: DENIED
  
 1) PLANS SEALED BY OUT OF STATE ARCHITECT. FLORIDA
 ADMINISTRATIVE RULE 61G1-16.002 DESCRIPTION OF SEAL.
 (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE
 ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION
 NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR,
 AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE
 HEXAGONAL. BOTH SEALS SHALL BE APPROXIMATELY 2" IN
 DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES
 SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA?
 AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT? OR
 ?LICENSED INTERIOR DESIGNER,? WHICHEVER IS APPLICABLE.
 (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT
 AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH
 CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN
 REGISTRATION NUMBERS, IN SUCH A MANNER:
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-10 Cont ID  
Sent By dhayes Date 2014-07-10 Time 16:42 Rev Time 0.00
Received By dhayes Date 2014-07-10 Time 16:40 Sent To  
Notes
2014-07-10 16:57:03DATE: 7/9/2014
 PROJECT: DREYFOSS RESIDENCE
 PERMIT#: 14050974
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) AN ELECTRICAL PERMIT IS REQUIRED. THE WRITTEN SCOPE
 OF WORK DOES NOT CALL OUT SPECIFIC ELECTRICAL WORK
 HOWEVER THE CODE REQUIRES ELECTRICAL WORK. SEE BELOW:
  
 2) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314.3.1
  
 3) AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS.PROVIDE A 20
 AMPERE BRANCH CIRCUIT FOR THE BATHROOM. NEC 210.11
 (C)(3)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-10 Cont ID  
Sent By dhayes Date 2014-06-10 Time 16:19 Rev Time 0.00
Received By dhayes Date 2014-06-10 Time 16:09 Sent To  
Notes
2014-07-10 16:57:42DATE: 7/9/2014
 PROJECT: DREYFOSS RESIDENCE
 PERMIT#: 14050974
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) AN ELECTRICAL PERMIT IS REQUIRED. THE WRITTEN SCOPE
 OF WORK DOES NOT CALL OUT SPECIFIC ELECTRICAL WORK
 HOWEVER THE CODE REQUIRES ELECTRICAL WORK. SEE BELOW:
  
 2) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314.3.1
  
 3) AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS.PROVIDE A 20
 AMPERE BRANCH CIRCUIT FOR THE BATHROOM. NEC 210.11
 (C)(3)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-07-09 Cont ID  
Sent By pleduc Date 2014-07-09 Time   Rev Time 0.00
Received By pleduc Date 2014-07-09 Time 16:39 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-04 Cont ID  
Sent By pleduc Date 2014-06-04 Time   Rev Time 0.00
Received By pleduc Date 2014-06-04 Time 11:25 Sent To  
Notes
2014-06-04 11:25:33THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-17 Cont ID  
Sent By jwitmer Date 2014-07-17 Time 11:36 Rev Time 0.00
Received By jwitmer Date 2014-07-15 Time 09:17 Sent To  
Notes
2014-07-15 09:17:59TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-10 Cont ID  
Sent By dhayes Date 2014-07-10 Time 16:46 Rev Time 0.00
Received By dhayes Date 2014-07-03 Time 09:34 Sent To  
Notes
2014-07-07 09:35:11RESUBMITTAL SENT TO JIM WITMER'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-10 Cont ID  
Sent By dhayes Date 2014-06-10 Time 16:21 Rev Time 0.00
Received By dhayes Date 2014-05-28 Time 13:04 Sent To  
Notes
2014-05-29 13:05:02INCOMING SENT TO B09. JW

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-07-17 Cont ID  
Sent By jwitmer Date 2014-07-17 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2014-07-17 Time 11:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-07-08 Cont ID  
Sent By jwitmer Date 2014-07-08 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2014-07-08 Time 10:04 Sent To  
Notes
2014-07-08 10:19:19PLUMBING PLAN REVIEW
 PERMIT: 14050974
 ADD: 525 S FLAGLER DR # GPH3
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)284-3722
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 08/2014
 ACTION: DENIED
  
 1)) SHEETS D-100 & A-100 SHOW THE REMOVAL OF A TUB AND
 NEW LOCATION FOR THE WATER CLOSET & BIDET. THERE IS NO
 FLAT SANITARY NOR SANITARY ISOMETRIC DIAGRAM SHOWING
 THE NEW SANITARY PIPING AND VENTING OF THESE FIXTURES.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FIXTURE CLEARANCES BIDET TO WATER
 CLOSET FBC-P FIGURE 405.3.1.
 2. FIXTURE REQUIREMENTS
 3. SANITARY DRAINAGE & VENTS
  
 3) A LETTER FROM THE CONDOMINIUM BOARD OR OWNER OF UNIT
 BELOW GIVING APPROVAL FORACCESS TO WORK IN THEIRE UNIT.
 HOW WILL THE FLOOR FIRE RATING BE MAINTAINED.
 2010 FBC-P 307.3 PENETRATIONS OF FLOOR/CEILING
 ASSEMBLIES AND FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES
 REQUIRED TO HAVE A FIRE-RESISTANCE RATING SHALL BE
 PROTECTED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-05 Cont ID  
Sent By jwitmer Date 2014-06-05 Time 19:18 Rev Time 0.00
Received By jwitmer Date 2014-06-05 Time 18:30 Sent To  
Notes
2014-06-05 19:18:16PLUMBING PLAN REVIEW
 PERMIT: 14050974
 ADD: 525 S FLAGLER DR # GPH3
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)284-3722
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY JUNE 05/2014
 ACTION: DENIED
  
 1) PLANS SEALED BY OUT OF STATE ARCHITECT. FLORIDA
 ADMINISTRATIVE RULE 61G1-16.002 DESCRIPTION OF SEAL.
 (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE
 ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION
 NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR,
 AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE
 HEXAGONAL. BOTH SEALS SHALL BE APPROXIMATELY 2" IN
 DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES
 SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA?
 AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT? OR
 ?LICENSED INTERIOR DESIGNER,? WHICHEVER IS APPLICABLE.
  
 2) SHEETS D-100 & A-100 SHOW THE REMOVAL OF A TUB AND
 NEW LOCATION FOR THE WATER CLOSET & BIDET. THERE IS NO
 FLAT SANITARY NOR SANITARY RISER DIAGRAM SHOWING THE
 NEW SANITARY PIPING AND VENTING OF THESE FIXTURES. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FIXTURE CLEARANCES BIDET TO WATER
 CLOSET FBC-P FIGURE 405.3.1.
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. VENTS
 6.PLUMBING RISE
  
 3) THE SANITARY WASTE WILL BE ROUTED THROUGH THE FLOOR
 BELOW HOW WILL THE CONTRACTOR GAIN ENTRY. HOW WILL THE
 FLOOR FIRE RATING BE MAINTAINED.
 2010 FBC-P 307.3 PENETRATIONS OF FLOOR/CEILING
 ASSEMBLIES AND FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES
 REQUIRED TO HAVE A FIRE-RESISTANCE RATING SHALL BE
 PROTECTED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  