Plan Review Details - Permit 14050931
Plan Review Stops For Permit 14050931
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By rmcdouga Date 2014-05-28 Time 07:21 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 07:21 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-07-17 Cont ID  
Sent By dhayes Date 2014-07-17 Time 12:47 Rev Time 0.00
Received By dhayes Date 2014-07-17 Time 11:51 Sent To  
Notes
2014-07-17 12:02:22DATE: 7/14/2014
 PROJECT: MALVERNE RESIDENCE
 PERMIT#: 14050937
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC
 250.94.
  
 2) A SWITCH CONTROLLED LIGHT IS REQUIRED AT THE ATTIC
 ACCESS. FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS,
 AND BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING
 A SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE
 POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY
 TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED
 AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC
 210.70(3)
  
 3) INDICATE A SMOKE AND C/O DETECTION SYSTEM AS
 REQUIRED PER FBC-R 314, 315
 "EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES". FBC-R 315.1
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-06-12 Cont ID  
Sent By dhayes Date 2014-06-12 Time 15:30 Rev Time 0.00
Received By dhayes Date 2014-06-12 Time 15:30 Sent To  
Notes
2014-06-12 15:36:50PROJECT: 210 MALVERNE RD.
  
 2ND ELECTRICAL.REVIEW
  
 ACTION: FAILED
  
 CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FLORIDA BUILDING CODE.
  
 1) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE
 SERVICE. NEC 250.50.
  
 2) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC
 250.94.
  
 3) INDICATE ALL REQUIRED OUTLETS PER NEC 210.52.
  
 4) INDICATE A SMOKE DETECTION SYSTEM AS REQUIRED PER
 FBC-R 314, 315
  
 5) INDICATE CIRCUITRY ON FLOOR PLAN. FBC 107.2.1
  
 6) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT
 ETC.. NEC 440.14
  
 7) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63
  
 NOTE: FBC 107.2.1 STATES IN PART:
 "CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN"
  
 THEREFORE. PER THE FBC 107.2.1 AS STATED ABOVE,
 ADDITIONAL CLARIFICATION IS REQUIRED TO CLARIFY THE
 SCOPE OF WORK:
  
 8) THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED TO
 PUT THEIR NAME AND SIGNATURE ON THE PLAN.
  
 9) INDICATE SPECIFICALLY WHAT IS EXISTING TO REMAIN AND
 WHAT IS PROPOSED TO BE NEW.
  
 10) INDICATE THE LOCATION OF THE SERVICE AND THE
 ELECTRICAL PANELS.
  
 11) INDICATE THE NAMES AND LOCATIONS OF ROOMS. EG.
 "BEDROOM, KITCHEN LIVINGROOM" AND SEPARATION OF
 APARTMENTS OR EFFICIENCIES.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-02 Cont ID  
Sent By dhayes Date 2014-06-02 Time 07:42 Rev Time 0.00
Received By dhayes Date 2014-06-02 Time 06:57 Sent To  
Notes
2014-06-02 07:42:35PROJECT: 210 MALVERNE RD.
  
 1ST REVIEW ELECTRICAL.
  
 ACTION: FAILED
  
 CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FLORIDA BUILDING CODE.
  
 COMMENTS:
  
 1) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE
 SERVICE. NEC 250.50.
  
 2) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC
 250.94.
  
 3) INDICATE ALL REQUIRED OUTLETS PER NEC 210.52.
  
 4) INDICATE A SMOKE DETECTION SYSTEM AS REQUIRED PER
 FBC-R 314, 315
  
 5) INDICATE CIRCUITRY ON FLOOR PLAN. FBC 107.2.1
  
 6) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT
 ETC.. NEC 440.14
  
 7) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63
  
 NOTE: FBC 107.2.1 STATES IN PART:
 "CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN"
  
 THEREFORE. PER THE FBC 107.2.1 AS STATED ABOVE,
 ADDITIONAL CLARIFICATION IS REQUIRED TO CLARIFY THE
 SCOPE OF WORK:
  
 8) THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED TO
 PUT THEIR NAME AND SIGNATURE ON THE PLAN.
  
 9) INDICATE SPECIFICALLY WHAT IS EXISTING TO REMAIN AND
 WHAT IS PROPOSED TO BE NEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-17 Cont ID  
Sent By dhayes Date 2014-07-17 Time 12:47 Rev Time 0.00
Received By dhayes Date 2014-07-15 Time 18:18 Sent To  
Notes
2014-07-16 18:18:32TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-12 Cont ID  
Sent By dhayes Date 2014-06-12 Time 15:37 Rev Time 0.00
Received By dhayes Date 2014-06-09 Time 18:21 Sent To  
Notes
2014-06-09 18:22:20TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-02 Cont ID  
Sent By dhayes Date 2014-06-02 Time 08:38 Rev Time 0.00
Received By dhayes Date 2014-05-28 Time 12:49 Sent To  
Notes
2014-05-28 12:51:42SENT TO ELECTRICAL UNDER $5,000.00

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-06-12 Cont ID  
Sent By rmcdouga Date 2014-06-12 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2014-06-12 Time 15:09 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By rmcdouga Date 2014-05-28 Time 12:48 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 12:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By rmcdouga Date 2014-05-28 Time 07:21 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 07:21 Sent To  
Notes
2014-05-28 07:23:52REPLACE BATH TUB AND SHOWER IN SAME LOCATIONS.