Plan Review Details - Permit 14050930
Plan Review Stops For Permit 14050930
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-12-10 Cont ID  
Sent By rmcdouga Date 2014-12-10 Time 18:35 Rev Time 0.00
Received By rmcdouga Date 2014-12-10 Time 15:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-11-05 Cont ID  
Sent By rmcdouga Date 2014-11-05 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2014-11-04 Time 18:46 Sent To  
Notes
2014-11-05 14:40:31DENIED BY BUILDING
  
 1) THE FL NUMBER FOR THE SINGLE HUNG WINDOWS THAT IS
 SPECIFIED ON THE PLANS AS BEING IMPACT RATED IS NOT
 ACCORDING TO THE PRODUCT APPROVAL. PLEASE CLARIFY.
 PRODUCT APPROVALS FOR IMPACT PROTECTION DEVICES AND AN
 INSTALLATION SCHEDULE WILL BE REQUIRED IF NON-IMPACT
 WINDOWS ARE USED. FBC 107.2.1, FBCR 301.2.1.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
2014-10-30 10:23:10UNABLE TO LOCATE THE PLANS. THEY HAVE NOT BEEN IN R15
 FOR AL LEAST TWO WEEKS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-22 Cont ID  
Sent By rmcdouga Date 2014-08-22 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2014-08-22 Time 07:21 Sent To  
Notes
2014-08-22 12:47:202010 FBC
  
 DENIED BY BUILDING
  
 1) THE WIND DESIGN DATA ON SHEET A-01 HAS DIFFERENT
 EXPOSURE CATEGORIES FOR EACH SIDE OF THE STRUCTURE.
 ASCE 7 - 10 SECTION 26.7.4.2 REQUIRES WIND LOADS FOR
 THE DESIGN OF THE MWFRS TO BE BASED ON THE EXPOSURE
 CATEGORY RESULTING IN THE HIGHEST WIND LOADS FOR ANY
 WIND DIRECTION AT THE THE SITE. ASCE 7 - 10 SECTION
 26.7.4.4 REQUIRES DESIGN WIND PRESSURES FOR COMPONENTS
 AND CLADDING TO BE BASED ON THE EXPOSURE CATEGORY
 RESULTING IN THE HIGHEST WIND LOADS FOR ANY WIND
 DIRECTION AT THE THE SITE. THE HIGHEST EXPOSURE
 CATEGORY THAT WAS SPECIFIED ON THE PLANS IS EXPOSURE C.
 THEREFORE, THE DESIGN FOR THE MWFRS AND THE COMPONENT
 AND CLADDING PRESSURES ARE TO BE BASED ON EXPOSURE C.
 PLEASE REVISE THE PLANS.
  
 2) BASED ON FBCR TABLES R301.2(2), R301.2(3) &
 R301.2(4), THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS ON THE PLANS APPEAR TO BE
 HIGHER THAN REQUIRED. FBCR 301.2.1.1 ALLOWS THE WIND
 SPEED TO BE CONVERTED TO NOMINAL WIND SPEEDS VASD WHEN
 THEIR TEST STANDARDS ARE BASED ON THE NOMINAL WIND
 SPEEDS.
  
 3) THE MAXIMUM DESIGN PRESSURES ON THE PRODUCT APPROVAL
 FOR THE OVERHEAD GARAGE DOOR ARE LOWER THAN THE
 REQUIRED DESIGN PRESSURES SPECIFIED ON THE PLANS.
 PLEASE CORRECT. FBCR 301.2.1
  
 4) FBCR 803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE
 FASTENED WITH 8D RING SHANK NAILS AT 6" O.C. & IF THE
 ROOF FRAMING HAS A SPECIFIC GRAVITY OF 0.42 TO 0.49 THE
 FASTENING SPACING SHALL BE 4 INCHES ON CENTER IN ROOF
 ZONE 3.
  
 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 DWELLING. FBC ENERGY 401.2
  
 6) PROVIDE A BUCK DETAIL FOR THE 9' X 7' OVERHEAD
 GARAGE DOOR ON THE PLAN. FBCR 612.10.2.1 SPECIFY HOW
 THE 2 X 6S ARE ATTACHED TO THE STRUCTURE.
  
 7) SUBMIT PRODUCT APPROVALS FOR ALL OF THE CONNECTORS
 AS REQUIRED BY DCA RULE 9N-3 OR SPECIFY THE FLORIDA OR
 MIAMI-DADE PRODUCT APPROVAL NUMBERS IN THE
 ANCHOR/CONNECTOR SCHEDULE. THE PRODUCT APPROVAL NUMBERS
 ARE NOT PROVIDED. THE MIAMI DADE NOA NO. OR THE STATE
 FL # IS REQUIRED.
  
 8) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE
 9N-3.
  
 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT.
  
 10) THE WINDOW TYPES ARE NOT IDENTIFIED ON THE PLANS.
 FROM THE DRAWINGS IT APPEARS THAT ALL OF THE WINDOWS
 ARE SINGLE HUNG. PRODUCT APPROVALS WERE SUBMITTED FOR A
 FIXED WINDOW. PLEASE IDENTIFY THIS WINDOW ON THE PLANS.
 CITY AMENDMENTS 107.2.1
  
 11) THE INFORMATION THAT WAS SUBMITTED FOR THE SINGLE
 HUNG WINDOWS AND THE DOORS DOES NOT HAVE THE FLORIDA OR
 MIAMI DADE PRODUCT APPROVAL ON THEM. PLEASE PROVIDE THE
 SHEETS WITH THIS INFORMATION SO THAT THEY CAN BE
 VERIFIED. DCA RULE 9N-3.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-07-02 Cont ID  
Sent By rmcdouga Date 2014-07-02 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2014-06-30 Time 18:33 Sent To  
Notes
2014-07-01 09:52:462010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. CITY
 AMENDMENTS 107.3.5.3 & FBCR 301.1
  
 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS ON THE PLANS. FBCR 301.2.1
  
 3) THE EXTERIOR BEARING WALLS OF THIS STRUCTURE DO NOT
 HAVE A TWO HOUR FIRE RATING AS REQUIRED FOR TYPE III-B
 CONSTRUCTION. IT IS TYPE V-B PER FBC 602. PLEASE
 CORRECT.
  
 4) SPECIFY THE REQUIRED TRUSS (LIVE AND DEAD) DESIGN
 LOADS ON THE PLANS. FBCR 301.6 AND R801.2
  
 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 DWELLING. FBC ENERGY 401.2
  
 6) SPECIFY THE ROOF SHEATHING THAT WILL BE INSTALLED ON
 THE PLANS.
  
 7) SHOW COMPLIANCE WITH FBCR 803.2.3.1 FOR FASTENING OF
 ROOF SHEATHING.
  
 8) SHOW COMPLIANCE WITH FBCR 806 FOR ROOF VENTILATION.
  
 9) PROVIDE A BUCK DETAIL FOR THE 9' X 7' OVERHEAD
 GARAGE DOOR ON THE PLAN. FBCR 612.10.2.1
  
 10) PROVIDE A BUCK DETAIL FOR THE SIDE SWING DOORS ON
 THE PLAN. FBCR 612.10.2.1
  
 11) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE
 DOUBLE 2 X 10 BEAM TO THE STRUCTURE AT THE FRONT PORCH.
 FBCR 301.1
  
 12) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE
 DOUBLE 2 X 12 BEAM TO THE STRUCTURE AT BEDROOM #1. FBCR
 802.1.9 ( A GIRDER TRUSS COULD BE USED)
  
 13) SPECIFY ALL OF THE CONNECTORS THAT WILL BE USED ON
 THE FRAMED GABLE WALL SHOWN IN DETAIL S-6 ON SHEET
 S-02. FBCR 301.1
  
 14) THE SIMPSON MST 36 STRAP SHOWN IN DETAIL S-5 ON
 SHEET S-02 DOES NOT HAVE ANY LATERAL LOAD RESISTANCE
 AND THE TRUSS CLIP IS NOT IDENTIFIED. PROVIDE A TRUSS
 ANCHOR/CONNECTOR SCHEDULE. FBCR 802.1.9
  
 15) SUBMIT PRODUCT APPROVALS FOR ALL OF THE CONNECTORS
 AS REQUIRED BY DCA RULE 9N-3 OR SPECIFY THE FLORIDA OR
 MIAMI-DADE PRODUCT APPROVAL NUMBERS IN THE
 ANCHOR/CONNECTOR SCHEDULE.
  
 16) SHOW THAT THE DOOR FROM THE GARAGE TO THE RESIDENCE
 COMPLIES WITH FBCR 302.5.1.
  
 17) NO INFORMATION IS PROVIDED ON THE PLANS FOR THE
 INTERIOR DOORS. PLEASE PROVIDE A DOOR SCHEDULE. CITY
 AMENDMENTS 107.
  
 18) SHOW COMPLIANCE WITH FBCR 310.1 FOR EMERGENCY
 ESCAPE AND RESCUE OPENINGS IN THE SLEEPING ROOMS.
  
 19) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS AND WINDOWS, THE ASPHALT ROOF SHINGLES
 AND THE OVERHEAD GARAGE DOOR. DCA RULE 9N-3
  
 20) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT.
  
 21) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-12-10 Cont ID  
Sent By rmcdouga Date 2014-12-10 Time 17:30 Rev Time 0.00
Received By rmcdouga Date 2014-12-10 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-11-05 Cont ID  
Sent By rmcdouga Date 2014-11-05 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2014-11-04 Time 18:53 Sent To  
Notes
2014-11-05 15:15:10DENIED BY ELECTRICAL
  
 1) THE ELECTICAL LOAD CALCULATIONS, THE PANEL SCHEDULE
 AND THE RISER PLAN SPECIFY A 150 AMP PANEL. THE
 ELECTRICAL FLOOR PLAN SPECIFIES A 100 AMP PANEL. PLEASE
 CORRECT. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-08-22 Cont ID  
Sent By rmcdouga Date 2014-08-22 Time 06:57 Rev Time 0.00
Received By rmcdouga Date 2014-08-22 Time 06:57 Sent To  
Notes
2014-08-22 07:21:242010 FBC / 2008 NEC
  
 ELECTRICAL DENIED
  
 THE NEW 100 AMP PANEL THAT IS SPECIFIED ON THE
 ELECTRICAL PLAN APPEARS TO BE TOO SMALL FOR THIS SINGLE
 FAMILY DWELLING. PLEASE ADDRESS THE FOLLOWING COMMENTS.
  
 1) SUBMIT TWO SETS OF LOAD CALCULATIONS AND PANEL
 SCHEDULE ON THE PLANS. CITY AMENDMENTS 107.3.5.3
  
 2) PROVIDE AN ELECTRICAL SERVICE RISER DIAGRAM WITH
 WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL ON THE
 PLANS. CITY AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT
 ON THE PLANS. NEC 110.9
  
 4) THE 2008 NEC IS THE APPLICABLE ELECTICAL CODE FOR
 THIS PROJECT. PLEASE CORRECT THE REFERENCE TO THE 2013
 NEC ON SHEET E-01.
  
 5) THE NOTE IN THE UPPER RIGHT SIDE OF THE PLAN
 SPECIFIES THE SFBC 2010. THERE IS NO LONGER AN SFBC.
 THIS SHOULD BE FBC ( FLORIDA BUILDING CODE ) 2010.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By rmcdouga Date 2014-07-01 Time 09:01 Rev Time 0.00
Received By rmcdouga Date 2014-07-01 Time 09:01 Sent To  
Notes
2014-07-01 08:47:522010 FBC / 2008 NEC
  
 ELECTRICAL DENIED
  
 1) SUBMIT TWO SETS OF LOAD CALCULATIONS AND PANEL
 SCHEDULE ON THE PLANS. CITY AMENDMENTS 107.3.5.3
  
 2) PROVIDE AN ELECTRICAL SERVICE RISER WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL ON THE PLANS. CITY
 AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT
 ON THE PLANS. NEC 110.9
  
 4) AN A/C SERVICE RECEPTACLE OUTLET IS REQUIRED IN AN
 ACCESSIBLE LOCATION FOR THE EXTERIOR CONDENSING UNIT.
 NEC 210.63
  
 5) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT
 RECEPTACLES.
  
 6) GFCI PROTECTION IS REQUIRED FOR RECEPTACLE OUTLETS
 LOCATED IN THE GARAGE AND ON THE EXTERIOR OF THE
 DWELLING. NEC 210.8
  
 7) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM
 BONDING.
  
 8) SHOW COMPLIANCE WITH NEC 210.70(3) FOR THE REQUIRED
 LIGHTING OUTLET IN THE ATTIC.
  
 IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW THE REVIEW ITEMS HAVE
 BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2014-10-30 Cont ID  
Sent By fmittner Date 2014-10-30 Time 15:50 Rev Time 0.00
Received By fmittner Date 2014-10-30 Time 15:50 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-07-02 Cont ID  
Sent By fmittner Date 2014-07-02 Time 15:39 Rev Time 0.00
Received By fmittner Date 2014-07-02 Time 15:39 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-06-02 Cont ID  
Sent By fmittner Date 2014-06-02 Time 11:49 Rev Time 0.00
Received By fmittner Date 2014-06-02 Time 11:49 Sent To  
Notes
2014-06-02 11:51:32PER APRIL HPB APPROVAL REQUIRES CENTER WINDOW TO BE
 PICTURE FLANKED BY CASEMENTS. FRIEDERIKE MITTNER SPOKE
 TO BRADLEY AND CONFIRMED REVISION IS REQURIED 6/2/14.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-12-10 Cont ID  
Sent By rmcdouga Date 2014-12-10 Time 18:35 Rev Time 0.00
Received By rmcdouga Date 2014-11-18 Time 08:42 Sent To  
Notes
2014-11-19 08:43:36INCOMING SENT TO R. MCDOUGALS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-05 Cont ID  
Sent By rmcdouga Date 2014-11-05 Time 15:15 Rev Time 0.00
Received By rmcdouga Date 2014-10-02 Time 15:45 Sent To  
Notes
2014-10-02 15:45:42R-15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-22 Cont ID  
Sent By rmcdouga Date 2014-08-22 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2014-08-01 Time 14:40 Sent To  
Notes
2014-08-05 14:40:31RE-SUBMITTAL SENT TO ROBERT MCDOUGAL'S DESK FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-02 Cont ID  
Sent By rmcdouga Date 2014-07-02 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2014-05-27 Time 10:59 Sent To  
Notes
2014-06-03 10:59:47R04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2014-12-10 Cont ID  
Sent By rmcdouga Date 2014-12-10 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2014-12-10 Time 16:52 Sent To  
Notes
2014-12-10 16:52:55BECAUSE CONDITIONED SPACE IS BEING ADDED, AND IMPACT
 FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED. ONE SET OF
 THE APPROVED PLANS CAN BE SIGNED OUT AND TAKEN TO PALM
 BEACH COUNTY FOR THE REVIEW. THE STAMPED PLANS AND A
 COPY OF THE PAID IMPACT FEE RECEIPT SHALL BE SUBMITTED
 TO THE CITY'S BUILDING DEPARTMENT BEFORE THE PERMIT CAN
 BE ISSUED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-08-22 Cont ID  
Sent By rmcdouga Date 2014-08-22 Time 06:52 Rev Time 0.00
Received By rmcdouga Date 2014-08-22 Time 06:52 Sent To  
Notes
2014-08-22 06:57:18BECAUSE CONDITIONED SPACE IS BEING ADDED, AND IMPACT
 FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED. ONE SET OF
 THE APPROVED PLANS CAN BE SIGNED OUT AND TAKEN TO PALM
 BEACH COUNTY FOR THE REVIEW. THE STAMPED PLANS AND A
 COPY OF THE PAID IMPACT FEE RECEIPT SHALL BE SUBMITTED
 TO THE CITY'S BUILDING DEPARTMENT BEFORE THE PERMIT CAN
 BE ISSUED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By rmcdouga Date 2014-07-01 Time 06:32 Rev Time 0.00
Received By rmcdouga Date 2014-06-30 Time 18:33 Sent To  
Notes
2014-08-22 06:57:46AN IMPACT FEE REVIEW WILL BE REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2014-12-10 Cont ID  
Sent By rmcdouga Date 2014-12-10 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2014-12-10 Time 16:14 Sent To  
Notes
2014-12-10 16:17:12REVISED MECHANICAL PLANS ARE REQUIRED TO BE SUBMITTED
 AND APPROVED BEFORE FINAL INSPECTION. THE PLANS THAT
 WERE SUBMITTED HAVE REDLINED CORRECTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-10-09 Cont ID  
Sent By rmcdouga Date 2014-10-09 Time 14:45 Rev Time 0.00
Received By rbergsma Date   Time   Sent To  
Notes
2014-10-09 14:42:16MECHANICAL DENIED
  
 THE ENERGY CALC'S MAKE ASSUMTIONS THAT ARE NOT
 SUPPORTED BY FACTS;
 THE AREA OF DUCTWORK IN THE ATTIC = 272 SQ FT, WITHOUT
 DUCT SIZING HOW WAS THIS DETERMINED
  
 THIS IS A LEVEL 3 ALTERATION AND ADDITION, PROVIDE
 COMPLETE MECHANICAL DRAWINGS FOR REVIEW AND APPROVAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-08-21 Cont ID  
Sent By rmcdouga Date 2014-08-21 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2014-08-21 Time 16:59 Sent To  
Notes
2014-08-21 17:05:12NOTES ON THE PLANS STATE THAT THE MECHANICAL PLANS WILL
 BE SUBMITTED UNDER A SEPARATE PERMIT. SEPARATE PERMIT,
 APPLICATION AND REVIEW IS REQUIRED FOR THE MECHANICAL
 WORK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By rmcdouga Date 2014-07-01 Time 06:32 Rev Time 0.00
Received By rmcdouga Date 2014-06-30 Time 18:33 Sent To  
Notes
2014-07-01 06:48:102010 FBC
  
 MECHANICAL DENIED
  
 1) SUBMIT TWO COPIES OF MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBCR M1401.3
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT
 MATCHES THE EQUIPMENT SIZING CALCULATIONS. FBCR M1401.3
  
 3) SPECIFY THE DUCT AND GRILL SIZES ON THE PLANS. FBCR
 M1601
  
 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-11-01 Cont ID  
Sent By rmcdouga Date 2014-11-01 Time 05:05 Rev Time 0.00
Received By tklarge Date 2014-11-01 Time 05:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-30 Cont ID  
Sent By rmcdouga Date 2014-06-30 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2014-06-30 Time 18:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-08-22 Cont ID  
Sent By rmcdouga Date 2014-08-22 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2014-08-22 Time 10:09 Sent To  
Notes
2014-08-22 10:10:55CERTAINTEED ASPHALT SHINGLE - NOA NO.11-0223.13

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-30 Cont ID  
Sent By fmittner Date 2014-10-30 Time 15:50 Rev Time 0.00
Received By fmittner Date 2014-10-30 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-02 Cont ID  
Sent By fmittner Date 2014-06-02 Time 11:51 Rev Time 0.00
Received By fmittner Date 2014-06-02 Time 11:51 Sent To B
Notes
***NONE***