Plan Review Details - Permit 14050928
Plan Review Stops For Permit 14050928
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-09-16 Cont ID  
Sent By jwitmer Date 2014-09-16 Time 16:17 Rev Time 0.00
Received By jwitmer Date 2014-09-16 Time 15:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-30 Cont ID  
Sent By JWITMER Date 2014-08-30 Time 07:33 Rev Time 0.00
Received By jwitmer Date 2014-08-27 Time 12:21 Sent To  
Notes
2014-08-30 07:33:22BUILDING PLAN REVIEW
 PERMIT: 14050928
 ADD: 2420 FLORIDA AVENUE
 CONT: K & M COMMERCIAL CONSTRUCTION
 TEL: (561)383-2817
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. AUG. 30/ 2014
 ACTION: DENIED
  
 NOTE THIS REVIEW WILL BE BASED ON THE 2010 FL. EXISITNG
 BUILDING CODE SECTION 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1) COVER SHEET CODE INFORMATION:
 1A)(1) THIS SHEET LIST F1, S2 & B OCCUPANCNCIES AS
 NON--SEPARATED OCCUPANCIES.
 PLEASE PROVIDE A BREAK DOWN IN SQUARE FEET FOR EACH OF
 THE OCCUPANCY GROUPS. 2010 FBC-B 508.3.2 ALLOWABLE
 BUILDING AREA AND HEIGHT.
 THE ALLOWABLE BUILDING AREA AND HEIGHT OF THE BUILDING
 OR PORTION THEREOF SHALL BE BASED ON THE MOST
 RESTRICTIVE ALLOWANCES FOR THE OCCUPANCY GROUPS UNDER
 CONSIDERATION FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING IN ACCORDANCE WITH SECTION 503.1.
  
 1A)(2) PLEASE PROVIDE THE TYPE OF INVENTORY THAT WILL
 BE STORED IN THE S2 STORAGE OCCUPANCY, THE USAGE AND
 MATERIALS STORED WOULD APPEAR TO MAKE THIS A S1 TYPE
 OCCUPANCY. 2010 FBC-B 311.2 MODERATE-HAZARD STORAGE
 S-1. PLEASE PROVIDE THE INVENTORY OF STORAGE ON THE
 PLANS FOR DOCUMENTATION. 107.2.1.4 QUALITY OF BUILDING
 PLANS.THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, FOR THE RECORD RETENTION PROGRAM.
  
 1B) THE DECLARED NONSEPARATED OCCUPANCIES PLEASE REVIEW
 FBC-B 508.3.1 AND 508.3.2 FOR THE LIMITING FACTOR IN
 NONSEPATED OCCUPANCIES. IN FBC-B 508.3.1 CHAPTER 9
 SECTION:
 903.2.4 (1) A GROUP F-1 FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M2) WILL REQUIRE FIRE SPRINKLERS.
 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER SYSTEM SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS CONTAINING A GROUP
 S-1 OCCUPANCY WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS:(1.) A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M2).
  
 1C) FBC-B 508.3.2 DEALS WIH THE ALLOWABLE BUILDING AREA
 AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE
 BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE
 OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING. 2010 FBC-B TABLE 503 WILL
 ONLY ALLOW 15,500 SQ FT FOR A F1 OCCUPANCY
 NON-SPRINKLERED.ALSO REVIEW 508.2.3. CORRECT NOTE FOUND
 ON THE COVRE SHEET & SHEET A1.3 ALLOWABLE HEIGHT AND
 AREA. WHERE AN OPEN AREA EXCEEDS 30 FT, YOU CAN ONLY
 TAKE 30 FT OR TTHE MULTIPLIER BECOMES A 1 IN THIS CASE.
 15,500 + 11,625= 27,125 SQ FT.
  
  
 2) SEMI-COMPLIED. WALK -IN COOLERS ARE TO BE FIRE
 SPRINKLERED TO SATISFY CODE REQUIREMENT 2603.4.1.3
 ALLOWABLE AREA FOR NON-SPRINKLERED WALK IN COOLERS. WE
 WILL NEED A ENGINEERED PLAN (IF OVER 50 SPRINKLER
 HEADS, OTHERWISE A CONTRACTOR CAN DESIGN) FLOW TEST AND
 SPECIFICATIONS. FOR THE REQUIRED FIRE SPRINKLER PLANS
 THE HYDROLICS AND SHOP DRAWING ARE REQUIRED. ALSO SEE
 FIRE COMMENS FOR REQUIRED DESIGN.
 903.1.1 ALTERNATIVE PROTECTION.
 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS
 COMPLYING WITH SECTION 904 SHALL BE PERMITTED IN LIEU
 OF AUTOMATIC SPRINKLER PROTECTION WHERE RECOGNIZED BY
 THE APPLICABLE STANDARD AND APPROVED BY THE FIRE CODE
 OFFICIAL.
  
  
 1ST ROUND REVIEW COMMENT. SHEET A1.2 INDICATES NEW FOAM
 INSULATION IN WALK IN COOLERS PLEASE REVIEW 2603.4.1.3
 2010 FBC-B SECTION FOR ALLOWABLE AREA FOR WALK IN
 COOLERS NON-SPRINKLERED BUILDINGS.
 FBC-B 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED
 BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES
 NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM FLAME SPREAD
 INDEX OF 75 IS PERMITTED IN WALK-IN COOLERS OR FREEZER
 UNITS WHERE THE AGGREGATE FLOOR AREA DOES NOT EXCEED
 400 SQUARE FEET (37 M2) AND THE FOAM PLASTIC IS COVERED
 BY A METAL FACING NOT LESS THAN 0.032-INCH-THICK (0.81
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A
 MINIMUM BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A
 THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED
 WHERE PROTECTED BY A THERMAL BARRIER.
  
 3) SHEET A1.3 LIFE SAFETY SHEET:
  
 3A) COMPLIED. THIS SHEET INDICATES THE 12,290 SQ FT
 AREA F2 OCCUPANCY BUT MAKES REFERANCE TO 1004.1
 EXCEPTION # 1 IN A SPECIAL PURPOSE FACTORY-INDUSTRIAL
 OCCUPANCY, THE OCCUPANT LOAD SHALL BE THE MAXIMUM
 NUMBER OF PERSONS TO OCCUPY THE AREA UNDER ANY PROBABLE
 CONDITIONS AS THE LIMITING THE OCCUPANT LOAD TO 40
 OCCUPANTS. PLEASE NOTE THE BUILDING OFFICIAL HAS
 REVIEWED AND DECLARED THIS TO BE A F1 TYPE OCCUPANCY.
 THE MAKING REFERANCE TO THE SPECIAL PURPOSE
 FACTORY-INDUSTRIAL OCCUPANCY YOU ARE NOW DECLARING THIS
 TO BE A F3 TYPE OCCUCANCY SINCE THIS IS WHERE SPECIAL
 PURPOSE FACTORY-INDUCTRIAL REFERANCE OCCURS SEE 306.4
 SPECIAL PURPOSE F-3.
 THE 2010 FBC-B TABLE 1004.1.1 DECLARES THE OCCUPANCY TO
 BE FIGURED AT 100 SQ FT/ OCCUPANT OR 123 OCCUPANTS FOR
 THIS AREA.
 THE 2010 FBC-B TABLE 1015. 1 ONLY ALLOWS 49 OCCUPANTS
 WITH A SINGLE EXIT. FBC-B TABLE 1016.1 WILL ONLY ALLOW
 200 FT IN A F1 TYPE OCCUPANCY. THIS AREA WILL REQUIRE 2
 EXITS FROM THIS LOCATION 1015.2 EXIT OR EXIT ACCESS
 DOORWAY ARRANGEMENT
  
 3B) COMPLIED.
  
 3C)COMPLIED. PLEASE UPDATE THE OCCUPANT LOADS TO
 REFLECT THE F1 OCCUPANCY THIS MAY EFFECT THE REQUIRED
 FIXTURE COUNT REQUIRED UNDER THE PLUMBING CODE.
  
 4) COVERSHEET SHOWS A NEW ALUMINUM SHADE CANOPY PLEASE
 PROVIDE THE SQUARE FEET OF AREA THIS WILL COVER AND
 SHOW ALSO ON THE A-1 SHEET NOT SURE IF ONLY THE LOADING
 DOCK OR IF THE CANOPY WILL GO ALLTHE WAY BACK TO THE
 EXISTING LOADING DOCK? CANOPY TO BE UNDER A SEPARATE
 PERMIT.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By jwitmer Date 2014-06-27 Time 12:18 Rev Time 0.00
Received By jwitmer Date 2014-06-25 Time 17:00 Sent To  
Notes
2014-06-25 18:40:36BUILDING PLAN REVIEW
 PERMIT: 14050928
 ADD: 2420 FLORIDA AVENUE
 CONT: K & M COMMERCIAL CONSTRUCTION
 TEL: (561)383-2817
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 25/ 2014
 ACTION: DENIED
  
 NOTE THIS REVIEW WILL BE BASED ON THE 2010 FL. EXISITNG
 BUILDING CODE SECTION 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1) COVER SHEET CODE INFORMATION:
 1A) THIS SHEET LIST F2, S2 & B OCCUPANCNCIES AS
 UN-SEPARATED USE.
 THE FIRST ISSUE IS THE DECLARED F2 OCCUPANCY (12,290 SQ
 FT AREA), THE BUILDING OFFICIAL HAS REVIEWED THE
 PROJECT WITH ME AND HE HAS DETERMINED THIS AREA TO BE
 CONSIDERED A F1 OCCUPANCY. THE F2 OCCUPANCIES INCLUDED
 BRICK, CERAMIC PRODUCTS, FOUNDRIES GYPSUM PRODUCTS
 ETC... 2010 FBC-B 306.2
  
 1B) THE DECLARED NONSEPARATED OCCUPANCIES PLEASE REVIEW
 FBC-B 508.3.1 AND 508.3.2 FOR THE LIMITING FACTOR IN
 NONSEPATED OCCUPANCIES. IN FBC-B 508.3.1 CHAPTER 9
 SECTION 903.2.4 (1) A GROUP F-1 FIRE AREA EXCEEDS
 12,000 SQUARE FEET (1115 M2) WILL REQUIRE FIRE
 SPRINKLERS.
  
 1C) FBC-B 508.3.2 DEALS WIH THE ALLOWABLE BUILDING AREA
 AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE
 BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE
 OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING. 2010 FBC-B TABLE 503 WILL
 ONLY ALLOW 12,000 SQ FT FOR A F1 OCCUPANCY
 NON-SPRINKLERED.ALSO REVIEW 508.2.3. CORRECT NOTE FOUND
 ON SHEET A1.3 ALLOWABLE HEIGHT AND AREA.
  
 2) SHEET A1.2 INDICATES NEW FOAM INSULATION IN WALK IN
 COOLERS PLEASE REVIEW 2603.4.1.3 2010 FBC-B SECTION FOR
 ALLOWABLE AREA FOR WALK IN COOLERS NON-SPRINKLERED
 BUILDINGS.
 FBC-B 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED
 BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES
 NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM FLAME SPREAD
 INDEX OF 75 IS PERMITTED IN WALK-IN COOLERS OR FREEZER
 UNITS WHERE THE AGGREGATE FLOOR AREA DOES NOT EXCEED
 400 SQUARE FEET (37 M2) AND THE FOAM PLASTIC IS COVERED
 BY A METAL FACING NOT LESS THAN 0.032-INCH-THICK (0.81
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A
 MINIMUM BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A
 THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED
 WHERE PROTECTED BY A THERMAL BARRIER.
  
 3) SHEET A1.3 LIFE SAFETY SHEET:
  
 3A) THIS SHEET INDICATES THE 12,290 SQ FT AREA F2
 OCCUPANCY BUT MAKES REFERANCE TO 1004.1 EXCEPTION # 1
 IN A SPECIAL PURPOSE FACTORY-INDUSTRIAL OCCUPANCY, THE
 OCCUPANT LOAD SHALL BE THE MAXIMUM NUMBER OF PERSONS TO
 OCCUPY THE AREA UNDER ANY PROBABLE CONDITIONS AS THE
 LIMITING THE OCCUPANT LOAD TO 40 OCCUPANTS. PLEASE NOTE
 THE BUILDING OFFICIAL HAS REVIEWED AND DECLARED THIS TO
 BE A F1 TYPE OCCUPANCY. THE MAKING REFERANCE TO THE
 SPECIAL PURPOSE FACTORY-INDUSTRIAL OCCUPANCY YOU ARE
 NOW DECLARING THIS TO BE A F3 TYPE OCCUCANCY SINCE THIS
 IS WHERE SPECIAL PURPOSE FACTORY-INDUCTRIAL REFERANCE
 OCCURS SEE 306.4 SPECIAL PURPOSE F-3.
 THE 2010 FBC-B TABLE 1004.1.1 DECLARES THE OCCUPANCY TO
 BE FIGURED AT 100 SQ FT/ OCCUPANT OR 123 OCCUPANTS FOR
 THIS AREA.
 THE 2010 FBC-B TABLE 1015. 1 ONLY ALLOWS 49 OCCUPANTS
 WITH A SINGLE EXIT. FBC-B TABLE 1016.1 WILL ONLY ALLOW
 200 FT IN A F1 TYPE OCCUPANCY. THIS AREA WILL REQUIRE 2
 EXITS FROM THIS LOCATION 1015.2 EXIT OR EXIT ACCESS
 DOORWAY ARRANGEMENT
  
 3B) 1015.5 REFRIGERATED ROOMS OR SPACES.
 ROOMS OR SPACES HAVING A FLOOR AREA LARGER THAN 1,000
 SQUARE FEET (93 M2), CONTAINING A REFRIGERANT
 EVAPORATOR AND MAINTAINED AT A TEMPERATURE BELOW 68?F
 (20?C), SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR
 EXIT ACCESS DOORS.
  
 TRAVEL DISTANCE SHALL BE DETERMINED AS SPECIFIED IN
 SECTION 1016.1, BUT ALL PORTIONS OF A REFRIGERATED ROOM
 OR SPACE SHALL BE WITHIN 150 FEET (45 720 MM) OF AN
 EXIT OR EXIT ACCESS DOOR WHERE SUCH ROOMS ARE NOT
 PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM.
 EGRESS IS ALLOWED THROUGH ADJOINING REFRIGERATED ROOMS
 OR SPACES.
  
 3C) PLEASE UPDATE THE OCCUPANT LOADS TO REFLECT THE F1
 OCCUPANCY THIS MAY EFFECT THE REQUIRED FIXTURE COUNT
 REQUIRED UNDER THE PLUMBING CODE.
  
 4)
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-05 Cont ID  
Sent By dhayes Date 2014-06-05 Time 15:04 Rev Time 0.00
Received By dhayes Date 2014-06-05 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-29 Cont ID  
Sent By pleduc Date 2014-05-29 Time   Rev Time 0.00
Received By pleduc Date 2014-05-29 Time 11:41 Sent To  
Notes
2014-05-29 15:24:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENT:
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-09-22 Cont ID  
Sent By jroach Date 2014-09-22 Time 14:34 Rev Time 0.00
Received By jroach Date 2014-09-09 Time 15:30 Sent To  
Notes
2014-09-09 15:32:32TO JW'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-03 Cont ID  
Sent By jroach Date 2014-09-03 Time 15:18 Rev Time 0.00
Received By jroach Date 2014-08-14 Time 17:22 Sent To  
Notes
2014-08-14 17:23:25C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-27 Cont ID  
Sent By jwitmer Date 2014-06-27 Time 12:18 Rev Time 0.00
Received By jwitmer Date 2014-05-27 Time 09:49 Sent To  
Notes
2014-05-28 09:49:39C11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-09-16 Cont ID  
Sent By jwitmer Date 2014-09-16 Time 15:52 Rev Time 0.00
Received By jwitmer Date 2014-09-16 Time 15:52 Sent To  
Notes
2014-09-16 15:54:15IMPACT FEE STAMP 09/09/2014 NO IMPACT FEES DUE. PRIOR
 USE FURNITURE MANUFACTURING. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-08-30 Cont ID  
Sent By jwitmer Date 2014-08-30 Time 06:13 Rev Time 0.00
Received By jwitmer Date 2014-08-30 Time 06:13 Sent To  
Notes
2014-08-30 06:13:44BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By jwitmer Date 2014-06-27 Time 12:18 Rev Time 0.00
Received By jwitmer Date 2014-06-27 Time 12:18 Sent To  
Notes
2014-06-27 12:18:54BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-06-24 Cont ID  
Sent By jsaez Date 2014-06-24 Time 08:03 Rev Time 0.00
Received By jsaez Date 2014-06-24 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-30 Cont ID  
Sent By JWITMER Date 2014-08-30 Time 07:46 Rev Time 0.00
Received By jwitmer Date 2014-08-27 Time 12:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By jwitmer Date 2014-06-27 Time 12:17 Rev Time 0.00
Received By jwitmer Date 2014-06-25 Time 17:00 Sent To  
Notes
2014-06-25 18:41:41PLUMBING PLAN REVIEW
 PERMIT: 14050928
 ADD: 2420 FLORIDA AVENUE
 CONT: K & M COMMERCIAL CONSTRUCTION
 TEL: (561)383-2817
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 25/ 2014
 ACTION: DENIED
  
 NOTE THIS REVIEW WILL BE BASED ON THE 2010 EXISITNG
 BUILDING CODE & BUILDING CODE FOR NEW ELEMENTS. 2010
 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1) PLEASE UPDATE THE OCCUPANT LOADS TO REFLECT THE F1
 OCCUPANCY THIS MAY EFFECT THE REQUIRED FIXTURE COUNT
 REQUIRED UNDER THE 2010 FBC- PLUMBING CODE TABLE 403.1.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2014-09-22 Cont ID  
Sent By jroach Date 2014-09-22 Time 14:26 Rev Time 0.00
Received By jroach Date 2014-09-22 Time 14:26 Sent To  
Notes
2014-09-22 14:27:50ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.22.2014
 PERMIT NO.: 14050928
 ADDRESS: 2420 FLORIDA AVENUE
 CONTRACTOR/CONTACT: KAREN HIBBERT
 TELEPHONE NO.: 561.383.2817
 SCOPE OF REVIEW: IMPROVEMENTS TO EXISTING WAREHOUSE.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL PARKING SPACES SHALL BE STRIPED AND SHALL
 PROVIDE WHEEL STOPS IN ACCORDANCE WITH THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS. DETAIL HAS
 BEEN ATTACHED TO THE PLANS.
  
 2. THE FENCE / SLIDING GATE SHALL BE INSTALLED UNDER A
 SEPARATE PERMIT.
  
 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED.
  
 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (CO), ALL APPROPRIATE AND NECESSARY PARKING EASEMENTS /
 AGREEMENTS SHALL BE RECORDED IN THE PUBLIC RECORDS OF
 PALM BEACH COUNTY TO PROVIDE FOR THE REQUIRED PARKING
 ON THE WEST SIDE OF FLORIDA AVENUE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-03 Cont ID  
Sent By JROACH Date 2014-09-03 Time 15:15 Rev Time 0.00
Received By jroach Date 2014-08-28 Time 16:30 Sent To  
Notes
2014-09-03 15:15:36ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.03.2014
 PERMIT NO.: 14050928
 ADDRESS: 2420 FLORIDA AVENUE
 CONTRACTOR/CONTACT: KAREN HIBBERT
 TELEPHONE NO.: 561.383.2817
 SCOPE OF REVIEW: IMPROVEMENTS TO EXISTING WAREHOUSE.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. A SEPARATE LANDSCAPE PERMIT IS REQUIRED. THE PERMIT
 APPLICATION SHALL BE ACCOMPANIED BY TWO (2) SETS OF
 SIGNED / SEALED LANDSCAPE PLANS ALONG WITH A CERTIFIED
 COST ESTIMATE SHOWING THE TOTAL COST OF THE
 INSTALLATION (MATERIALS AND LABOR). PRIOR TO SUBMITTAL
 OF THE LANDSCAPE PERMIT APPLICATION, THE FOLLOWING
 ITEMS NEED TO BE ADDRESSED:
  
  A. IS IT POSSIBLE TO PLACE A TREE IN THE PROPOSED
 LANDSCAPE ISLAND IN THE NORTHWEST CORNER OF THE
 PROPERTY?
  
  B. THE LANDSCAPE PLANS SHALL BE REVISED TO REFLECT
 120% COVERAGE BY AN AUTOMATIC IRRIGATION SYSTEM.
  
  C. THE PLANTING DETAIL SHALL BE MODIFIED TO SHOW THAT
 MULCH WILL BE PULLED AWAY FROM THE BASE OF ALL TREES /
 PALMS.
  
  D. THE PLANTING PLAN NEEDS TO BE REVISED TO LABEL THE
 GREEN BUTTONWOOD AS "CE", NOT "IC" AS CURRENTLY SHOWN.
  
 2. THE PERMIT SHALL BE REVISED TO PROVIDE FOR THE
 FOLLOWING:
  
  A. ALL PARKING SPACES SHALL BE STRIPED AND SHALL
 PROVIDE WHEEL STOPS IN ACCORDANCE WITH THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS. DETAIL HAS
 BEEN ATTACHED TO THE PLANS.
  
  B. A DUMPSTER DETAIL SHALL BE PROVIDED SHOWING HOW THE
 ENCLOSURE IS TO BE CONSTRUCTED.
  
  C. A DETAIL SHALL BE PROVIDED FOR THE FENCE / SLIDING
 GATE.
  
  D. THE LANDSCAPE ISLANDS ON EITHER SIDE OF THE WALK
 (WHICH EXTENDS SOUTH FROM THE SOUTH EXIT FROM THE
 BUILDING) SHALL BE EXTENDED SOUTH TO MATCH THE BACK OF
 THE PARKING ROW THAT IS TO THE WEST OF THE FENCE /
 GATE. THE LANDSCAPE PLAN SHOWS THIS CORRECTLY.
  
 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED.
  
 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (CO), ALL APPROPRIATE AND NECESSARY PARKING EASEMENTS /
 AGREEMENTS SHALL BE RECORDED IN THE PUBLIC RECORDS OF
 PALM BEACH COUNTY TO PROVIDE FOR THE REQUIRED PARKING
 ON THE WEST SIDE OF FLORIDA AVENUE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-23 Cont ID  
Sent By jroach Date 2014-06-23 Time 12:20 Rev Time 0.00
Received By jroach Date 2014-06-12 Time 14:47 Sent To  
Notes
2014-06-23 12:21:12ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.23.2014
 PERMIT NO.: 14050928
 ADDRESS: 2420 FLORIDA AVENUE
 CONTRACTOR/CONTACT: KAREN HIBBERT
 TELEPHONE NO.: 561.383.2817
 SCOPE OF REVIEW: INTERIOR IMPROVEMENTS TO EXISTING
 WAREHOUSE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-441 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), BECAUSE THE
 PROPOSED SCOPE OF WORK EXCEEDS 50 PERCENT OF THE VALUE
 OF THE EXISTING STRUCTURE, THE SITE SHALL BE BROUGHT
 INTO COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE
 ZLDRS. PLANS SHALL BE SUBMITTED INDICATING SUCH. IF
 EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A LANDSCAPE PERMIT. PLEASE NOTE THAT
 PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING:
  
 A. THE LOCATION OF ALL EXISTING AND PROPOSED
 STRUCTURES, IMPROVEMENTS, ETC.
  
 B. THE LOCATION OF ALL EXISTING AND PROPOSED TREES,
 SHRUBS, GROUND COVERS, ETC.
  
 C. THE LOCATION OF UTILITY AND DRAINAGE EASEMENTS,
 OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK
 VALVES, CLEAN OUTS, FIRE HYDRANTS, LIGHT POLES, ETC.
 THAT MAY IMPACT LANDSCAPING.
  
 D. TABULATION TABLE INDICATING HOW THE EXISTING AND
 PROPOSED PLANT MATERIAL COMPLIES WITH ARTICLE XIV.
  
 E. SPECIES, QUANTITY, HEIGHT, SPREAD, SPACING, AND
 LOCATION OF THE EXISTING AND PROPOSED PLANT MATERIAL.
  
 F. STATEMENT THAT ALL LANDSCAPE AREAS WILL BE PROVIDED
 WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM, INCLUDING
 THE ADJACENT RIGHT-OF-WAY (PLEASE NOTE THAT ANY NEW
 IRRIGATION SHALL BE DONE UNDER A SEPARATE PERMIT).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2014-06-06 10:57:586/5/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved