Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-29 Cont ID  
Sent By dhayes Date 2014-05-29 Time 10:22 Rev Time 0.00
Received By dhayes Date 2014-05-29 Time 09:09 Sent To  
Notes
2014-05-29 10:20:49ELECTRICAL DENIED BASED ON THE 2008 EDITION OF THE NEC
 AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE
  
 1) PROVIDE SMOKE DETECTORS AS REQUIRED FOR NEW
 DWELLINGS. FBC-R 314.3.1, 315.1, FBC 107.3.5
  
 2) RECESSED LUMINAIRES SHALL BE SEALED, AIR TIGHT AND
 IC RATED. FBC 402.4.5
  
 3) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC
 406.8(B)
  
 4) THOSE OUTLETS IN WET LOCATIONS SHALL BE GFI &
 WEATHER RESISTANT. NEC 406.11
  
 5) ALL OUTLETS REQUIRING GFI PROTECTION SHALL MEET THE
 PROVISIONS OF NEC 210.8
  
 6) ALL OUTLETS REQUIRING ARC FAULT PROTECTION SHALL
 MEET THE PROVISIONS OF NEC 210.12
  
 7) THE MINIMUM OUTLET REQUIREMENTS FOR DWELLING UNITS
 SHALL MEET THE PROVISIONS OF NEC 210.52
  
 8) GROUNDING ELECTRODE SYSTEM SHALL MEET THE PROVISIONS
 OF NEC 250
  
 9) SERVICE DISCONNECTING MEANS SHALL BE PROVIDED. NEC
 230.70
  
 10) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT AND
 GROUNDING DETAIL, AND PANEL SCHEDULE REQUIRED. FBC-
 107.3.5.3 ?
  
 11) LUMINAIRES IN CLOTHES CLOSETS SHALL MEET THE
 PROVISIONS OF NEC 410.16
  
 12) PERSON RESPONSIBLE FOR THE ELECTRICAL DESIGN TO
 PROVIDE NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-18 Cont ID  
Sent By dhayes Date 2014-06-18 Time 14:52 Rev Time 0.00
Received By dhayes Date 2014-06-18 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-29 Cont ID  
Sent By dhayes Date 2014-05-29 Time 10:22 Rev Time 0.00
Received By dhayes Date 2014-05-23 Time 14:44 Sent To  
Notes
2014-05-23 14:49:49GIVEN TO JGOMEZ TO REVIEW WITH OTHER PERMITS ON SAME
 JOB.
2014-05-23 14:44:43ROUTED TO ELECTRICAL