| 2014-05-31 14:10:29 | ELECTRICAL 1ST REVIEW. | | | | | | ACTION: DENIED. | | | | | | CODE: 2010 FBC, 2008 NEC | | | | | | COMMENTS: | | | | | | 1) INDICATE A LOCATION ON THE SITE PLAN FOR THE NEW 150 | | | KVA TRANSFORMER AND NEW PANEL "HA". FBC 107.3.5.1 | | | | | | 2) PROVIDE A PANEL DIRECTORY FOR THE NEW PANEL "HA". | | | NEC 408.4 | | | | | | 3) INDICATE HOW THE SERVICE MAINS WILL BE LABELED. NEC | | | 230.72 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-06-12 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-06-12 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-06-12 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2014-06-12 11:32:33 | INCOMING SENT TO D. HAYES DESK. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-05-31 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-05-31 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-23 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2014-05-23 13:42:10 | ROUTED TO ELECTRICAL |
|
|
|