| 2014-06-23 07:48:15 | BUILDING PLAN REVIEW |
| | PERMIT: 14050913 |
| | ADD: 1016 CLARE SUITE # 3 |
| | CONT: RIELLY CONSTRUCTION |
| | TEL: (561)262-6876 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY JUNE 23/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE LIFE SAFETY SHEET LS 1.1 DESIGN STANDAARDS & |
| | CODE REQUIREMENT HEADING LIST THE BUILDING AS FULLY |
| | SPRINKLERED WITH A NFPA 13 SYSTEM. PLEASE NOTE THAT THE |
| | SPRINKLERS DOES NOT STATE WHAT TYPE OF HEADS ARE |
| | CURRENTLY IN USE. PLEASE REFER TO THE 2010 FBC-B |
| | SECTION 709.1 EXCEPTION #3 THAT WILL GREATLY EFFECT |
| | YOUR DESIGN AND CODE COMPLIANCE. EXCEPTION 3. IN |
| | MINI-WAREHOUSES/SELF-STORAGE BUILDINGS, WALLS USED TO |
| | SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE |
| | FIRE-RESISTANCE RATING, PROVIDED A SPRINKLER SYSTEM |
| | MEETING THE REQUIREMENTS OF ORDINARY HAZARD GROUP II AS |
| | DEFINED BY NFPA 13, IS INSTALLED EMPLOYING QUICK |
| | RESPONSE HEADS. |
| | |
| | 2) LIFE SAFETY SHEET 1.1 & 1.2 IT APPEARS THAT |
| | STAIRWELL 1 ON THE 1ST FLOOR & 2ND FLOOR HAS BEEN |
| | CLOSED UP AND NOW A VOID SPACE? THAT WILL LEAVE (3) |
| | UNENCLOSED EXITS. THIS MAY STILL BE A STORAGE OCCUPANCY |
| | 2010 FLORIDA EXISITNG BUILDING CODE 705.3 NUMBER OF |
| | EXITS. THE NUMBER OF EXITS SHALL BE IN ACCORDANCE WITH |
| | THE APPROPRIATE SECTIONS OF THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | NFPA 1 -14.6.1.3 IN EXISTING BUILDINGS, WHERE A 2 STORY |
| | EXIT ENCLOSURE CONNECTS THE STORY OF EXIT DISCHARGE |
| | WITH AN ADJACENT STORY, THE EXIT SHALL BE PERMITTED TO |
| | BE ENCLOSED ONLY ON THE STORY OF EXIT DISCHARGE, |
| | PROVIDED THAT NOT LESS THAN 50 % OF THE NUMBER AND |
| | CAPACITY OF EXITS ON THE STORY OF EXIT DISCHARGE ARE |
| | INDEPENDENT OF SUCH ENCLOSURES. THE SAME LANGUAGE IS |
| | FOUND UNDER NFPA 101. 7.2.2.5.1.3. |
| | NEITHER STAIR # 107 OR 111 HAVE A ENCLOSURE AT THE |
| | BOTTOM OF THE STAIRWELL THAT LEAD TO THE EXTERIOR OF |
| | THE BUILDING. |
| | |
| | 3) LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR |
| | $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING. |
| | 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES |
| | IN THE EVENT OF DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 4A) THE PLANS INDICATE A NEW ELEVATOR, THIS ELEVATOR |
| | WILL NEED TO COMPLY WITH THE 2010 FBC-ACCESSIBILITY |
| | CODE 3001.3 ACCESSIBILITY. |
| | PASSENGER ELEVATORS ARE REQUIRED TO BE ACCESSIBLE BY |
| | THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | |
| | 4B) NEW WORK. 2010 FBC-B 3001.5.1 EACH NEW ELEVATOR |
| | SHALL COMPLY WITH THE FLORIDA ELEVATOR SAFETY CODE THAT |
| | WAS IN EFFECT AT THE TIME OF RECEIPT OF APPLICATION FOR |
| | THE CONSTRUCTION PERMIT FOR THE ELEVATOR. |
| | |
| | 5) THE LIFE SAFETY SHEETS NOR ARCHITECTURAL SHEETS SHOW |
| | THE ELEVATOR SHAFT AS 1 HOUR FIRE RATEDOR FOR THE |
| | MACHANICAL ROOM. 2010 FBC-B |
| | 3002.1 HOISTWAY ENCLOSURE PROTECTION. |
| | ELEVATOR, DUMBWAITER AND OTHER HOISTWAY ENCLOSURES |
| | SHALL BE SHAFT ENCLOSURES COMPLYING WITH SECTION 708. |
| | 3002.1.1 OPENING PROTECTIVES. |
| | OPENINGS IN HOISTWAY ENCLOSURES SHALL BE PROTECTED AS |
| | REQUIRED IN CHAPTER 7. |
| | |
| | 6) LIFE SAFETY & A1.1 SHOW A WALL TYPE # 5 WITH FOAM |
| | SHEET INSULATION. SHEET A3.2 DETAIL # 5 INDICATES THE |
| | FOAM INSULATION WALL PANELS TO BE 5 " IN THICKNESS |
| | INFILL BETWEEN THE DOUBLE T 2ND FLOOR PRECAST BEAM AND |
| | FLOORING SYSTEM. PLEASE PROVIDE THE MANUFACTURERS |
| | SPECIFICATION FOR THE FOAM INSULATION AND COMPLIANCE |
| | WITH FBC-B 2603.3 AND OR EXCEPTIONS. ALSO SEE 2010 |
| | FBC-MECHANICAL FOR USE IN PLENUMS FBC-M 602.2 & |
| | 602.2.1. |
| | |
| | 7) SHEET S-1 PROVIDES THE WIND DESIGN FOR THE NEW |
| | EXTERIOR DOOR ELEMENTS BUT NO PRODUCT APPROVALS WERE |
| | SUBMITTED WITH THIS REVIEW. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, |
| | |
| | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) THE SHEET LS 1.1 LIST THIS BUILDING AS A TYPE VA |
| | BUILDING PLEASE PROVIDE HOW THE 1 HR FIRE RATING WILL |
| | BE ACHIEVED AND CODE COMPLIANCE WITH FBC-B TABLE 601. |
| | THE PLANS SHOW NEW STRUCTURAL MEMBERS WITH THE NEW HOLE |
| | BEING CUT INTO THE FLOOR. |
| | |
| | 10) SINCE THIS BUILDING IS CHANGING THE USAGE TYPE FROM |
| | STORAGE TO MINI STORAGE UNITS TTHE PLANS WILL NEED TO |
| | GO TO P B C IMPACT FEE OFFICE FOR ASSESSMENT OF IMPACT |
| | FEES. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |