Plan Review Details - Permit 14050913
Plan Review Stops For Permit 14050913
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 13:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-04 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 15:16 Rev Time 0.00
Received By jwitmer Date 2014-08-04 Time 14:20 Sent To  
Notes
2014-08-04 15:16:46BUILDING PLAN REVIEW
 PERMIT: 14050913
 ADD: 1016 CLARE SUITE # 3
 CONT: RIELLY CONSTRUCTION
 TEL: (561)262-6876
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JUNE 23/ 2014
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET LS 1.1 DESIGN STANDARDS & CODE
 REQUIREMENT HEADING LIST THE BUILDING AS FULLY
 SPRINKLERED WITH A NFPA 13 SYSTEM. PLEASE NOTE THAT THE
 SPRINKLERS DOES NOT STATE WHAT TYPE OF HEADS ARE
 CURRENTLY IN USE. PLEASE REFER TO THE 2010 FBC-B
 SECTION 709.1 EXCEPTION #3 THAT WILL GREATLY EFFECT
 YOUR DESIGN AND CODE COMPLIANCE. EXCEPTION 3. IN
 MINI-WAREHOUSES/SELF-STORAGE BUILDINGS, WALLS USED TO
 SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE
 FIRE-RESISTANCE RATING, PROVIDED A SPRINKLER SYSTEM
 MEETING THE REQUIREMENTS OF ORDINARY HAZARD GROUP II AS
 DEFINED BY NFPA 13, IS INSTALLED EMPLOYING QUICK
 RESPONSE HEADS.
  
 2) COMPLIED.
  
 3) 2ND REVIEW, RESPONSE INDICATES THE CONTRACTOR WILL
 PROVIDE A COST BREAKDOWN OF THE EXPENDITURES ON
 ACCISSIBILITY AND ACCESSIBLE ITEMS. NO SUCHDOCUMENTS
 WERE SUBMITTED FOR THIS REVIEW.
 LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR
 $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING.
 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
  
 4A) PROVISO SHOP DRAWINGS TO FOLLOW< DEFERRED
 SUBMITTAL; THE PLANS INDICATE A NEW ELEVATOR, THIS
 ELEVATOR WILL NEED TO COMPLY WITH THE 2010
 FBC-ACCESSIBILITY CODE 3001.3 ACCESSIBILITY.
 PASSENGER ELEVATORS ARE REQUIRED TO BE ACCESSIBLE BY
 THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 4B) PROVISO SHOP DRAWINGS TO FOLLOW< DEFERRED
 SUBMITTAL. NEW WORK. 2010 FBC-B 3001.5.1 EACH NEW
 ELEVATOR SHALL COMPLY WITH THE FLORIDA ELEVATOR SAFETY
 CODE THAT WAS IN EFFECT AT THE TIME OF RECEIPT OF
 APPLICATION FOR THE CONSTRUCTION PERMIT FOR THE
 ELEVATOR. NO SUBMITTALS FOR EITHER THE FREIGHT
 ELEVATOR.
  
 5) SEMI-COMPLIED. THE PLANS SHOW A 1 HOUR RATED WALL ON
 THE 1ST FLOOR MISSING ON LS 1.2. 3002.1.1 OPENING
 PROTECTIVES. OPENINGS IN HOISTWAY ENCLOSURES SHALL BE
 PROTECTED AS REQUIRED IN CHAPTER 7. DOORS ARE (1) HOUR
 FIRE RATED NOT SHOWN ON PLANS.
  
 6-9) COMPLIED.
  
 10) SINCE THIS BUILDING IS CHANGING THE USAGE TYPE FROM
 STORAGE TO MINI STORAGE UNITS TTHE PLANS WILL NEED TO
 GO TO P B C IMPACT FEE OFFICE FOR ASSESSMENT OF IMPACT
 FEES.
  
 11) NEW COMMENT, SHEET LS2 NOT CHANGED OUT SHOWING THE
 LULA LIFT TO THE 2ND FLOOR NOR THE REQUIRED 1 HOUR
 ENCLOSURE AND DOOR.
  
 12) NEW COMMENT SHEETS S-2 & S3 HAVE NOT BEEN UPDATED
 TO SHOW THE LULA LIFT PENETRATING THE 2ND FLOOR AND
 STEEL FRAMING MEMBERS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-23 Cont ID  
Sent By jwitmer Date 2014-06-23 Time 11:11 Rev Time 0.00
Received By jwitmer Date 2014-06-23 Time 05:31 Sent To  
Notes
2014-06-23 07:48:15BUILDING PLAN REVIEW
 PERMIT: 14050913
 ADD: 1016 CLARE SUITE # 3
 CONT: RIELLY CONSTRUCTION
 TEL: (561)262-6876
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JUNE 23/ 2014
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET LS 1.1 DESIGN STANDAARDS &
 CODE REQUIREMENT HEADING LIST THE BUILDING AS FULLY
 SPRINKLERED WITH A NFPA 13 SYSTEM. PLEASE NOTE THAT THE
 SPRINKLERS DOES NOT STATE WHAT TYPE OF HEADS ARE
 CURRENTLY IN USE. PLEASE REFER TO THE 2010 FBC-B
 SECTION 709.1 EXCEPTION #3 THAT WILL GREATLY EFFECT
 YOUR DESIGN AND CODE COMPLIANCE. EXCEPTION 3. IN
 MINI-WAREHOUSES/SELF-STORAGE BUILDINGS, WALLS USED TO
 SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE
 FIRE-RESISTANCE RATING, PROVIDED A SPRINKLER SYSTEM
 MEETING THE REQUIREMENTS OF ORDINARY HAZARD GROUP II AS
 DEFINED BY NFPA 13, IS INSTALLED EMPLOYING QUICK
 RESPONSE HEADS.
  
 2) LIFE SAFETY SHEET 1.1 & 1.2 IT APPEARS THAT
 STAIRWELL 1 ON THE 1ST FLOOR & 2ND FLOOR HAS BEEN
 CLOSED UP AND NOW A VOID SPACE? THAT WILL LEAVE (3)
 UNENCLOSED EXITS. THIS MAY STILL BE A STORAGE OCCUPANCY
 2010 FLORIDA EXISITNG BUILDING CODE 705.3 NUMBER OF
 EXITS. THE NUMBER OF EXITS SHALL BE IN ACCORDANCE WITH
 THE APPROPRIATE SECTIONS OF THE FLORIDA FIRE PREVENTION
 CODE.
 NFPA 1 -14.6.1.3 IN EXISTING BUILDINGS, WHERE A 2 STORY
 EXIT ENCLOSURE CONNECTS THE STORY OF EXIT DISCHARGE
 WITH AN ADJACENT STORY, THE EXIT SHALL BE PERMITTED TO
 BE ENCLOSED ONLY ON THE STORY OF EXIT DISCHARGE,
 PROVIDED THAT NOT LESS THAN 50 % OF THE NUMBER AND
 CAPACITY OF EXITS ON THE STORY OF EXIT DISCHARGE ARE
 INDEPENDENT OF SUCH ENCLOSURES. THE SAME LANGUAGE IS
 FOUND UNDER NFPA 101. 7.2.2.5.1.3.
 NEITHER STAIR # 107 OR 111 HAVE A ENCLOSURE AT THE
 BOTTOM OF THE STAIRWELL THAT LEAD TO THE EXTERIOR OF
 THE BUILDING.
  
 3) LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR
 $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING.
 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 4A) THE PLANS INDICATE A NEW ELEVATOR, THIS ELEVATOR
 WILL NEED TO COMPLY WITH THE 2010 FBC-ACCESSIBILITY
 CODE 3001.3 ACCESSIBILITY.
 PASSENGER ELEVATORS ARE REQUIRED TO BE ACCESSIBLE BY
 THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 4B) NEW WORK. 2010 FBC-B 3001.5.1 EACH NEW ELEVATOR
 SHALL COMPLY WITH THE FLORIDA ELEVATOR SAFETY CODE THAT
 WAS IN EFFECT AT THE TIME OF RECEIPT OF APPLICATION FOR
 THE CONSTRUCTION PERMIT FOR THE ELEVATOR.
  
 5) THE LIFE SAFETY SHEETS NOR ARCHITECTURAL SHEETS SHOW
 THE ELEVATOR SHAFT AS 1 HOUR FIRE RATEDOR FOR THE
 MACHANICAL ROOM. 2010 FBC-B
 3002.1 HOISTWAY ENCLOSURE PROTECTION.
 ELEVATOR, DUMBWAITER AND OTHER HOISTWAY ENCLOSURES
 SHALL BE SHAFT ENCLOSURES COMPLYING WITH SECTION 708.
 3002.1.1 OPENING PROTECTIVES.
 OPENINGS IN HOISTWAY ENCLOSURES SHALL BE PROTECTED AS
 REQUIRED IN CHAPTER 7.
  
 6) LIFE SAFETY & A1.1 SHOW A WALL TYPE # 5 WITH FOAM
 SHEET INSULATION. SHEET A3.2 DETAIL # 5 INDICATES THE
 FOAM INSULATION WALL PANELS TO BE 5 " IN THICKNESS
 INFILL BETWEEN THE DOUBLE T 2ND FLOOR PRECAST BEAM AND
 FLOORING SYSTEM. PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATION FOR THE FOAM INSULATION AND COMPLIANCE
 WITH FBC-B 2603.3 AND OR EXCEPTIONS. ALSO SEE 2010
 FBC-MECHANICAL FOR USE IN PLENUMS FBC-M 602.2 &
 602.2.1.
  
 7) SHEET S-1 PROVIDES THE WIND DESIGN FOR THE NEW
 EXTERIOR DOOR ELEMENTS BUT NO PRODUCT APPROVALS WERE
 SUBMITTED WITH THIS REVIEW.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) THE SHEET LS 1.1 LIST THIS BUILDING AS A TYPE VA
 BUILDING PLEASE PROVIDE HOW THE 1 HR FIRE RATING WILL
 BE ACHIEVED AND CODE COMPLIANCE WITH FBC-B TABLE 601.
 THE PLANS SHOW NEW STRUCTURAL MEMBERS WITH THE NEW HOLE
 BEING CUT INTO THE FLOOR.
  
 10) SINCE THIS BUILDING IS CHANGING THE USAGE TYPE FROM
 STORAGE TO MINI STORAGE UNITS TTHE PLANS WILL NEED TO
 GO TO P B C IMPACT FEE OFFICE FOR ASSESSMENT OF IMPACT
 FEES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-08-06 Cont ID  
Sent By dhayes Date 2014-08-06 Time 11:15 Rev Time 0.00
Received By dhayes Date 2014-08-06 Time 09:47 Sent To  
Notes
2014-08-06 10:07:00DATE: 8/6/14
 PROJECT: ELITE STORAGE.
 PERMIT#: 14050913
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY PLANS, AND
 MANUFACTURER SPECIFICATIONS ARE REQUIRED FOR: LIFT,
 GENERATOTR, FIRE ALARM, SECURITY, CCTV, NETWORK,
 DATA/COM, ACCESS CONTROL AND AUDIO/VIDEO. FBC CITY
 AMENDMENTS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-23 Cont ID  
Sent By dhayes Date 2014-06-23 Time 15:19 Rev Time 0.00
Received By dhayes Date 2014-06-23 Time 13:17 Sent To  
Notes
2014-06-23 15:19:45DATE: 6/23/2014
 PROJECT: ELITE STORAGE.
 PERMIT#: 14050913
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES NEC 701.11(G)
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) ALL ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED
 WITH GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. NEC
 422.52
  
 4) PROVIDE SPECS AND CIRCUITRY INFORMATION ON INSTA-HOT
 FOR 1ST FL BATHROOM.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY PLANS, AND
 MANUFACTURER SPECIFICATIONS ARE REQUIRED FOR: LIFT,
 GENERATOTR, FIRE ALARM, SECURITY, CCTV, NETWORK,
 DATA/COM, ACCESS CONTROL AND AUDIO/VIDEO. FBC CITY
 AMEMNDMENTS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-08-05 Cont ID  
Sent By pleduc Date 2014-08-05 Time   Rev Time 0.00
Received By pleduc Date 2014-08-05 Time 12:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-29 Cont ID  
Sent By pleduc Date 2014-05-29 Time   Rev Time 0.00
Received By pleduc Date 2014-05-29 Time 11:41 Sent To  
Notes
2014-05-29 15:58:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENT:
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2014-08-22 Time 07:54 Sent To  
Notes
2014-08-22 07:55:01INCOMING SENT TO JW DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-06 Cont ID  
Sent By dhayes Date 2014-08-06 Time 11:16 Rev Time 0.00
Received By dhayes Date 2014-07-30 Time 09:25 Sent To  
Notes
2014-07-31 09:25:36C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-02 Cont ID  
Sent By skennedy Date 2014-07-02 Time 08:34 Rev Time 0.00
Received By skennedy Date 2014-05-23 Time 11:24 Sent To  
Notes
2014-05-27 11:29:55C16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-08-05 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 15:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2014-08-04 15:26:59SHEET A1.1 STAMPED NO IMPACT FEES DUES 7/10/2014
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-06-23 Cont ID  
Sent By jwitmer Date 2014-06-23 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2014-06-23 Time 11:12 Sent To  
Notes
2014-06-23 11:12:38BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-06-24 Cont ID  
Sent By jsaez Date 2014-06-24 Time 08:50 Rev Time 0.00
Received By jsaez Date 2014-06-24 Time 08:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-08-05 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2014-08-04 Time 14:20 Sent To  
Notes
2014-08-04 15:25:14SHEET A1.1 ACCESSIBLE RESTROOM IS DIMENSIONED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-23 Cont ID  
Sent By jwitmer Date 2014-06-23 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2014-06-23 Time 05:50 Sent To  
Notes
2014-06-23 11:31:04PLUMBING PLAN REVIEW
 PERMIT: 14050913
 ADD: 1016 CLARE SUITE # 3
 CONT: RIELLY CONSTRUCTION
 TEL: (561)262-6876
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JUNE 23/ 2014
 ACTION: DENIED
  
 1) SHEET P1.1 THE NEW RESTROOM IS NOT DIMENSIONED,
 COMPLIANCE WITH THE 2010 FBC- ACCESSIBILITY FOR TOLIET
 ROOM AND 604.3.2 CAN NOT BE DETERMINED.
  
 2) ) SHEET P1.1 ALSO SHOWS A SINGLE WATER FOUNTAIN.
 PLEASE REVIEW 2010 FBC-ACCESSIBILITY CODE 211.2 MINIMUM
 NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 3) SHEET P1.1 INDICATES A NEW INSTANTANEOUS WATER
 HEATER BELOW SINK, THE PLANS DO NOT CALL OUT IF THIS IS
 THE REQUIRED SERVICE SINK.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED, &
 PLUMBING TABLE 403.1.
  
 4) SHEET P0.1 SANITARY RISER DOES NOT SHOW THE WATER
 CLOSET OR THE SERVICE SINK. SERVICE SINK WILL NEED ITS
 OWN VENT. FBC-P 907.1.
 WET VENTS ARE ONLY SUPPOSE TO BE USED IN RESIDENTIAL
 USE, WITH BATHROOMS BOAF INFORMAL INTERPRETATION #
 6090.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2014-07-01 Cont ID  
Sent By avann Date 2014-07-01 Time 10:07 Rev Time 0.00
Received By ajones Date 2014-07-01 Time 10:07 Sent To  
Notes
2014-06-05 17:19:106/5/14