Plan Review Details - Permit 14050884
Plan Review Stops For Permit 14050884
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-08-06 Cont ID  
Sent By rmcdouga Date 2014-08-06 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2014-08-05 Time 06:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-28 Cont ID  
Sent By rmcdouga Date 2014-06-28 Time 09:59 Rev Time 0.00
Received By rmcdouga Date 2014-06-27 Time 07:36 Sent To E
Notes
2014-06-27 16:40:372010 FBC
  
 DENIED BY BUILDING
  
 1) THE ARCHITECT IS REQUIRED TO SIGN AND SEAL THE PLANS
 THAT ARE SUBMITTED FOR PUBLIC RECORD. FAC 61G1-16.003
  
 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C.
 PLEASE REVISE PLANS AND ADJUST THE WINDLOAD PRESSURES.
 FBCR 301.2.1.4.3
  
 3) SUBMIT TWO SETS OF A DRAINAGE PLAN THAT SHOWS
 COMPLIES WITH FBCR 401.3 SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. IT
 CAN NOT BE DRAINED ONTO ADJACENT LOTS.
  
 4) SHOW THAT THE DOOR FROM THE GARAGE TO THE KITCHEN
 COMPLIES WITH FBCR 302.5.1.
  
 5) SHOW COMPLIANCE WITH FBCR 302.6 FOR DWELLING /
 GARAGE FIRE SEPARATION.
  
 6) SHOW COMPLIANCE WITH FBCR 806 FOR ROOF VENTILATION.
  
 7) SHOW COMPLIANCE WITH FBCR 807.1 FOR ATTIC ACCESS.
  
 8) PROVIDE A WALL SECTION THAT SHOWS THE WALL AND ATTIC
 INSULATION ( UN-VENTED ATTIC ), ETC. CITY AMENDMENTS
 107.2.1
  
 9) SPECIFY THE LENGTH OF THE OVERHANG AND THE SOFFIT
 MATERIAL THAT WILL BE INSTALLED. CITY AMENDMENTS
 107.2.1 AND FBCR 616.1
  
 10) SPECIFY THE MATERIAL THAT WILL BE INSTALLED ON THE
 CEILING OF THE LOGGIA. CITY AMENDMENTS 107.2.1
  
 11) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS, LISTING AND INSTALLATION INSTRUCTIONS
 FOR THE BUILT-IN BBQ ON THE LOGGIA. FBCR M1901.2 AND
 G2408.1.
  
 12) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORT
 FOR THE SPRAY FOAM INSULATION IF IT IS USED. FBCR 316
  
 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 14) THE PRODUCT APPROVAL FOR THE WOOD FIXED WINDOWS NOA
 NO. 11-1024.07 HAS BEEN SUPERSEDED BY NOA NO.
 14-0402.02. PLEASE SUBMIT THE CURRENT NOA. DCA RULE
 9N-3
  
 15) THE DRAWINGS THAT WERE SUBMITTED FOR THE FIBERGLASS
 SWING DOOR AT THE GARAGE WERE NOT SHRUNK TO FIT ON AN
 8" X 11" PAGE AND SOME OF THE INFORMATION WAS CUT OFF.
 PLEASE PROVIDE NEW PAGES WITH COMPLETE INFORMATION. DCA
 RULE 9N-3 AND CITY AMENDMENTS 107.2.1
  
 16) PLEASE PROVIDE A RESPONSE LETTER THAT INDICATES HOW
 EACH OF THE REVIEW ITEMS WAS ADDRESSED. THIS WILL HELP
 TO REDUCE PLAN REVIEW TIME.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-08-12 Cont ID  
Sent By dhayes Date 2014-08-12 Time 10:10 Rev Time 0.00
Received By dhayes Date 2014-08-12 Time 08:53 Sent To  
Notes
2014-08-12 09:41:08 
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-07-25 Cont ID  
Sent By dhayes Date 2014-07-25 Time 11:07 Rev Time 0.00
Received By dhayes Date 2014-07-25 Time 07:12 Sent To  
Notes
2014-07-25 11:07:32DATE: 7/25/2014
 PROJECT: MAHONEY RESIDENCE
 PERMIT#: 14050884
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A RISER DIAGRAM AND A LOAD CALCULATION TO
 INDICATE THE AREA IN SQUARE FEET OF THE BUILDING OR
 OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE
 DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING
 DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO
 BE USED. NEC 215.5 FBC 107.2.1
  
 2) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI
 PROTECTED. NEC 210.8. THE OUTLET FOR THE GARAGE DOOR
 OPENER NEEDS TO BE INDENTIFIED AS BEING GFI PROTECTED.
  
 3)AT LEAST ONE RECEPTACLE SHALL BE INSTALLED AT EACH
 ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF 600 MM
 (24 IN.) OR GREATER AND A SHORT DIMENSION OF 300 MM (12
 IN.) OR GREATER. NEC 210.52(B)(2)
  
 PROVIDE A DETAIL INDICATING THE GROUNDING ELECTRODE
 SYSTEM IN COMPLIANCE WITH THE FOLLOWING NOTES:
 4) ALL GROUNDING ELECTRODES AS DESCRIBED IN
 250.52(A)(1) THROUGH (A)(7) THAT ARE PRESENT AT EACH
 BUILDING OR STRUCTURE SERVED SHALL BE BONDED TOGETHER
 TO FORM THE GROUNDING ELECTRODE SYSTEM. WHERE NONE OF
 THESE GROUNDING ELECTRODES EXIST, ONE OR MORE OF THE
 GROUNDING ELECTRODES SPECIFIED IN 250.52(A)(4) THROUGH
 (A)(8) SHALL BE INSTALLED AND USED. NEC 250.50
 GROUNDING ELECTRODE SYSTEM.
  
 5) THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR AT THE
 SERVICE, AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED
 BY A FEEDER(S) ORBRANCHCIRCUIT(S), OR AT A SEPARATELY
 DERIVED SYSTEM OF A GROUNDED OR UNGROUNDED AC SYSTEM
 SHALL NOT BE LESS THAN GIVEN IN TABLE 250.66, EXCEPT AS
 PERMITTED IN 250.66(A) THROUGH (C) NEC 250.66 SIZE OF
 ALTERNATING-CURRENT GROUNDING ELECTRODE CONDUCTOR. FOR
 A 300AMP SERVICE NEEDS A MINIMUM OF A #2CU GROUNDING
 ELECTRODE CONDUCTOR.
  
 6) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94.
  
 7) ALL METAL PIPING SYSTEMS SHALL BE BONDED. BOND COLD
 WATER PIPE, METAL GAS PIPING AND ANY EXPOSED STRUCTURAL
 STEEL WHEN AVAILABLE AS REQUIRED. NEC 250.104,
  
 8) PROVIDE SPECIFICATIONS, AND CONNECTION DETAILS FOR
 STEAM GENERATOR INDICATING THE SUITABILITY FOR
 INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS
 OF THIS CODE. NEC 110.3(A)(1 THRU 8
  
 9) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE
 LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS
 SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT
 CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32
 KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS
 DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE
 SUPPORTED. (D) BOXES AT CEILING-SUSPENDED (PADDLE) FAN
 OUTLETS.
  
 10) NOTE ON THE PLANS THAT ALL CIRCUITRY REQUIRED TO
 HAVE ARC-FAULT CIRCUITRY INTURUPTING CAPACITY SHALL BE
 IN COMPLIANCE WITH THE PROVISIONS OF NEC 210.12,
  
 11) NOTE ON THE PLANS THAT ALL NEW RECEPTACLES SHALL BE
 TAMPER RESISTANT IN COMPLIANCE WITH THE PROVISIONS OF
 NEC 406.11
  
 12) REVISE THE PLANS ACCORDINGLY TO INDICATE COMPLIANCE
 WITH ALL OF THE FOLLOWING:
 PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
 FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, AND
 BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE
 POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY
 TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED
 AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC
 210.70(3)
 DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT FROM
 AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING OR
 REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS SHALL
 BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
 INDICATE THE CIRCUITRY AND DISCONNECTING MEANS FOR THE
 A/C AHU IN THE ATTIC.
  
 AIR HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 SIX (6) FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER,
 EFFICIENT, AND ECONOMIC OPERATION OF THE AIR
 CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR
 MAINTENANCE IS PERFORMED. YOUR AIR CONDITIONING SYSTEM
 IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING:
 1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION
 DRAIN IS NOT WORKING PROPERLY OR;
 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION. FBC-M 306.3.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-07-01 Cont ID  
Sent By dhayes Date 2014-07-01 Time 15:36 Rev Time 0.00
Received By dhayes Date 2014-07-01 Time 14:23 Sent To  
Notes
2014-07-01 15:35:45DATE: 7/1/2014
 PROJECT: MALONEY RESIDENCE
 PERMIT#: 14050884
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 ELECTRICAL PERMIT APPLICATION REQUIRED FROM QUALIFIED,
 REGISTERED ELECTRICAL CONTRACTOR. PLANS TO BE REVISED
 TO CORRECT THE FOLLOWING DEFICIENCIES:
  
 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. FBC-R 107.3.5.3
  
 2) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE
 SERVICE. NEC 250.50
  
 3) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC
 250.94
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
  
 5) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 6) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C)(3)
  
 7) KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY
 NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. NEC
 210.52(B)(3)
  
 8) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF
 24" OR GREATER AND A SHORT DIMENSION OF 12" OR GREATER.
 NEC 210.52(C)(2)
  
 SEPARATE PERMITS REQUIRED FOR GENERATOR, SWIMMING POOL,
 STRUCTURED CABLING FOR NETWORK, SECURITY, AUDIO/VIDEO,
 CCTV
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2014-08-12 Cont ID  
Sent By rmcdouga Date 2014-08-12 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2014-08-12 Time 18:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-12 Cont ID  
Sent By rmcdouga Date 2014-08-12 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2014-08-08 Time 13:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-06 Cont ID  
Sent By rmcdouga Date 2014-08-06 Time 17:22 Rev Time 0.00
Received By rmcdouga Date 2014-07-24 Time 17:06 Sent To  
Notes
2014-07-24 17:07:18SENT TO D. HAYES DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-07-01 Cont ID  
Sent By dhayes Date 2014-07-01 Time 15:36 Rev Time 0.00
Received By dhayes Date 2014-05-22 Time 17:36 Sent To  
Notes
2014-05-22 17:36:48ROUTE TO R11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-08-05 Cont ID  
Sent By rmcdouga Date 2014-08-05 Time 07:19 Rev Time 0.00
Received By rmcdouga Date 2014-08-05 Time 07:19 Sent To  
Notes
2014-08-05 07:22:26MU-2014-15596 NO FEES WERE CHARGED. IMPACT FEE STAMP ON
 SHEET A-101.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By rmcdouga Date 2014-06-27 Time 07:35 Rev Time 0.00
Received By rmcdouga Date 2014-06-27 Time 07:35 Sent To  
Notes
2014-06-27 07:36:02AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By hmoser Date 2014-05-28 Time 16:26 Rev Time 0.00
Received By hmoser Date 2014-05-28 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-08-12 Cont ID  
Sent By rmcdouga Date 2014-08-12 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2014-08-12 Time 16:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-08-05 Cont ID  
Sent By rmcdouga Date 2014-08-05 Time 07:01 Rev Time 0.00
Received By rmcdouga Date 2014-08-05 Time 06:58 Sent To  
Notes
2014-08-05 07:46:112010 FBC
  
 DENIED BY PLUMBING
  
 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN IS REQUIRED TO BE ON THE PLUMBING PLANS.
 CITY AMENDMENTS 107.2.1
  
 2) THE PLUMBING RISER DIAGRAM SHOWS A BAR SINK THAT IS
 NOT SHOWN ON THE ARCHITECTURAL PLANS. PLEASE CORRECT.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-27 Cont ID  
Sent By rmcdouga Date 2014-06-27 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2014-06-27 Time 07:34 Sent To  
Notes
2014-06-27 16:20:532010 FBC
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO SETS OF A PLUMBING RISER DIAGRAM AS
 REQUIRED BY CITY AMENDMENTS 107.3.5.3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-06-28 Cont ID  
Sent By rmcdouga Date 2014-06-28 Time 07:17 Rev Time 0.00
Received By rmcdouga Date 2014-06-28 Time 07:17 Sent To  
Notes
2014-06-28 07:37:56ROOFING PRODUCT APPROVALS:
  
 - FL1654 POLYGLASS - MODIFIED ROOFING SYSTEM (FLAT
 ROOF)
  
 - FL11288 CERTAINTEED - TILE UNDERLAYMENT
  
 - FL122328 TAMKO - 30 # UNDERLAYMENT
  
 - NOA NO. 10-1202.01 ENTEGRA - PLANTATION CONCRETE ROOF
 TILE
  
 - FL 6332 3M - AH160 ROOF TILE ADHESIVE

Review Stop Z ZONING
Rev No 2 Status P Date 2014-06-11 Cont ID  
Sent By dkittred Date 2014-06-11 Time 13:56 Rev Time 0.00
Received By dkittred Date 2014-06-11 Time 13:49 Sent To  
Notes
2014-08-06 18:09:578/6/14 - RESTAMPED APPROVED SHEETS IN REVISED PLAN
 SUBMITTAL. DK
  
2014-06-11 13:56:16PLANNING AND ZONING COMMENTS:
  
 6/11/4 (UPDATE TO COMMENTS FROM 5/29/14)
  
 1. SEPARATE LANDSCAPE PERMIT HAS BEEN SUBMITTED
 (14060377) AND IS UNDER REVIEW.
  
 GENERAL COMMENT:
 2. SEPARATE PERMITS WILL BE REQUIRED FOR THE POOL AND
 DRIVEWAY(S). PLEASE NOTE THAT ONLY ONE DRIVEWAY UP TO
 20 FEET WIDE OR TWO DRIVEWAYS UP TO 10 FEET WIDE EACH
 ARE PERMITTED ON THE SUBJECT PROPERTY (REF: ZLDR
 SECTION 94-313(1)(C) AND 94-482).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2014-05-29 Cont ID  
Sent By dkittred Date 2014-05-29 Time 10:13 Rev Time 0.00
Received By dkittred Date 2014-05-29 Time 09:28 Sent To  
Notes
2014-05-29 10:13:49PLANNING AND ZONING COMMENTS: ***FAILED***
  
 5/29/14
  
 COMMENT TO BE ADDRESSED FOR THIS PERMIT:
 1. SEPARATE LANDSCAPE PERMIT DEMONSTRATING COMPLIANCE
 WITH ZLDR SECTION 94-442(A)(2) AND 94-482, AS
 APPLICABLE, IS REQUIRED TO BE SUBMITTED PRIOR TO ZONING
 APPROVAL OF THE NEW SINGLE-FAMILY RESIDENCE.
  
 GENERAL COMMENT:
 2. SEPARATE PERMITS WILL BE REQUIRED FOR THE POOL AND
 DRIVEWAY(S). PLEASE NOTE THAT ONLY ONE DRIVEWAY UP TO
 20 FEET WIDE OR TWO DRIVEWAYS UP TO 10 FEET WIDE EACH
 ARE PERMITTED ON THE SUBJECT PROPERTY (REF: ZLDR
 SECTION 94-313(1)(C) AND 94-482).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-05-28 11:37:235/28/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved