| 2014-07-25 11:07:32 | DATE: 7/25/2014 |
| | PROJECT: MAHONEY RESIDENCE |
| | PERMIT#: 14050884 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A RISER DIAGRAM AND A LOAD CALCULATION TO |
| | INDICATE THE AREA IN SQUARE FEET OF THE BUILDING OR |
| | OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL |
| | CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE |
| | DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING |
| | DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO |
| | BE USED. NEC 215.5 FBC 107.2.1 |
| | |
| | 2) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI |
| | PROTECTED. NEC 210.8. THE OUTLET FOR THE GARAGE DOOR |
| | OPENER NEEDS TO BE INDENTIFIED AS BEING GFI PROTECTED. |
| | |
| | 3)AT LEAST ONE RECEPTACLE SHALL BE INSTALLED AT EACH |
| | ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF 600 MM |
| | (24 IN.) OR GREATER AND A SHORT DIMENSION OF 300 MM (12 |
| | IN.) OR GREATER. NEC 210.52(B)(2) |
| | |
| | PROVIDE A DETAIL INDICATING THE GROUNDING ELECTRODE |
| | SYSTEM IN COMPLIANCE WITH THE FOLLOWING NOTES: |
| | 4) ALL GROUNDING ELECTRODES AS DESCRIBED IN |
| | 250.52(A)(1) THROUGH (A)(7) THAT ARE PRESENT AT EACH |
| | BUILDING OR STRUCTURE SERVED SHALL BE BONDED TOGETHER |
| | TO FORM THE GROUNDING ELECTRODE SYSTEM. WHERE NONE OF |
| | THESE GROUNDING ELECTRODES EXIST, ONE OR MORE OF THE |
| | GROUNDING ELECTRODES SPECIFIED IN 250.52(A)(4) THROUGH |
| | (A)(8) SHALL BE INSTALLED AND USED. NEC 250.50 |
| | GROUNDING ELECTRODE SYSTEM. |
| | |
| | 5) THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR AT THE |
| | SERVICE, AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED |
| | BY A FEEDER(S) ORBRANCHCIRCUIT(S), OR AT A SEPARATELY |
| | DERIVED SYSTEM OF A GROUNDED OR UNGROUNDED AC SYSTEM |
| | SHALL NOT BE LESS THAN GIVEN IN TABLE 250.66, EXCEPT AS |
| | PERMITTED IN 250.66(A) THROUGH (C) NEC 250.66 SIZE OF |
| | ALTERNATING-CURRENT GROUNDING ELECTRODE CONDUCTOR. FOR |
| | A 300AMP SERVICE NEEDS A MINIMUM OF A #2CU GROUNDING |
| | ELECTRODE CONDUCTOR. |
| | |
| | 6) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| | INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| | FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| | ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| | DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| | STRUCTURES. NEC 250.94. |
| | |
| | 7) ALL METAL PIPING SYSTEMS SHALL BE BONDED. BOND COLD |
| | WATER PIPE, METAL GAS PIPING AND ANY EXPOSED STRUCTURAL |
| | STEEL WHEN AVAILABLE AS REQUIRED. NEC 250.104, |
| | |
| | 8) PROVIDE SPECIFICATIONS, AND CONNECTION DETAILS FOR |
| | STEAM GENERATOR INDICATING THE SUITABILITY FOR |
| | INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS |
| | OF THIS CODE. NEC 110.3(A)(1 THRU 8 |
| | |
| | 9) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE |
| | SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE |
| | LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS |
| | SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT |
| | CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32 |
| | KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS |
| | DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS |
| | THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| | MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE |
| | SUPPORTED. (D) BOXES AT CEILING-SUSPENDED (PADDLE) FAN |
| | OUTLETS. |
| | |
| | 10) NOTE ON THE PLANS THAT ALL CIRCUITRY REQUIRED TO |
| | HAVE ARC-FAULT CIRCUITRY INTURUPTING CAPACITY SHALL BE |
| | IN COMPLIANCE WITH THE PROVISIONS OF NEC 210.12, |
| | |
| | 11) NOTE ON THE PLANS THAT ALL NEW RECEPTACLES SHALL BE |
| | TAMPER RESISTANT IN COMPLIANCE WITH THE PROVISIONS OF |
| | NEC 406.11 |
| | |
| | 12) REVISE THE PLANS ACCORDINGLY TO INDICATE COMPLIANCE |
| | WITH ALL OF THE FOLLOWING: |
| | PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| | GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| | EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| | MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| | NEC 110.33(B) |
| | FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, AND |
| | BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING A |
| | SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE |
| | INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR |
| | CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE |
| | POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY |
| | TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED |
| | AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC |
| | 210.70(3) |
| | DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT FROM |
| | AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING OR |
| | REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS SHALL |
| | BE PERMITTED TO BE INSTALLED ON OR WITHIN THE |
| | AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14 |
| | INDICATE THE CIRCUITRY AND DISCONNECTING MEANS FOR THE |
| | A/C AHU IN THE ATTIC. |
| | |
| | AIR HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE |
| | FOLLOWING CONDITIONS ARE MET: |
| | 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| | SIX (6) FEET (1829 MM) OF AN ATTIC ACCESS. |
| | 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE |
| | UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| | PROPERLY. |
| | 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| | REPLACE THE AIR HANDLER. |
| | 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| | INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| | CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST |
| | PARAGRAPH IN BOLD: |
| | |
| | NOTICE TO HOMEOWNER |
| | A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR |
| | HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, |
| | EFFICIENT, AND ECONOMIC OPERATION OF THE AIR |
| | CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR |
| | MAINTENANCE IS PERFORMED. YOUR AIR CONDITIONING SYSTEM |
| | IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: |
| | 1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION |
| | DRAIN IS NOT WORKING PROPERLY OR; |
| | 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE |
| | CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL |
| | DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF |
| | SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER |
| | WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF |
| | PEAK OPERATION. FBC-M 306.3.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |