| Plan Review Stops For Permit 14050819 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-05-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-22 |
Time |
20:43 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-22 |
Time |
20:22 |
Sent To |
I |
|
| Notes |
| 2014-05-22 20:44:02 | APPROVED W/THE FOLLOWING NOTATIONS: | | | NOTES FOR PERMIT #14050819 | | | CARPORT WAS ENCLOSED UNDER PERMIT #13120985 W/O ANY | | | ELECTRIC. ALL ELECTRIC IN ENCLOSED AREA IS PART OF THIS | | | PERMIT OR HAS BEEN PERFORMED W/O THE BENEFIT OF A | | | PERMIT. | | | | | | AS PER NEC 210.8, ALL OUTLETS IN THE GARAGE SHALL BE | | | GFCI PROTECTED | | | AS PER NEC 406.11, ALL OUTLETS SHALL BE LISTED | | | TAMPER-RESISTANT | | | SMOKE DETECTORS AS PER FBC-R 314 & 315 SHALL BE | | | REQUIRED. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-05-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-22 |
Time |
20:44 |
Rev Time |
|
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
PC |
|
| Notes |
| 2014-05-22 20:45:12 | PROCESSED AND SENT TO READY RACK "O" OWNER BLDR. | | | | | 2014-05-21 14:36:08 | ROUTED TO ELECTRICAL LESS THAN $5000 |
|
|
|