Plan Review Details - Permit 14050798
Plan Review Stops For Permit 14050798
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-18 Cont ID  
Sent By jwitmer Date 2014-06-18 Time 14:01 Rev Time 0.00
Received By jwitmer Date 2014-06-18 Time 13:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-24 Cont ID  
Sent By jwitmer Date 2014-05-24 Time 10:39 Rev Time 0.00
Received By jwitmer Date 2014-05-24 Time 09:33 Sent To  
Notes
2014-05-24 10:38:43BUILDING PLAN REVIEW
 PERMIT: 14050798
 ADD: 1793 PALM BEACH LAKES # W409
 CONT: TBD
 TEL: (561)348-4805
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 24/ 2014
 ACTION: DENIED
  
 1) ARCHITECTURAL SHEETS STAMPED NOT SIGNED BY THE
 DESIGNER OF RECORD. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) ELECTRICAL SHEETS STAMPED NOT SIGNED BY THE DESIGNER
 OF RECORD. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
  
 3) SHEET A1.1 THE OCCUPANCY LOAD FOR THIS TENANT IS 59,
 2010 FBC-B TABLE 1015.1 REQUIRES 2 EXITS FOR A OCCUPANT
 LOAD GREATER THAN 49 FOR A MERCANTILE OCCUPANCY. PLEASE
 REVIEW THE CODE REQUIREMENTS FOR EXITING THROUGH A
 STORE ROOM, MISSING THE REQUIREMENT # 4, AISLE DEFINED
 BY FULL- OR PARTIAL-HEIGHT FIXED WALLS OR SIMILAR
 CONSTRUCTION .
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 4) EXCEPTION # 2
 2.1 MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2. .NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-16 Cont ID  
Sent By albarran Date 2014-06-16 Time 14:47 Rev Time 0.00
Received By albarran Date 2014-06-16 Time 14:25 Sent To  
Notes
2014-06-16 14:49:31THIS PERMIT WAS PREVIOUSLY REVIEWED AND APPROVED.
 APPARENTLY THE DESIGN PROFESSIONAL SUBMITTED NEW SHEETS
 TO ADDRESS COMMENTS FORM OTHER TRADES AND THE NEW SET
 REQUIRED STAMPING ONCE AGAIN.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By albarran Date 2014-05-28 Time 17:22 Rev Time 0.00
Received By albarran Date 2014-05-28 Time 16:16 Sent To  
Notes
2014-05-28 17:24:07THE SUBMITTED PLANS PASSED THE ELECTRICAL REVIEW, BUT
 THE PLANS NEED TO BE SIGNED AND AN ELECTRICAL PERMIT
 SECURED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-06-16 Cont ID  
Sent By pleduc Date 2014-06-16 Time   Rev Time 0.00
Received By pleduc Date 2014-06-16 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-06-03 Cont ID  
Sent By pleduc Date 2014-06-03 Time   Rev Time 0.00
Received By pleduc Date 2014-06-03 Time 10:40 Sent To Z
Notes
2014-06-03 11:03:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ALL FIRE ALARM WORK SHALL BE COMPLETED UNDER SEPARATE
 SHOP DRAWINGS BY A CERIFIED FIRE ALARM CONTRACTOR.
 PLEASE NOTE THIS ON THE SUBMITTAL IN THE APPROPRIATE
 PLACES.
  
 PLEASE REVIEW AND ADDRESS BUILDING COMMENTS AND
 RESUBMIT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-05 Cont ID  
Sent By shill Date 2014-07-05 Time 11:28 Rev Time 0.00
Received By shill Date 2014-06-13 Time 12:54 Sent To  
Notes
2014-06-14 12:56:39RE-SUB BACK TO C10.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-10 Cont ID  
Sent By eschneid Date 2014-06-10 Time 08:56 Rev Time 0.00
Received By eschneid Date 2014-05-21 Time 17:19 Sent To  
Notes
2014-05-23 17:20:04SENT TO B10 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-05-24 Cont ID  
Sent By jwitmer Date 2014-05-24 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2014-05-24 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By hmoser Date 2014-05-28 Time 09:51 Rev Time 0.00
Received By hmoser Date 2014-05-28 Time 09:51 Sent To  
Notes
2014-05-28 09:51:36PLAN REVIEW BY JS.PX1328

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-05-24 Cont ID  
Sent By jwitmer Date 2014-05-24 Time 10:39 Rev Time 0.00
Received By jwitmer Date 2014-05-24 Time 09:31 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status N Date 2014-06-09 Cont ID  
Sent By eschneid Date 2014-06-09 Time 18:21 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2014-06-09 18:21:41CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY'S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THE
 MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED HAS
 A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: "THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS.?
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A 'SAFE' CLIMATE
 WITHIN A BUILT ENVIRONMENT" RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS "QUALITY OF LIFE." A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER'S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS AND ANTI-THEFT TAGS
 ON MERCHANDISE.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
 (14) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
 (15) INTERIOR SHELVING AND DISPLAYS SHOULD BE NO HIGHER
 THAN FIVE FEET, EVEN LESS IN FRONT OF WINDOWS.
  
  
 OFFICER K. TUCKER-CARSILLO
 CRIME PREVENTION UNIT
 WEST PALM BEACH POLICE DEPT
 600 BANYAN BLVD
 WEST PALM BEACH, FL 33401
 (561) 822-1620 OFFICE
 (561) 822-1648 FAX
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-07-03 Cont ID  
Sent By eschneid Date 2014-07-03 Time 15:45 Rev Time 0.25
Received By eschneid Date 2014-07-03 Time 15:45 Sent To PC
Notes
2014-07-03 15:50:27SIGNS REQUIRE SEPARATE PERMITS WITH PLANS.
  
2014-07-01 16:35:357-1-14

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-09 Cont ID  
Sent By eschneid Date 2014-06-09 Time 18:00 Rev Time 0.75
Received By eschneid Date 2014-06-09 Time 18:00 Sent To  
Notes
2014-06-09 18:17:43FAILED
  
 1) THE REAR DOOR IS LISTED AS EXISTING, YET IT IS NOT
 SHOWN IN THE SAME LOCATION AS THE REAR DOOR ON THE AS
 BUILT SHELL PERMIT (SEE PERMIT REVISION 14040466).
 EITHER REVISE THE DRAWINGS OR PROVIDE CONSTRUCTION
 DRAWINGS FOR THE RELOCATED DOOR.
  
 2) THE ELEVATIONS DO NOT MATCH THE SHELL APPROVED
 ELEVATIONS. GLAZING IS DIFFERENT. EITHER REVISE THE
 DRAWINGS OR PROVIDE CONSTRUCTION DRAWINGS FOR THE NEW
 GLAZING.
  
 3) SIGNS REQUIRE SEPARATE PERMITS WITH PLANS.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822--1446.
2014-05-28 11:30:335/28/14