Plan Review Details - Permit 14050789
Plan Review Stops For Permit 14050789
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-03 Cont ID  
Sent By shill Date 2014-07-03 Time 17:01 Rev Time 0.00
Received By shill Date 2014-07-03 Time 17:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-17 Cont ID  
Sent By shill Date 2014-06-17 Time 17:03 Rev Time 0.00
Received By shill Date 2014-06-17 Time 17:03 Sent To  
Notes
2014-06-17 17:04:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 109, VALUE TO INCLUDE LABOR, MATERIALS,
 OVERHEAD, PROFIT, ENGINEERING. PROVIDE A COPY OF THE
 CONTRACT FOR THIS JOB.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-09 Cont ID  
Sent By dhayes Date 2014-07-09 Time 09:55 Rev Time 0.00
Received By dhayes Date 2014-07-09 Time 09:55 Sent To  
Notes
2014-07-09 10:02:34DATE: 7/9/2014
 PROJECT: BURGER KING
 PERMIT#: 1405789
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1)ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
 2)THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY.
 SUITABILITY FOR INSTALLATION AND USE SHALL BE IN
 CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-02 Cont ID  
Sent By dhayes Date 2014-06-02 Time 12:08 Rev Time 0.00
Received By dhayes Date 2014-06-02 Time 11:52 Sent To B
Notes
2014-06-02 12:08:055501 CORPORATE WAY
  
 1ST ELECTRICAL REVIEW.
  
 ACTION: DENIED.
  
 CODE REFFERENCE: 2008 EDITION OF THE NEC, 2010 EDITION
 OF THE FLORIDA BUILDING CODE.
  
 COMMENTS:
  
 1) DISCONNECT REQUIRED. NEC 600.6
  
 2) ADDITIONAL DETAILS REQUIRED ON HOW CIRCUITRY ENTERS
 THE SIGN. FBC 107.2.1
  
 3) ADDITIONAL DETAIL REQUIRED ON LOW VOLTAGE FOR THE
 SPEAKER WIRING. FBC 107.2.1
  
 4) PROVIDE DETAILS ON THE LOW VOLTAGE DATA AND SPEAKER
 CABLING FBC 107.2.1
  
 5) LOW VOLTAGE CABLES INSTALLED IN A WET LOCATION SHALL
 BE RATED FOR THE ENVIRONMENT IN WHICH THEY ARE
 INSTALLED. NEC 110.3
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-09 Cont ID  
Sent By dhayes Date 2014-07-09 Time 10:02 Rev Time 0.00
Received By dhayes Date 2014-07-03 Time 17:01 Sent To  
Notes
2014-07-03 17:01:357/3 TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-17 Cont ID  
Sent By shill Date 2014-06-17 Time 17:04 Rev Time 0.00
Received By shill Date 2014-05-21 Time 15:29 Sent To  
Notes
2014-05-21 15:30:06ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-22 Cont ID  
Sent By sgraham Date 2014-05-22 Time 12:05 Rev Time 0.00
Received By sgraham Date 2014-05-22 Time 12:05 Sent To E
Notes
***NONE***