Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-27 Cont ID  
Sent By rmcdouga Date 2014-08-27 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2014-08-27 Time 06:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-18 Cont ID  
Sent By rmcdouga Date 2014-07-18 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2014-07-18 Time 11:48 Sent To  
Notes
2014-07-18 16:41:172010 FBC
  
 DENIED BY BUILDING
  
 1) ON THE LATEST PLAN SUBMITTAL THE STORAGE SHED
 EXTENSION IS NOW BEING CALLED A CABANA WITH A BATH. A
 CABANA IS CONSIDERED LIVING SPACE AND WILL NEED AN
 IMPACT FEE REVIEW AND A CERTIFICATE OF OCCUPANCY IS
 REQUIRED BEFORE THE BUILDING CAN BE OCCUPIED. FBC
 EXISTING BUILDING 901.4
  
 2) THIS IS A CHANGE OF OCCUPANCY FROM A UTILITY TO AN
 R-3. THIS IS A CHANGE TO A HIGHER HAZARD CATEGORY PER
 THE FBC EXISTING BUILDING SECTION 912.3. THE EXISTING
 STRUCTURE IS REQUIRED TO BE ANALYZED AND IS REQUIRED TO
 COMPLY WITH THE WINDLOAD REQUIREMENTS FOR A RISK
 CATEGORY II STRUCTURE. FBC EXISTING BUILDING 907.2
  
 3) THE ROOM WITH THE CLOSET IS CONSIDERED A BEDROOM
 (SLEEPING ROOM) AND IS REQUIRED TO HAVE A WINDOW THAT
 COMPLIES WITH FBC EXISTING BUILDING 912.4.1 (EXCEPTION
 7) AND HAVE A CLEAR OPENING AREA OF NO LESS THAN 4
 SQUARE FEET WITH MINIMUM OPENING HEIGHT OF 22 INCHES
 AND MINIMUM OPENING WIDTH OF 20 INCHES AND A MAXIMUM
 SILL HEIGHT OF 44 INCHES.
  
 4) SMOKE ALARMS IN ACCORDANCE WITH FBCR 314 WILL BE
 REQUIRED. THERE IS ALSO ADDITIONAL ELECTRICAL
 REQUIREMENTS FOR A RESIDENTIAL OCCPANCY.
  
 5) FBC 306.4 FOR REQUIRED HOT AND COLD WATER FOR THE
 BATHROOM.
  
 6) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION
 SECTIONS 101.4.1 AND 103.2.
  
 7) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 WINDOWS AS REQUIRED BY DCA RULE 9N-3.
  
 8) SUBMIT TWO COPIES OF AN INSTALLATION SCHEDULE AND A
 KEY PLAN FOR THE STORM PANELS. SPECIFY THE ANCHOR TYPE,
 CONNECTION TYPE AND ANCHOR SPACING. SEE THE ANCHOR
 SCHEDULES ON SHEET 3 OF THE PRODUCT APPROVAL. CITY
 AMENDMENTS 107.2.1 AND 301.1
  
 9) THE PLANS SHOW 2 X 4 CEILING JOISTS SPANNING OVER 11
 FEET, WHICH EXCEEDS THE SPANS ALLOWED BY THE AF & PA
 TABLES. PLEASE CORRECT. FBC R801.2
  
 10) THE VALUE OF WORK ON THE PERMIT APPLICATION IS
 $3900.00. THIS IS TOO LOW FOR THE WORK THAT IS
 SPECIFIED . FOR PERMIT VALUATION PURPOSES THE VALUE IS
 THE TOTAL REPLACEMENT VALUE. PLEASE SUBMIT A COST
 BREAKDOWN INCLUDING LABOR, MATERIALS, DESIGN COSTS AND
 OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A
 CONTRACTOR. CITY AMENDMENT 109.3
  
 11) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW ITEMS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
 ***********************************THIS REVIEW IS NOT
 COMPLETE AT THIS TIME.
 ***************************************
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-23 Cont ID  
Sent By rmcdouga Date 2014-06-23 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2014-06-19 Time 19:00 Sent To  
Notes
2014-06-19 19:01:212010 FBC
  
 DENIED BY BUILDING
  
 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS
 107.2.1
  
 2) SUBMIT TO COPIES OF A SURVEY THAT SHOWS THE LOCATION
 OF THE EXISTING STORAGE BUILDING AND THE ADDITION AND
 THE DISTANCE TO PROPERTY LINES AND OTHER BUILDINGS ON
 THE SAME PROPERTY. FBC R302.1
  
 3) THE MEAN ROOF HEIGHT ON THE COVER SHEET IS LISTED AS
 30 FEET AND IT IS SPECIFIED AS 15 FEET ON SHEET 8.
 PLEASE CORRECT. CITY AMENDMENT 107.2.1
  
 4) ON SHEET 5.0 THE FOOTING IS SPECIFIED AS 8" X 12"
 WITH 6" ABOVE GRADE AND 6" BELOW GRADE. FBCR 403.1
 REQUIRES FOOTINGS TO BE A MINIMUM OF 12" WIDE AND FBCR
 403.1.4 REQUIRES THE BOTTOM OF FOOTINGS TO BE A MINIMUM
 OF 12" BELOW GRADE. PLEASE CORRECT.
  
 5) ON SHEET 6.0 THE RAFTER SPACING IS 1' 4" ON THE
 FRAMING PLAN AND 24" O.C. ON THE TYPICAL END DETAIL
 NOTE. PLEASE CORRECT. CITY AMENDMENT 107.2.1
  
 6) THE VALUE OF WORK ON THE PERMIT APPLICATION IS
 $3900.00. THIS APPEARS TO BE LOW FOR A BATHROOM
 ADDITION. FOR PERMIT VALUATION PURPOSES THE VALUE IS
 THE TOTAL REPLACEMENT VALUE. PLEASE SUBMIT A COST
 BREAKDOWN INCLUDING LABOR, MATERIALS, DESIGN COSTS AND
 OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A
 CONTRACTOR. CITY AMENDMENT 109.3
  
 7) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE OUTLOOKERS AT THE GABLE END. FBC R301.1 & R802.1.9
  
 8) SPECIFY THE CONNECTORS OR ANCHORS THAT WILL BE USED
 TO ATTACH THE WALLS TO THE SLAB. FBC R301.1
  
 9) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 EXTERIOR DOOR AND WINDOWS, THE SIMPSON CONNECTORS (
 MTS12, H2.5 AND A23) AS REQUIRED BY DCA RULE 9N-3.
  
 10) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. CITY AMENDMENT 107.2.1
 AND FBCR 301.1
  
 11) THE PLANS SHOW 2 X 4 CEILING JOISTS SPANNING OVER
 11 FEET, WHICH EXCEEDS THE SPANS ALLOWED BY THE AF & PA
 TABLES. PLEASE CORRECT. FBC R801.2
  
 12) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW ITEMS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-08-27 Cont ID  
Sent By rmcdouga Date 2014-08-27 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2014-08-27 Time 06:51 Sent To  
Notes
2014-08-27 10:31:08APPROVED WITH EXCEPTIONS. SEE RED-LINED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-07-23 Cont ID  
Sent By rmcdouga Date 2014-07-23 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2014-07-23 Time 06:42 Sent To  
Notes
2014-07-23 07:29:132010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 EXISTING STORAGE AREA THAT IS BEING CONVERTED TO LIVING
 SPACE SHALL COMPLY WITH THE FOLLOWING:
  
 1) PROVIDE LOAD CALCULATIONS AND A PANEL SCHEDULE FOR
 THE EXISTING 60 AMP PANEL. CITY AMENDMENTS 107.2.1 AND
 NEC 220.40
  
 2) COMPLY WITH NEC 210.52 (A) FOR RECEPTACLE OUTLET
 SPACING.
  
 3) COMPLY WITH NEC 210.70 FOR REQUIRED LIGHTING
 OUTLETS.
  
 4) SHOW COMPLIANCE WITH FBC 210.12 FOR ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION (AFCI).
  
 5) SHOW COMPLIANCE WITH FBC 406.11 FOR TAMPER-RESISTANT
 RECEPTACLES.
  
 6) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-22 Cont ID  
Sent By albarran Date 2014-05-22 Time 10:25 Rev Time 0.00
Received By albarran Date 2014-05-22 Time 09:34 Sent To  
Notes
2014-05-22 10:28:04APPROVED ELECTRICAL REVIEW WITH THE FOLLOWING PROVISO
 AND NOTATIONS ENTERED INTO THE PLANS.
  
 ELECTRICAL PROVISO FOR PT#14050684
 PER NEC 210.8 OUTLETS IN THE STG AREA SHALL BE GFCI
 PROTECTED.
 PER NEC 110.26(D) ILLUMINATION SHALL BE PROVIDED AT THE
 ELECTRICAL PANEL
 PER NEC 210.70(A)(2)(A) A WALL SWITCH CONTROLLED LIGHT
 SHALL BE PROVIDED IN THE STG.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-27 Cont ID  
Sent By rmcdouga Date 2014-08-27 Time 10:30 Rev Time 0.00
Received By rmcdouga Date 2014-08-22 Time 11:22 Sent To  
Notes
2014-08-22 11:23:54INCOMING SENT TO R. MCDOUGALS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-23 Cont ID  
Sent By rmcdouga Date 2014-07-23 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2014-07-08 Time 12:56 Sent To  
Notes
2014-07-08 12:56:55R06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-23 Cont ID  
Sent By rmcdouga Date 2014-06-23 Time 17:42 Rev Time 0.00
Received By rmcdouga Date 2014-05-19 Time 18:07 Sent To  
Notes
2014-05-19 18:09:14R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-08-27 Cont ID  
Sent By rmcdouga Date 2014-08-27 Time 06:51 Rev Time 0.00
Received By rmcdouga Date 2014-08-27 Time 06:51 Sent To  
Notes
2014-08-27 06:55:10PLANS WERE CHANGED TO SHOW THAT STRUCTURE IS FOR
 STORAGE. IMPACT FEES ARE NOT REQUIRED FOR STORAGE
 SPACE. NO HABITAL SPACE INDICATED ON THE PLANS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-07-18 Cont ID  
Sent By rmcdouga Date 2014-07-18 Time 16:53 Rev Time 0.00
Received By rmcdouga Date 2014-07-18 Time 16:53 Sent To  
Notes
2014-07-18 16:56:37A CABANA IS CONSIDERED HABITABLE SPACE AND AN IMPACT
 FEE REVIEW BY PALM BEACH COUNTY WILL BE REQUIRED AFTER
 THE PLANS HAVE BEEN APPROVED BY THE BUILDING
 DEPARTMENT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-06-19 Cont ID  
Sent By rmcdouga Date 2014-06-19 Time 18:58 Rev Time 0.00
Received By rmcdouga Date 2014-06-19 Time 18:58 Sent To  
Notes
2014-06-19 18:58:57IMPACT FEES ARE NOT REQUIRED FOR STORAGE SPACE. NO
 HABITAL SPACE INDICATED ON THE PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-06-03 Cont ID  
Sent By jsaez Date 2014-06-03 Time 14:14 Rev Time 0.00
Received By jsaez Date 2014-06-03 Time 14:13 Sent To  
Notes
2014-06-03 15:25:40MECHANICA PERMITL NOT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-19 Cont ID  
Sent By rmcdouga Date 2014-06-19 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2014-06-19 Time 18:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-08-22 Cont ID  
Sent By sgraham Date 2014-08-22 Time 11:43 Rev Time 0.00
Received By sgraham Date 2014-08-22 Time 11:43 Sent To B
Notes
2014-08-22 11:44:58NOTICE: ROOM TO BE USED AS A STORAGE ROOM ONLY, NO
 SLEEPING IS ALLOWED, ZONING-SF7. SG

Review Stop Z ZONING
Rev No 2 Status P Date 2014-07-15 Cont ID  
Sent By sgraham Date 2014-07-15 Time 09:16 Rev Time 0.00
Received By sgraham Date 2014-07-15 Time 09:16 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-06 Cont ID  
Sent By sgraham Date 2014-06-06 Time 12:09 Rev Time  
Received By sgraham Date   Time   Sent To  
Notes
2014-05-21 15:30:335/21/14 ZONING FAILED
 1.PROVIDE 2 SURVEYS
 2. NO KITCHEN ALLOWED
 3. PROVIDE A FLOOR PLAN SHOWING A CABANA NOT STORAGE
2014-05-21 14:54:015/21/14