| Plan Review Stops For Permit 14050689 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-27 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-27 |
Time |
06:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-18 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-18 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2014-07-18 16:41:17 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) ON THE LATEST PLAN SUBMITTAL THE STORAGE SHED | | | EXTENSION IS NOW BEING CALLED A CABANA WITH A BATH. A | | | CABANA IS CONSIDERED LIVING SPACE AND WILL NEED AN | | | IMPACT FEE REVIEW AND A CERTIFICATE OF OCCUPANCY IS | | | REQUIRED BEFORE THE BUILDING CAN BE OCCUPIED. FBC | | | EXISTING BUILDING 901.4 | | | | | | 2) THIS IS A CHANGE OF OCCUPANCY FROM A UTILITY TO AN | | | R-3. THIS IS A CHANGE TO A HIGHER HAZARD CATEGORY PER | | | THE FBC EXISTING BUILDING SECTION 912.3. THE EXISTING | | | STRUCTURE IS REQUIRED TO BE ANALYZED AND IS REQUIRED TO | | | COMPLY WITH THE WINDLOAD REQUIREMENTS FOR A RISK | | | CATEGORY II STRUCTURE. FBC EXISTING BUILDING 907.2 | | | | | | 3) THE ROOM WITH THE CLOSET IS CONSIDERED A BEDROOM | | | (SLEEPING ROOM) AND IS REQUIRED TO HAVE A WINDOW THAT | | | COMPLIES WITH FBC EXISTING BUILDING 912.4.1 (EXCEPTION | | | 7) AND HAVE A CLEAR OPENING AREA OF NO LESS THAN 4 | | | SQUARE FEET WITH MINIMUM OPENING HEIGHT OF 22 INCHES | | | AND MINIMUM OPENING WIDTH OF 20 INCHES AND A MAXIMUM | | | SILL HEIGHT OF 44 INCHES. | | | | | | 4) SMOKE ALARMS IN ACCORDANCE WITH FBCR 314 WILL BE | | | REQUIRED. THERE IS ALSO ADDITIONAL ELECTRICAL | | | REQUIREMENTS FOR A RESIDENTIAL OCCPANCY. | | | | | | 5) FBC 306.4 FOR REQUIRED HOT AND COLD WATER FOR THE | | | BATHROOM. | | | | | | 6) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION | | | SECTIONS 101.4.1 AND 103.2. | | | | | | 7) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | WINDOWS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 8) SUBMIT TWO COPIES OF AN INSTALLATION SCHEDULE AND A | | | KEY PLAN FOR THE STORM PANELS. SPECIFY THE ANCHOR TYPE, | | | CONNECTION TYPE AND ANCHOR SPACING. SEE THE ANCHOR | | | SCHEDULES ON SHEET 3 OF THE PRODUCT APPROVAL. CITY | | | AMENDMENTS 107.2.1 AND 301.1 | | | | | | 9) THE PLANS SHOW 2 X 4 CEILING JOISTS SPANNING OVER 11 | | | FEET, WHICH EXCEEDS THE SPANS ALLOWED BY THE AF & PA | | | TABLES. PLEASE CORRECT. FBC R801.2 | | | | | | 10) THE VALUE OF WORK ON THE PERMIT APPLICATION IS | | | $3900.00. THIS IS TOO LOW FOR THE WORK THAT IS | | | SPECIFIED . FOR PERMIT VALUATION PURPOSES THE VALUE IS | | | THE TOTAL REPLACEMENT VALUE. PLEASE SUBMIT A COST | | | BREAKDOWN INCLUDING LABOR, MATERIALS, DESIGN COSTS AND | | | OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A | | | CONTRACTOR. CITY AMENDMENT 109.3 | | | | | | 11) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW ITEMS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | | | | | | | | | | ***********************************THIS REVIEW IS NOT | | | COMPLETE AT THIS TIME. | | | *************************************** | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-06-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-06-23 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-06-19 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2014-06-19 19:01:21 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS | | | 107.2.1 | | | | | | 2) SUBMIT TO COPIES OF A SURVEY THAT SHOWS THE LOCATION | | | OF THE EXISTING STORAGE BUILDING AND THE ADDITION AND | | | THE DISTANCE TO PROPERTY LINES AND OTHER BUILDINGS ON | | | THE SAME PROPERTY. FBC R302.1 | | | | | | 3) THE MEAN ROOF HEIGHT ON THE COVER SHEET IS LISTED AS | | | 30 FEET AND IT IS SPECIFIED AS 15 FEET ON SHEET 8. | | | PLEASE CORRECT. CITY AMENDMENT 107.2.1 | | | | | | 4) ON SHEET 5.0 THE FOOTING IS SPECIFIED AS 8" X 12" | | | WITH 6" ABOVE GRADE AND 6" BELOW GRADE. FBCR 403.1 | | | REQUIRES FOOTINGS TO BE A MINIMUM OF 12" WIDE AND FBCR | | | 403.1.4 REQUIRES THE BOTTOM OF FOOTINGS TO BE A MINIMUM | | | OF 12" BELOW GRADE. PLEASE CORRECT. | | | | | | 5) ON SHEET 6.0 THE RAFTER SPACING IS 1' 4" ON THE | | | FRAMING PLAN AND 24" O.C. ON THE TYPICAL END DETAIL | | | NOTE. PLEASE CORRECT. CITY AMENDMENT 107.2.1 | | | | | | 6) THE VALUE OF WORK ON THE PERMIT APPLICATION IS | | | $3900.00. THIS APPEARS TO BE LOW FOR A BATHROOM | | | ADDITION. FOR PERMIT VALUATION PURPOSES THE VALUE IS | | | THE TOTAL REPLACEMENT VALUE. PLEASE SUBMIT A COST | | | BREAKDOWN INCLUDING LABOR, MATERIALS, DESIGN COSTS AND | | | OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A | | | CONTRACTOR. CITY AMENDMENT 109.3 | | | | | | 7) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH | | | THE OUTLOOKERS AT THE GABLE END. FBC R301.1 & R802.1.9 | | | | | | 8) SPECIFY THE CONNECTORS OR ANCHORS THAT WILL BE USED | | | TO ATTACH THE WALLS TO THE SLAB. FBC R301.1 | | | | | | 9) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | EXTERIOR DOOR AND WINDOWS, THE SIMPSON CONNECTORS ( | | | MTS12, H2.5 AND A23) AS REQUIRED BY DCA RULE 9N-3. | | | | | | 10) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE STORM PANELS. CITY AMENDMENT 107.2.1 | | | AND FBCR 301.1 | | | | | | 11) THE PLANS SHOW 2 X 4 CEILING JOISTS SPANNING OVER | | | 11 FEET, WHICH EXCEEDS THE SPANS ALLOWED BY THE AF & PA | | | TABLES. PLEASE CORRECT. FBC R801.2 | | | | | | 12) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW ITEMS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-27 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-27 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2014-08-27 10:31:08 | APPROVED WITH EXCEPTIONS. SEE RED-LINED PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-07-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-23 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-23 |
Time |
06:42 |
Sent To |
|
|
| Notes |
| 2014-07-23 07:29:13 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | EXISTING STORAGE AREA THAT IS BEING CONVERTED TO LIVING | | | SPACE SHALL COMPLY WITH THE FOLLOWING: | | | | | | 1) PROVIDE LOAD CALCULATIONS AND A PANEL SCHEDULE FOR | | | THE EXISTING 60 AMP PANEL. CITY AMENDMENTS 107.2.1 AND | | | NEC 220.40 | | | | | | 2) COMPLY WITH NEC 210.52 (A) FOR RECEPTACLE OUTLET | | | SPACING. | | | | | | 3) COMPLY WITH NEC 210.70 FOR REQUIRED LIGHTING | | | OUTLETS. | | | | | | 4) SHOW COMPLIANCE WITH FBC 210.12 FOR ARC-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION (AFCI). | | | | | | 5) SHOW COMPLIANCE WITH FBC 406.11 FOR TAMPER-RESISTANT | | | RECEPTACLES. | | | | | | 6) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-05-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-22 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-22 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2014-05-22 10:28:04 | APPROVED ELECTRICAL REVIEW WITH THE FOLLOWING PROVISO | | | AND NOTATIONS ENTERED INTO THE PLANS. | | | | | | ELECTRICAL PROVISO FOR PT#14050684 | | | PER NEC 210.8 OUTLETS IN THE STG AREA SHALL BE GFCI | | | PROTECTED. | | | PER NEC 110.26(D) ILLUMINATION SHALL BE PROVIDED AT THE | | | ELECTRICAL PANEL | | | PER NEC 210.70(A)(2)(A) A WALL SWITCH CONTROLLED LIGHT | | | SHALL BE PROVIDED IN THE STG. | | | | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-27 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-22 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2014-08-22 11:23:54 | INCOMING SENT TO R. MCDOUGALS DESK. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-07-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-23 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-08 |
Time |
12:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-06-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-06-23 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-05-19 |
Time |
18:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
N |
Date |
2014-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-27 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-27 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2014-08-27 06:55:10 | PLANS WERE CHANGED TO SHOW THAT STRUCTURE IS FOR | | | STORAGE. IMPACT FEES ARE NOT REQUIRED FOR STORAGE | | | SPACE. NO HABITAL SPACE INDICATED ON THE PLANS. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-07-18 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-07-18 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2014-07-18 16:56:37 | A CABANA IS CONSIDERED HABITABLE SPACE AND AN IMPACT | | | FEE REVIEW BY PALM BEACH COUNTY WILL BE REQUIRED AFTER | | | THE PLANS HAVE BEEN APPROVED BY THE BUILDING | | | DEPARTMENT. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2014-06-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-06-19 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-06-19 |
Time |
18:58 |
Sent To |
|
|
| Notes |
| 2014-06-19 18:58:57 | IMPACT FEES ARE NOT REQUIRED FOR STORAGE SPACE. NO | | | HABITAL SPACE INDICATED ON THE PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2014-06-03 |
|
|
Cont ID |
|
| Sent By |
jsaez |
Date |
2014-06-03 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jsaez |
Date |
2014-06-03 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2014-06-03 15:25:40 | MECHANICA PERMITL NOT REQUIRED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-06-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-06-19 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-06-19 |
Time |
18:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2014-08-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-08-22 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-08-22 |
Time |
11:43 |
Sent To |
B |
|
| Notes |
| 2014-08-22 11:44:58 | NOTICE: ROOM TO BE USED AS A STORAGE ROOM ONLY, NO | | | SLEEPING IS ALLOWED, ZONING-SF7. SG |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-07-15 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-07-15 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-07-15 |
Time |
09:16 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-06-06 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-06-06 |
Time |
12:09 |
Rev Time |
|
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-05-21 15:30:33 | 5/21/14 ZONING FAILED | | | 1.PROVIDE 2 SURVEYS | | | 2. NO KITCHEN ALLOWED | | | 3. PROVIDE A FLOOR PLAN SHOWING A CABANA NOT STORAGE | | 2014-05-21 14:54:01 | 5/21/14 |
|
|