Plan Review Details - Permit 14050634
| Plan Review Stops For Permit 14050634 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-07-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-31 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-30 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2014-07-30 17:22:49 | SENT TO J GOMEZ FOR REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-07-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-09 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-09 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2014-06-18 13:42:21 | TO JG DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-05-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-05-28 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-05-15 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2014-05-22 10:51:02 | TO JGOMEZ TO REVIEW WITH 14041079 | | 2014-05-15 15:25:40 | ROUTED TO MECHANICAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2014-07-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-31 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-31 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2014-07-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-09 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-09 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2014-07-09 08:50:19 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW | | | SECOND CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED: | | | EQUIPMENT SIZING CALCULATIONS TO INCLUDE THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS ALONG WITH THE SENSIBLE AND TOTAL COOLING | | | CAPACITIES AS REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY | | | CONSERVATION (REPEAT COMMENT). | | | | | | 2- A/C PLAN: | | | A) SIZE OF RETURN AIR TRANSFER DUCT IN THE MASTER | | | BEDROOM DOESN'T COMPLY WITH EXCEPTION #1 OF SEC. | | | M1602.4 OF 2010 FBC-RESIDENTIAL. THE SIZE OF THE | | | TRANSFER DUCT NEED TO BE INCREASED TO 14" MIN. NOTE: | | | ALL THE SUPPLY AIR INTO THE MASTER BEDROOM SHALL BE | | | INCLUDED WHEN SIZING THE DUCT. | | | | | | B) PROVIDE NAME, SIGNATURE AND LICENSE NUMBER OF THE | | | A/C CONTRACTOR DOING THE WORK AS REQUIRED BY FLORIDA | | | STATUTE 471.003 AND SEC. 107.2.1 CITY AMENDMENTS TO | | | FBC. | | | | | | C) PROVIDE AL THE EQUIPMENT INFORMATION (MANUFACTURER, | | | MODEL ETC). . AND LOCATION INCLUDING THE CONDENSER | | | UNIT. SEC. 107.3.5.3 CITY AMENDMENTS | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICE | | | (561)805-6712 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-05-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-05-28 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-05-28 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2014-05-28 13:49:19 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED: | | | CALCULATIONS ARE INCOMPLETE. CALCULATIONS NEED TO SHOW | | | THE EQUIPMENT MANUFACTURER AND MODEL NUMBER AS REQUIRED | | | BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- PLANS AND EQUIPMENT SIZING CALCULATIONS SUBMITTED | | | SHOW 2 EXISTING 2.5 TON UNITS. ACCORDING TO CITY | | | RECORDS THERE ARE NO PERMITS FOR THE A/C EQUIPMENT | | | REPLACEMENT IN THE LAST 14 YEARS. PROVIDE PROOF THAT | | | EQUIPMENT IS THE ORIGINAL EQUIPMENT OF THE HOUSE OR | | | PROVIDE COMPLETE INFORMATION AS REQUIRED BY SEC. | | | 101.4.7.1.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 3- A/C PLAN: | | | A) PROVIDE NAME AND SIGNATURE OF PERSON RESPONSIBLE FOR | | | THE DESIGN. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | B) PROVIDE AL THE EQUIPMENT INFORMATION (MANUFACTURER, | | | MODEL ETC). . AND LOCATION INCLUDING THE CONDENSER | | | UNIT. SEC. 107.3.5.3(1) CITY AMENDMENTS | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICE | | | (561)805-6712 |
|
|
|