Plan Review Details - Permit 14050542
Plan Review Stops For Permit 14050542
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-20 Cont ID  
Sent By jwitmer Date 2014-06-20 Time 16:10 Rev Time 0.00
Received By jwitmer Date 2014-06-20 Time 16:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 19:54 Rev Time 0.00
Received By jwitmer Date 2014-05-23 Time 07:30 Sent To  
Notes
2014-05-23 19:03:11BUILDING PLAN REVIEW
 PERMIT: 14050542
 ADD: 801 S OLIVE AVE SUITE # 114 & 113
 CONT: ATLANTIC WINDOW CO.
 TEL: (561)248-4552
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 23/ 2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE AFLOOR PLAN OF THE WHOLE UNIT, IT
 APPEARS A TENANT SEPERATION WALL IS BEING ELIMINATED
 JOINING TWO CONDOMINIUM UNITS TOGETHER. IF SO A UNITITY
 OF TITLE IS REQUIRED. UNITY OF TITLE. THE PROPOSED
 BUILDING STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM 'THE SITE'. A
 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. SEE WEBSITE
 FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
  
 2) THE PERMIT APPLICATION INDICATES THE REPLACE TILE
 FLOOR THROUGH OUT, PLEASE PROVIDE COMPLIANCE WITH;
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 2B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 3) THE VALUE OF THE PERMIT IS EXTREMLY LOW!!!! W P B
 ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-25 Cont ID  
Sent By dhayes Date 2014-06-25 Time 12:02 Rev Time 0.00
Received By dhayes Date 2014-06-25 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-21 Cont ID  
Sent By albarran Date 2014-05-21 Time 12:06 Rev Time 0.00
Received By albarran Date 2014-05-21 Time 11:08 Sent To  
Notes
2014-05-21 12:07:52FIRST REVIEW FOR PERMIT 14050542
  
 THE ABOVE PERMIT CAME UP FOR ELECTRICAL REVIEW THIS
 MORNING AND THE FOLLOWING DEFICIENCIES WERE NOTED:
 1. THE DECLARED VALUATION NEEDS TO BE ADJUSTED AS PER
 THE W P B ADMINISTRATIVE: CODE 109.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 2. THE ELECTRICAL NOTES REFER TO THE LATEST EDITION OF
 THE ELECTRICAL CODE. THOUGH THE 2011 EDITION IS OUT, IT
 HAS NOT BEEN ADOPTED AND THUS YOU SHALL COMPLY WITH THE
 2008 EDITION OF THE NEC.
 3. AS PER NEC 2008 SECTION 406.11, ALL NEW 125 VOLT, 15
 & 20 AMP RECEPTACLES IN DWELLING UNITS SHALL BE
 TAMPER-RESISTANT.
 4. AS PER NEC 210.8, ALL THE OUTLETS IN THE KITCHEN
 SHALL BE PROTECTED WITH GFCI.
 5. AS PER NEC 210.12, ALL NEW WIRING IN THE UNIT SHALL
 BE ARC-FAULT PROTECTED.
 6. FROM THE SUBMITTED DRAWING, IT IS NOT POSSIBLE TO
 DETERMINE IF A BACK SPLASH WILL BE USED AND/OR THE TYPE
 OF BACK SPLASH WHICH WILL BE USED. ALL NEW OUTLET BOXES
 IN THAT AREA SHALL COMPLY WITH THE DEPTH REQUIREMENTS
 OF NEC 314.21.
 7. OUTLET PLACEMENT REQUIREMENTS SHALL COMPLY WITH NEC
 210.52(B) & (C).
 8. SMOKE DETECTOR COMPLIANCE AS DICTATED IN FBC-R
 314.3.1 SHALL BE REQUIRED.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-25 Cont ID  
Sent By dhayes Date 2014-06-25 Time 12:03 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
2014-06-18 18:57:42SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 19:54 Rev Time 0.00
Received By jwitmer Date 2014-05-14 Time 13:48 Sent To  
Notes
2014-05-15 13:49:14SENT TO B9 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-20 Cont ID  
Sent By jwitmer Date 2014-06-20 Time 16:10 Rev Time 0.00
Received By jwitmer Date 2014-06-20 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 19:54 Rev Time 0.00
Received By jwitmer Date 2014-05-23 Time 07:37 Sent To  
Notes
2014-05-23 19:54:02PLUMBING PLAN REVIEW
 PERMIT: 14050542
 ADD: 801 S OLIVE AVE SUITE # 114 & 113
 CONT: ATLANTIC WINDOW CO.
 TEL: (561)248-4552
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 23/ 2014
 ACTION: DENIED
  
 1) THE NEW LOCATION OF THE KITCHEN SINK IS SHOWN TYING
 IN ON A POWDER ROOM WET VENT. THE WASTE TIE INTO THE
 WET VENT HAS TO HAPPEN PAST THE HORIZONTAL WET VENT
 BENEATH THE SLAB. 2010 FBC-P 909.2.1 HORIZONTAL WET
 VENT.
 THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT
 SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR
 ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR
 DRAIN. WHERE THE DRY-VENT CONNECTS TO A WATER CLOSET
 FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO
 THE HORIZONTAL WET-VENT SYSTEM. NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]