| Plan Review Stops For Permit 14050532 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-06-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-10 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-10 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2014-06-10 14:06:37 | GOOD MORNING EVERYONE, | | | | | | PLEASE REVIEW THE FOLLOWING INFORMATION AND UPDATE YOUR | | | RECORDS ACCORDINGLY. | | | | | | ADDRESSES HAVE BEEN ADDED TO PCN 74434315190030210 | | | FOLLOWING A PERMITTING REQUEST. | | | THE SITE HAS TWO EXISTING STRUCTURES: ONE FRONT AND ONE | | | BACK. EACH STRUCTURE CONTAINS TWO DWELLING UNITS | | | THE PRIMARY ADDRESS, 325 10TH ST (SITUSSEQ# 97573) IS | | | EXISTING AND WILL REMAIN AS THE PRIMARY SITE AND FRONT | | | STRUCTURE ADDRESS. | | | THE STRUCTURE HAS TWO UNIT AND ADDRESSES HAVE BEEN | | | ADDED: THE EAST USING IS 325 10TH ST #1 (SITUSSEQ | | | #1517659) AND THE WEST UNIT 325 10TH ST #2 (SITUSSEQ# | | | 1517660) | | | THE EXISTING REAR STRUCTURE ALSO HAS TWO UNITS EXISTING | | | UNITS. THE ADDRESS 327 10TH ST (SITUSSEQ# 1517658) HAS | | | BEEN ASSIGNED AS THE REAR BUILDING STRUCTURE ADDRESS | | | WHILE 327 10TH ST #1 (SITUSSEQ# 1517661) HAS BEEN | | | ASSIGNED AS THE SOUTH UNIT AND 327 10TH ST #2 | | | (SITUSSEQ# 1517662) HAS BEEN ASSIGNED AS THE NORTH | | | UNIT. | | | | | | | | | | | | THESE CHANGES HAVE BEEN MADE IN THE CITY OF WEST PALM | | | BEACH GIS AND COMMUNITYPLUS SYSTEMS AND THE PBC EPZB | | | SYSTEM | | | | | | | | | | | | SCOTT ALEF | | | GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | PUBLIC UTILITIES DEPARTMENT | | | 401 CLEMATIS ST., WEST PALM BEACH, FL 33401 | | | PHONE: 561-494-1094 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-07-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-11 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-11 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2014-07-11 10:24:25 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- SHEET #1: UNIT #2 SHOWS A PROPOSED BEDROOM WHERE THE | | | GARAGE WAS LOCATED. PROVIDE SPECIFICATIONS SHOWING HOW | | | THE FINISH FLOOR IS GOING TO BE RAISED TO COMPLY WITH | | | SEC. R404.1.6 OF 2010 FBC-RESIDENTIAL. | | | 2- REVISE ENERGY CALCULATIONS SUBMITTED: | | | A) THIS IS NOT A SINGLE FAMILY. IT'S MULTIPLE FAMILY | | | RESIDENCE ( SEE DEFINITIONS IN CHAPTER 2 OF ENERGY | | | CONSERVATION CODE). REVISE ALL THE INFORMATION ON PAGE | | | ONE AS REQUIRED. | | | B) ROOF IS NOT FLAT TILE/SLATE. SEE PLANS AND REVISE AS | | | REQUIRED. | | | C) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS | | | REQUIRED BY SEC. 103.2.3.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | 3- NEW COMMENT: | | | ENERGY CALCULATIONS ARE TAKING THE CEILING FAN CREDIT. | | | PLANS TO SHOW CEILING FANS AND SIZE IN ALL ROOMS AS | | | REQUIRED BY SEC. 405.6.6 AND TABLE 405.6.6 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | 4- ENGINEER TO REVISE TENANT SEPARATION DETAIL: | | | NATIONAL GYPSUM COMPANY INFORMATION SUBMITTED SHOWS WP | | | 3605 ASSEMBLY WITH NOT INSULATION INCLUDED. NEED | | | APPROVED ASSEMBLY THAT INCLUDES THE INSULATION. | | | ***NOTE: ASSEMBLY WP 3241 SHOWN ON THE SAME PAGE | | | SUBMITTED INCLUDES THE INSULATION. REVISE DETAIL TO | | | MATCH WP3605 ASSEMBLY. | | | 5- ENGINEER OF RECORD TO APPROVE DOORS AND WINDOWS | | | PRODUCT APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-09 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2014-06-09 18:59:50 | RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- SHEET #1: UNIT #2 SHOWS A PROPOSED BEDROOM WHERE THE | | | GARAGE WAS LOCATED. PROVIDE SPECIFICATIONS SHOWING HOW | | | THE FINISH FLOOR IS GOING TO BE RAISED TO COMPLY WITH | | | SEC. R404.1.6 OF 2010 FBC-RESIDENTIAL. | | | | | | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.4.3 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- TENANT SEPARATION DETAIL: PROVIDE TENANT SEPARATION | | | ASSEMBLY NUMBER (UL LISTING OR GYPSUM BOARD LISTING) | | | USING 2 X 4 WOOD STUDS INSTEAD OF METAL STUDS TO VERIFY | | | COMPLIANCE WITH SEC. R302.3 OF 2010 FBC-RESIDENTIAL. | | | ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE WITH ASTM E | | | 119 OR UL 263. | | | | | | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF SHINGLES. | | | | | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS. | | | | | | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-05-28 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-28 |
Time |
19:50 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-28 |
Time |
19:33 |
Sent To |
|
|
| Notes |
| 2014-05-28 19:51:35 | APPROVED THE ELECTRICAL REVIEW WITH THE FOLLOWING | | | PROVISOS: | | | ELECTRICAL PROVISO FOR PERMIT: 140500532 | | | 1. OUTLET PLACEMENT AS INDICATED ON PLANS DOES NOT | | | COMPLY WITH THE REQUIREMENTS OF NEC 210.52. FIELD | | | VERIFY OUTLET SPACING TO COMPLY WITH WALL, HALLWAY AND | | | KITCHEN COUNTER REQUIREMENTS. | | | 2. CEILING OUTLET BOXES FOR LUMINAIRES SHALL COMPLY | | | WITH NEC 314.27 AND BE LISTED TO SUPPORT 50 LBS. | | | 3. FOR MORE EFFECTIVE ENERGY CONSERVATION, YOU SHOULD | | | USE 3 WAY SWITCHING OF LIGHTING WHEREVER POSSIBLE. | | | 4. PER FBC-R 303.8 YOU SHALL PROVIDE HEATING, THEREFORE | | | THE WALL A/C UNITS SHALL BE REVERSIBLE. | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-07-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-18 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-25 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2014-07-21 09:52:18 | LAST REVIEW DONE 7/18/14 BY ZONING. JG. | | 2014-07-18 15:26:19 | TO STEVE KENNEDY FOR PROCESSING. | | 2014-07-14 08:56:33 | 7/15/14 RE-SUBMITTAL SENT TO ZONING SHELF FOR ANA'S | | | REVIEW. JG. | | 2014-07-11 09:16:54 | CONTRACTOR SUBMITTED CORRECTIONS ON 6/25/14 ALONG WITH | | | CORRECTIONS FOR 14050531 (FRONT BUILDING). JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-05-14 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2014-05-14 14:20:07 | EXPEDITED SENT TO R3 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
18:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-09 |
Time |
18:37 |
Sent To |
|
|
| Notes |
| 2014-06-09 18:39:19 | MU-2014-3662. NO FEES DUE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-07-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-15 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-15 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-06-05 |
|
|
Cont ID |
|
| Sent By |
jsaez |
Date |
2014-06-05 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
jsaez |
Date |
2014-06-05 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2014-06-05 12:00:39 | 1. NO MECHANICAL PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-07-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-11 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-11 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-06-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-09 |
Time |
19:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2014-07-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-07-11 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-07-11 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2014-07-11 11:06:07 | SHINGLES NOA 13-0419.04. JG. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2014-06-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-06-09 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-06-09 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2014-06-09 19:00:59 | RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF SHINGLES. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-07-18 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2014-07-18 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2014-07-18 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2014-07-18 15:26:01 | LANDSCAPE AND SITE IMPROVEMENTS PER PERMIT NO. 14050531 | | | (FRONT STUCTURE). |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2014-05-30 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2014-05-30 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2014-05-30 12:10:19 | 1. ADDITIONAL PARKING SPACE ALONG STREET FRONTAGE IS | | | NOT PERMITTED.EXISTING CURB CUT CANNOT BE | | | EXPANDED/WIDENED. | | | 2. PARKING SPACES FROM ALLEY SHALL PROVIDE A MINIMUM OF | | | 24' OF BACK UP AREA. THE EXISTING 15 FOOT WIDE ALLEY | | | CAN BE COUNTED AS PART OF THAT AREA. | | | 3. PARKING SPACES ON ALLEY SHALL BE SCREENED WITH A 5' | | | LANDSCAPE BUFFER AND A HEDGE 24" AT PLANTING. | | | 4. ALL MECHANICAL EQUIPMENT (AC UNITS) SHALL BE | | | ENCLOSED AND SCREENED. | | | 5. PROPOSED LANDSCAPE DOES NOT MATCH PROPOSED ENTRANCE | | | ON MAIN BUILDING. | | | 6. PARKING SPACES FROM ALLEY SHALL BE STRIPED ACCORDING | | | TO CITY CODE. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439 | | 2014-05-15 16:38:35 | 5/15/14 |
|
|