Plan Review Details - Permit 14050520
Plan Review Stops For Permit 14050520
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-05-25 Cont ID  
Sent By JWITMER Date 2014-05-25 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2014-05-25 Time 06:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-20 Cont ID  
Sent By ALBARRAN Date 2014-05-20 Time 10:18 Rev Time 0.00
Received By albarran Date 2014-05-20 Time 09:19 Sent To B
Notes
2014-05-20 10:21:00BECAUSE THIS IS AN EXPEDITED PLAN I WALKED IT TO JIM IN
 BLDG. PER SAK.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-05-25 Cont ID  
Sent By MGONZALE Date 2014-05-25 Time   Rev Time 1.00
Received By mgonzale Date 2014-05-25 Time   Sent To I
Notes
2014-05-25 19:22:12NO CONFLICT WITH UTILITIES
  
 CONTRACTOR / EOR TO CERTIFY TO THE CITY OF WPB.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-22 Cont ID  
Sent By WJOLIN Date 2014-05-22 Time   Rev Time 0.00
Received By pleduc Date 2014-05-22 Time 09:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-28 Cont ID  
Sent By jwitmer Date 2014-05-28 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2014-05-14 Time 11:33 Sent To  
Notes
2014-05-19 11:41:05IN HAROLD'S OFFICE AS OF 5/19.
2014-05-14 11:34:23EXPEDITED REVISION SENT TO C13 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-20 Cont ID  
Sent By HMOSER Date 2014-05-20 Time 06:56 Rev Time 0.00
Received By hmoser Date 2014-05-20 Time 06:56 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-25 Cont ID  
Sent By JWITMER Date 2014-05-25 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2014-05-25 Time 06:32 Sent To  
Notes
2014-05-25 08:12:36PLUMBING PLAN REVIEW
 REVISION: 14050520
 PERMIT: 13121076
 ADD: 8156 OKEECHOBEE BLVD
 CONT: P & T CONSTRUCTION
 TEL: (561)324-8055
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. MAY 25/ 2014
 ACTION: PLUMBING PROVISO
 PLUMBNG APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
 REVISION REQUIRED!!!
  
 1A) DISCREPANCY IN PLANS, PLEASE REVIEW REVISION # 4
 P-1.1 VERSES P-3.1, IN SHEET P-1.1 THE PLANS INDICATE A
 CHANGE IN VENT LOCATION AND VENT SIZE TO THE EMERGENCY
 FLOOR DRAIN TO A 1 1/2 INCHES, SHEET P-3.1 THE
 ISOMETRIC FOR THIS FLOOR DRAIN THE DIMENSION IS NOT
 CLEAR EITHER A 2" OR 2 1/2" WHICH WAS ON THE ORIGINAL
 PLANS. PLEASE CORRECT THE DISCREPANCY.
  
 1B) IN RE-REVIEWING THE EMERGENCY FLOOR DRAIN SANITARY
 AND VENTING, THE PLANAS DO NOT INDICATE THE SIZE OF THE
 SANITARY LINE, SHEET P-6.2 UNDER THE HEADING FD-1 ZURN
 Z415B THE OUTLET CAN BE A 2 INCH, 3 INCH OR 4 INCH IN
 SIZE NOT KNOWING THE SANITARY SIZING THE PROPER VENT
 SIZE CAN NOT BE ESTABLISHED, SEE 2010 FBC-PLUMBING
 916.2 VENTS OTHER THAN STACK VENTS OR VENT STACKS. THE
 DIAMETER OF INDIVIDUAL VENTS, BRANCH VENTS, CIRCUIT
 VENTS AND RELIEF VENTS SHALL BE AT LEAST ONE-HALF THE
 REQUIRED DIAMETER OF THE DRAIN SERVED. THE REQUIRED
 SIZE OF THE DRAIN SHALL BE DETERMINED IN ACCORDANCE
 WITH TABLE 710.1(2). VENT PIPES SHALL NOT BE LESS THAN
 11/4 INCHES (32 MM) IN DIAMETER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-22 Cont ID  
Sent By ERIC Date 2014-05-22 Time 15:28 Rev Time 0.50
Received By eschneid Date 2014-05-22 Time 15:28 Sent To  
Notes
***NONE***