Plan Review Details - Permit 14050494
Plan Review Stops For Permit 14050494
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-30 Cont ID  
Sent By dhayes Date 2014-05-30 Time 16:28 Rev Time 0.00
Received By dhayes Date 2014-05-30 Time 16:28 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-22 Cont ID  
Sent By dhayes Date 2014-05-22 Time 09:50 Rev Time 0.00
Received By dhayes Date 2014-05-22 Time 09:50 Sent To  
Notes
2014-05-22 10:05:55ELECTRICAL PLAN REVIEW HAS BEEN FOUND TO BE DEFICIENT
 IN THE AREAS LISTED BELOW. COMPLIANCE SHALL BE BASED ON
 THE 2008 NEC, THE 2010 FBC, AND THE 2007 NFPA 72
  
 1) SMOKE DETECTORS ARE INDICATED ON THE FLOOR PLAN BUT
 NOT ON THE RISER DIAGRAM. THE SMOKE DETECTORS WILL HAVE
 TO TIE TO THE EXISTING FACP. PLEASE INDICATE WITH A
 LINE DIAGRAM HOW THIS WILL BE ACCOMPLISHED.
  
 2) THE SMOKE DETECTORS SHALL BE COMPATABLE TO THE
 EXISTING FACP. PLEASE INDICATE ON THE PLAN THE
 MANUFACTURER OF THE FACP AND SUBMIT SUPPORTING
 DOCUMENTATION INDICATING COMPATABILITY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-06-03 Cont ID  
Sent By pleduc Date 2014-06-03 Time 15:00 Rev Time 0.00
Received By pleduc Date 2014-06-03 Time 14:54 Sent To PC
Notes
2014-05-30 14:48:37NEW SHEETS SUBMITTED. NEED TO RE-STAMP. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-16 Cont ID  
Sent By pleduc Date 2014-05-16 Time   Rev Time 0.00
Received By pleduc Date 2014-05-16 Time 12:20 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2014-06-03 Cont ID  
Sent By pleduc Date 2014-06-03 Time   Rev Time 0.00
Received By pleduc Date 2014-05-29 Time 14:47 Sent To PC
Notes
2014-05-30 14:47:57RESUBMITTAL SENT TO DAVID HAYES' FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-12 Cont ID  
Sent By jlmitch Date 2014-06-12 Time 10:00 Rev Time  
Received By jlmitch Date   Time   Sent To  
Notes
2014-05-13 16:39:34ROUTED TO FIRE


Account Summary | Usage Policy | Privacy Policy