Plan Review Details - Permit 14050490
Plan Review Stops For Permit 14050490
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-05-14 Cont ID  
Sent By skennedy Date 2014-05-14 Time 10:53 Rev Time 0.00
Received By skennedy Date 2014-05-14 Time 10:53 Sent To Z
Notes
2014-05-14 10:55:13NO SUB-STRUCTURAL REQUIRED , INCIDENTAL WORK TO BE
 UNDER PRIMARY PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-01 Cont ID  
Sent By dhayes Date 2014-07-01 Time 10:27 Rev Time 0.00
Received By dhayes Date 2014-07-01 Time 10:27 Sent To  
Notes
2014-07-01 10:35:51DATE: 7/1/2014
 PROJECT: OAKTON COMMONS CHARTER SCHOOL
 PERMIT#: 14050490
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) THE PLANS INDICATE THE USE OF A TIME CLOCK TO
 CONTROL A LIGHTING CONTACTOR. WHEN USING A TIME CLOCK
 INDICATE THE MINIMUM 10HR REQUIRED PROGRAM BACKUP TIME.
 FBC 505.2.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-14 Cont ID  
Sent By dhayes Date 2014-05-14 Time 09:43 Rev Time 0.00
Received By dhayes Date 2014-05-14 Time 07:26 Sent To B
Notes
2014-05-14 09:07:58ELECTRICAL PROVISO:
  
  PLEASE BE SURE TO SEE 2010 FBC SECTION 505.2.4 FOR
 EXTERIOR LIGHTING CONTROLS REQUIRED. THERE ARE ONE OF
 TWO METHODS PERMITTED FOR CONTROLS. YOUR PLANS INDICATE
 THE USE OF A TIME CLOCK TO CONTROL
 A LIGHTING CONTACTOR. IF USING A TIME CLOCK PLEASE BE
 SURE TO LIST THE MINIMUM REQUIRED PROGRAMMING BATTERY
 BACKUP TIME. THE CODE REQUIRES 10HRS MINIMUM
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-01 Cont ID  
Sent By dhayes Date 2014-07-01 Time 10:36 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-29 Cont ID  
Sent By eschneid Date 2014-05-29 Time 14:40 Rev Time 0.00
Received By eschneid Date 2014-05-13 Time 16:23 Sent To  
Notes
2014-05-13 16:23:18ROUTED TO ELECTRICAL

Review Stop Z ZONING
Rev No 2 Status P Date 2014-07-01 Cont ID  
Sent By eschneid Date 2014-07-01 Time 09:06 Rev Time 0.25
Received By eschneid Date 2014-07-01 Time 09:06 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-05-29 Cont ID  
Sent By eschneid Date 2014-05-29 Time 14:31 Rev Time 0.50
Received By eschneid Date 2014-05-29 Time 14:31 Sent To  
Notes
2014-05-29 14:40:41FAILED
  
 1) THE OAKTON COMMONS DESIGN GUIDELINES SPECIFY, "ALL
 OUTDOOR LIGHTING FIXTURES SHALL NOT EXCEED TWENTY-FIVE
 (25) FEET IN HEIGHT, MEASURED FORM FINISHED GRADE TO
 HIGHEST POINT." THE LIGHT POLE STRUCTURE DETAIL SHOWS
 AN EXTENSION (THE ACTUAL LIGHT?) EXCEEDING THE 25 FOOT
 MEASURE POINT.
  
 2) THE CITY'S PLANNED DEVELOPMENT REGULATIONS SPECIFY
 THAT THE LIGHT LEVEL SHALL NOT EXCEED ONE (1) FOOT
 CANDLE AT OR BEYOND THE PROPERTY LINE. THE PHOTOMETRIC
 CALCULATIONS SHALL BE SHOWN AT THE PROPERTY LINE ALONG
 THE OKEECHOBEE BOULEVARD PROPERTY LINE AND SHALL NOT
 EXCEED ONE (1) FOOT CANDLE.
  
 3) THE LIGHT POLES THEMSELVES ARE IN APPROVED
 LOCATIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.