| Plan Review Stops For Permit 14050396 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-05-13 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-13 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-13 |
Time |
09:39 |
Sent To |
I |
|
| Notes |
| 2014-05-13 10:51:54 | ELECTRICAL PROVISOS FOR PERMIT #14050396 | | | THE LACK OF SUPPORTING DOCUMENTS MAKES WAY FOR THE | | | FOLLOWING NOTATIONS AND/OR RESTRICTIONS. | | | | | | IF THE AIR HANDLER IS TO BE INSIDE THE ATTIC, THE | | | REQUIREMENTS OF NEC 110.33(B) WILL REQUIRE THAT A | | | PERMANENT LADDER BE ADDED TO THE ATTIC ACCESS. PROPER | | | LIGHTING AS REQUIRED BY | | | NEC 210.70 (A)(3) SHALL BE PROVIDED. A GUARD AROUND THE | | | LAMP AS REQUIRED IN NEC 410.11 SHALL BE REQUIRED. IN | | | ADDITION TO THIS, THE OUTLET REQUIRED BY NEC 210.63, | | | SHALL COMPLY W/NEC 210.8. | | | | | | FLORIDA BLDG. CODE RESIDENTIAL SECTION 314 REQUIRES | | | THAT YOU COME INTO COMPLIANCE WITH THE SMOKE DETECTOR | | | REQUIREMENTS FOR FINAL INSPECTION. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-05-13 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-13 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-12 |
Time |
12:05 |
Sent To |
PC |
|
| Notes |
| 2014-05-13 10:52:39 | CONTACTED EC W/STATUS UPDATE | | 2014-05-12 12:06:46 | <5000 ELEC |
|
|
|