Plan Review Details - Permit 14050396
Plan Review Stops For Permit 14050396
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-13 Cont ID  
Sent By albarran Date 2014-05-13 Time 10:51 Rev Time 0.00
Received By albarran Date 2014-05-13 Time 09:39 Sent To I
Notes
2014-05-13 10:51:54ELECTRICAL PROVISOS FOR PERMIT #14050396
 THE LACK OF SUPPORTING DOCUMENTS MAKES WAY FOR THE
 FOLLOWING NOTATIONS AND/OR RESTRICTIONS.
  
 IF THE AIR HANDLER IS TO BE INSIDE THE ATTIC, THE
 REQUIREMENTS OF NEC 110.33(B) WILL REQUIRE THAT A
 PERMANENT LADDER BE ADDED TO THE ATTIC ACCESS. PROPER
 LIGHTING AS REQUIRED BY
 NEC 210.70 (A)(3) SHALL BE PROVIDED. A GUARD AROUND THE
 LAMP AS REQUIRED IN NEC 410.11 SHALL BE REQUIRED. IN
 ADDITION TO THIS, THE OUTLET REQUIRED BY NEC 210.63,
 SHALL COMPLY W/NEC 210.8.
  
 FLORIDA BLDG. CODE RESIDENTIAL SECTION 314 REQUIRES
 THAT YOU COME INTO COMPLIANCE WITH THE SMOKE DETECTOR
 REQUIREMENTS FOR FINAL INSPECTION.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-13 Cont ID  
Sent By albarran Date 2014-05-13 Time 10:52 Rev Time 0.00
Received By albarran Date 2014-05-12 Time 12:05 Sent To PC
Notes
2014-05-13 10:52:39CONTACTED EC W/STATUS UPDATE
2014-05-12 12:06:46<5000 ELEC