| Plan Review Stops For Permit 14050342 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-06-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-10 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-10 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-06-02 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-02 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-02 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2014-06-02 14:04:38 | 1ST REVIEW 6/2/14 | | | | | | PLEASE SUBMIT NEW PLANS AS FOLLOWS: | | | | | | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, OR OTHER ACCEPTABLE MEDIUM. THE | | | QUALITY OF THE PLAN IS INSUFFICIENT. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-06-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-10 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-06-10 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2014-06-10 09:49:11 | THIS FILE WAS APPROVED WITH A COUPLE OF MISSING OUTLETS | | | DRAWN ON THE PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-05-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-21 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-21 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2014-06-02 14:19:25 | SUPPLEMENTAL COMMENTS | | | | | | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, OR OTHER ACCEPTABLE MEDIUM. THE | | | QUALITY OF THE PLAN IS INSUFFICIENT. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | | | | | | 2014-05-21 16:38:48 | FAILED FIRST REVIEW AS FOLLOWS: | | | NOT ENOUGH ELECTRICAL INFORMATION FOR A SUCCESSFUL | | | REVIEW. YOU SHALL PROVIDE A LAYOUT OF THE PROPOSED | | | KITCHEN WITH CABINETS AND THE REQUIRED OUTLETS MARKED. | | | YOU SHALL INCLUDE THE REQUIRED NOTES AND APPLICABLE | | | CODE. | | | INDICATE IF THE NEW COOK TOP AND DOUBLE OVEN ARE GAS | | | PROVIDE A PANEL SCHEDULE | | | | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2014-06-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-10 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-10 |
Time |
08:01 |
Sent To |
E |
|
| Notes |
| 2014-06-10 08:20:58 | SENT TO MIKE ALBARRAN'S DESK FOR ELECTRICAL REVIEW. | | 2014-06-10 08:19:49 | GAS 2ND REVIEW: | | | | | | THIS SUBMITTAL DOES NOT CONTAIN A PERMIT APPLICATION | | | FOR GAS OR ADEQUATE INFORMATION AS TO A GAS RISER FOR | | | THE PROPOSED RINIA TANKLESS WATER HEATER. | | | MINIMUM PLAN REVIEW REQUIREMENTS: FBC 107.3.5.3 | | | RESIDENTIAL - GAS PIPING, COMBUSTION AIR VENTING, | | | APPLIANCES, TYPE OF GAS. | | | | | | APPLICANT HAS CHOOSEN TO APPLY FOR A GAS PERMIT | | | SEPARATLY. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2014-06-02 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-02 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-02 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2014-06-02 14:10:47 | 1ST REVIEW: 6/2/14 | | | | | | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, OR OTHER ACCEPTABLE MEDIUM. THE | | | QUALITY OF THE PLAN IS INSUFFICIENT. | | | | | | RESIDENTIAL (ONE AND TWO-FAMILY) MINIMUM PLAN REVIEW | | | CRITERIA;107.3.5.3 | | | GAS PIPING | | | VENTING | | | COMBUSTION AIR | | | APPLIANCES | | | TYPE OF GAS | | | RISER DIAGRAM/SHUTOFFS | | | PROVIDE A GAS RISER DIAGRAM AND SPECIFICATIONS FOR THE | | | PROPOSED TANKLESS WATER HEATER. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-06-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-10 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-05 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2014-06-06 10:48:24 | RESUBMITTAL SENT TO STEVE KENNEDY'S DESK FOR REVIEW. | | | JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-06-02 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-02 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-09 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-06-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-10 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-10 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-06-02 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-02 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-06-02 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2014-06-02 14:14:34 | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, OR OTHER ACCEPTABLE MEDIUM. THE | | | QUALITY OF THE PLAN IS INSUFFICIENT. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|