| 2014-05-13 07:55:43 | ELECTRICAL REVIEW DENIED. THE ELECTRICAL SYSTEM IS |
| | FOUND TO BE DEFICIENT IN THE FOLLOWING AREAS BASED ON |
| | 2008 EDITION OF THE NEC AND THE 2010 FBC, FBC RES., FBC |
| | ENERGY, SEE COMMENTS BELOW. |
| | |
| | 1) AT LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED |
| | LIGHT FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 404.1 |
| | |
| | 2) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED. |
| | FBC-R402.4.5 |
| | |
| | 3) ARC-FAULT PROTECTION IS NOW REQUIRED IN RESIDENTIAL |
| | OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH CIRCUITS THAT |
| | ARE NOT ALREADY REQUIRED TO BE PROTECTED BY GROUND |
| | FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER 120 VOLTS. |
| | NEC 210.12(B) |
| | |
| | 4) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC |
| | 406.11 THOSE OUTLETS IN WET LOCATIONS SHALL BE WEATHER |
| | RESISTANT NEC 406.8(B)(1) |
| | |
| | 5) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN ALL OF THESE |
| | LOCATIONS SHALL BE GFCI PROTECTED. |
| | |
| | 6) GFCI PROTECTED OUTLETS ARE REQUIRED FRONT AND BACK |
| | AT EACH RESIDENTIAL BUILDING AND AT THE LOCATION OF THE |
| | MECHANICAL EQUIPMENT. NEC 210-52 (E) (1), 210-63 |
| | |
| | 7) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST |
| | HAVE A RECEPTACLE OUTLET GFCI PROTECTED. NEC |
| | 210.52(E)(3). |
| | |
| | 8) ANY SPACE 2 FEET OR MORE IN WIDTH (INCLUDING SPACE |
| | MEASURED AROUND CORNERS) RECEPTACLES SHALL BE INSTALLED |
| | SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE |
| | FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FEET FROM A |
| | RECEPTACLE OUTLET. NEC 210.50(A)(1) SPACING. |
| | |
| | 9) IN KITCHENS, PANTRIES, BREAKFAST ROOMS, DINING |
| | ROOMS, AND SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE |
| | OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NEC 210.52(C)(1) THROUGH (C)(5). |
| | ADDITIONAL OUTLETS ARE REQUIRED FOR THE KITCHEN |
| | COUNTERTOPS. |
| | |
| | 10) LAUNDRY BRANCH CIRCUITS IN ADDITION TO THE NUMBER |
| | OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS |
| | SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY |
| | RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS |
| | CIRCUIT SHALL HAVE NO OTHER OUTLETS. |
| | |
| | 11) A WATER HEATER IS A MINIMUM PLAN REVIEW CRITERIA |
| | FOR RESIDENTIAL PLANS. PLEASE PROVIDE A MEANS FOR |
| | HEATING WATER AND INDICATE THE ELECTRICAL LOAD AND |
| | CIRCUITING ON THE PANEL DIRECTORY AND FLOOR PLAN. FBC |
| | 107.3.5 |
| | |
| | 12) IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED |
| | GARAGE OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS |
| | REQUIRED WITHIN TEN FEET OF EACH ROOM USED FOR |
| | SLEEPING. FBC R314, 315 |
| | |
| | 13) PROVIDE SMOKE DETECTORS PURSUANT TO FBC-R 314.3.1 |
| | AS REQUIRED FOR NEW DWELLINGS. FBC 107.3.5 PLEASE |
| | PROVIDE ONE ADDITIONAL SMOKE/CO DETECTOR AT THE SECOND |
| | FL LANDING. |
| | |
| | 14) PROVIDE THE ARC FAULT CALCULATION TO INDICATE THE |
| | AIC RATING ON SERVICE SWITCHGEAR. NEC 110.9 AND 110.10 |
| | |
| | 15) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED |
| | AT A READILY ACCESSIBLE LOCATION INSIDE OR OUTSIDE THE |
| | BUILDING NEAREST THE POINT OF SERVICE ENTRANCE IN |
| | ACCORDANCE WITH NEC 230.70. PLEASE INDICATE THE |
| | LOCATION OF THE ELECTRICAL SERVICE ENTRANCE AND |
| | DISCONNECTING MEANS. |
| | |
| | 16) THE GROUNDING ELECTRODE SYSTEM SHALL BE INSTALLED |
| | AS DESCRIBED IN SECTION III OF THE NEC 250 |
| | |
| | 17) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE |
| | MAIN SERVICE GROUND. NEC 250.94 |
| | |
| | 18) INCLUDE THE SIZE OF THE BRANCH CIRCUIT, WIRING |
| | METHOD AND LOCATION OF DISCONNECTS FOR MOTORS INCLUDING |
| | HVAC EQUIPMENT. FBC 107.1 |
| | |
| | 19) THE INSTALLATION OF ELECTRICAL WIRING FOR, AND |
| | EQUIPMENT IN AND ADJACENT TO, NATURAL OR ARTIFICIALLY |
| | MADE BODIES OF WATER NOT COVERED BY OTHER ARTICLES IN |
| | THIS CODE SHALL COMPLY WITH THE PROVISIONS OF THE NEC |
| | 682. |
| | |
| | NOTE: A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE |
| | SUBMITTED INCLUDING ALL DETAILED PLANS, SHOP DRAWINGS, |
| | EQUIPMENT SUBMITTALS, PRODUCT APPROVALS, ETC? IS |
| | REQUIRED FOR ALL OF THE FOLLOWING: FUTURE SWIMMING |
| | POOL, DOCK, GENERATOR, AUDIO, VIDEO, NETWORK, SECURITY, |
| | CCTV. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR AT [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |