Plan Review Details - Permit 14050320
Plan Review Stops For Permit 14050320
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-22 Cont ID  
Sent By albarran Date 2014-05-22 Time 18:30 Rev Time 0.00
Received By albarran Date 2014-05-22 Time 18:19 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-12 Cont ID  
Sent By albarran Date 2014-05-12 Time 17:53 Rev Time 0.00
Received By albarran Date 2014-05-12 Time 17:23 Sent To I
Notes
2014-05-12 17:59:51FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS:
  
 FROM THE SUBMITTED ELECTRICAL PLAN & RISER I CAN'T
 ASCERTAIN COMPLIANCE WITH NEC 230.2 LIMITING THE BLDG
 TO A SINGLE SERVICE.
  
 IF IT IS THE INTENTION OF THIS WORK TO CONSOLIDATE THE
 EXISTING SERVICE WITH THE NEW ONE, PLEASE INDICATE THIS
 ON THE DRAWINGS. IF IT IS NOT THE INTENTION, AS PER NEC
 230.2(D), THEN COMPLIANCE W/NEC 230.2(E) SHALL BE
 REQUIRED
  
 WHEN ADDRESSING THE ABOVE, COMPLETE NOTE #26 TO COMPLY
 WITH NEC 210.4, AND COMPLETE NOTE #33 TO COMPLY WITH
 NEC 406.8
  
 IF YOU HAVE ANY QUESTIONS ON THIS REVIEW, PLEASE
 CONTACT MIKE ALBARRAN (561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-22 Cont ID  
Sent By albarran Date 2014-05-22 Time 18:30 Rev Time 0.00
Received By albarran Date 2014-05-21 Time 17:24 Sent To PC
Notes
2014-05-22 18:31:07APPROVED REVIEW AND PROCESSED OUT.
2014-05-22 17:27:59RESUBMITTAL SENT TO MIKE ALBARRAN'S DESK FOR REVIEW .
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-12 Cont ID  
Sent By albarran Date 2014-05-12 Time 18:00 Rev Time 0.00
Received By albarran Date 2014-05-09 Time 12:08 Sent To PC
Notes
2014-05-12 18:07:41I CONTACTED MARK OF FRESHWATER & SON ELECTRIC TO GIVE
 HIM A STATUS UPDATE.
 SENT TO SMALL DENIED "F"
2014-05-09 12:08:58ROUTED TO ELECTRICAL