Plan Review Details - Permit 14050320
| Plan Review Stops For Permit 14050320 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-05-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-22 |
Time |
18:30 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-22 |
Time |
18:19 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-05-12 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-12 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-12 |
Time |
17:23 |
Sent To |
I |
|
| Notes |
| 2014-05-12 17:59:51 | FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS: | | | | | | FROM THE SUBMITTED ELECTRICAL PLAN & RISER I CAN'T | | | ASCERTAIN COMPLIANCE WITH NEC 230.2 LIMITING THE BLDG | | | TO A SINGLE SERVICE. | | | | | | IF IT IS THE INTENTION OF THIS WORK TO CONSOLIDATE THE | | | EXISTING SERVICE WITH THE NEW ONE, PLEASE INDICATE THIS | | | ON THE DRAWINGS. IF IT IS NOT THE INTENTION, AS PER NEC | | | 230.2(D), THEN COMPLIANCE W/NEC 230.2(E) SHALL BE | | | REQUIRED | | | | | | WHEN ADDRESSING THE ABOVE, COMPLETE NOTE #26 TO COMPLY | | | WITH NEC 210.4, AND COMPLETE NOTE #33 TO COMPLY WITH | | | NEC 406.8 | | | | | | IF YOU HAVE ANY QUESTIONS ON THIS REVIEW, PLEASE | | | CONTACT MIKE ALBARRAN (561) 805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-05-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-22 |
Time |
18:30 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-21 |
Time |
17:24 |
Sent To |
PC |
|
| Notes |
| 2014-05-22 18:31:07 | APPROVED REVIEW AND PROCESSED OUT. | | 2014-05-22 17:27:59 | RESUBMITTAL SENT TO MIKE ALBARRAN'S DESK FOR REVIEW . | | | JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-05-12 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-05-12 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-05-09 |
Time |
12:08 |
Sent To |
PC |
|
| Notes |
| 2014-05-12 18:07:41 | I CONTACTED MARK OF FRESHWATER & SON ELECTRIC TO GIVE | | | HIM A STATUS UPDATE. | | | SENT TO SMALL DENIED "F" | | 2014-05-09 12:08:58 | ROUTED TO ELECTRICAL |
|
|
|