Plan Review Details - Permit 14050295
Plan Review Stops For Permit 14050295
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-15 Cont ID  
Sent By skennedy Date 2014-05-15 Time 16:17 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-13 Cont ID  
Sent By rmcdouga Date 2014-05-13 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2014-05-13 Time 10:53 Sent To  
Notes
2014-05-13 11:27:082010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE SAM 3 90 SOUND UNDERLAYMENT.
  
 2) SUBMIT DOCUMENTATION THAT SHOWS THE UNDERLAYMENT
 COMPLIES WITH FBC 1207.2 FOR AIR BOURNE SOUND (STC OF
 NOT LESS THAN 50) AND FBC 1207.3 FOR STRUCTURE BOURNE
 SOUND ( IIC OF NOT LESS THAN 50).
  
 3) SUBMIT DOCUMENTATION THAT SHOWS THAT THE SURFACE
 BURNING TEST REPORT THAT WAS SUBMITTED IS FOR THE SAM 3
 90 SOUND CONTROL MEMBRANE AND NOT ONE OF THE OTHER
 PRODUCT PRODUCED BY NAC PRODUCTS INC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-13 Cont ID  
Sent By rmcdouga Date 2014-05-13 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2014-05-08 Time 12:05 Sent To  
Notes
2014-05-08 12:05:54BLDG <5000