| Plan Review Stops For Permit 14050273 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-30 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-30 |
Time |
06:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-05-18 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-18 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-18 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2014-05-18 09:23:08 | 1ST REVIEW: | | | | | | 1) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY | | | DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, GARAGE DOOR | | | SUBMITTALS. GARAGE DOOR IS MISSING, OTHERS OK. | | | | | | 2) FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE | | | SETBACKS AND BUILDING SEPARATION. THE SITE PLAN AND | | | SURVEY PROVIDED DO NOT MATCH. | | | | | | 3) FBC-110.7 SUPPLY A DRAINAGE DESIGN. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC | | | SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN | | | COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. | | | | | | 4) FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE | | | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION | | | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | I REASSESSED THE VALUE AT $533,244.84 USING THE | | | INTERNATIONAL CODE CONGRESS BUILDING VALUE DATED | | | PUBLISHED 02/14. | | | | | | NOTE: FLOOD ZONE REVIEW IS PENDING. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-05-30 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-30 |
Time |
07:47 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-05-27 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-05-27 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-27 |
Time |
16:52 |
Sent To |
B |
|
| Notes |
| 2014-05-27 16:04:22 | 2ND ELECTRICAL REVIEW DENIED. THE ELECTRICAL SYSTEM IS | | | STILL FOUND TO BE DEFICIENT IN THE FOLLOWING AREAS | | | BASED ON 2008 EDITION OF THE NEC AND THE 2010 FBC. SEE | | | COMMENTS BELOW: | | | | | | 1) GROUNDING ELECTRODE CONDUCTOR IS IMPROPERLY SIZED | | | 250.66, THE GROUNDING ELECTRODE CONDUCTOR FOR A 300AMP | | | SERVICE IS REQUIRED TO BE A #2CU MINIMUM. | | | | | | 2) AN INTERSYSTEM BOND STRIP IS REQUIRED PER 250.94 | | | | | | 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES | | | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) | | | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION | | | FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE | | | SHALL BE GFCI PROTECTED. INCLUDING THE GARAGE DOOR | | | OPENERS. | | | | | | 4) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT | | | ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. NEC 210.52 (A)(2). | | | THERE ARE SEVERAL AREAS THROUGHOUT THE HOME TO BE | | | ADDRESSED. THIS INCLUDES FIXED PANELS. "THE SPACE | | | OCCUPIED BY FIXED PANELS IN EXTERIOR WALLS, EXCLUDING | | | SLIDING PANELS" | | | | | | 7) IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED | | | GARAGE OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS | | | REQUIRED WITHIN TEN FEET OF EACH ROOM USED FOR | | | SLEEPING. FBC R314, 315 | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE POOL, AND | | | DOCK. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR AT [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-05-19 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-05-19 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-19 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2014-05-19 14:22:37 | ELECTRICAL REVIEW DENIED. THE ELECTRICAL SYSTEM IS | | | FOUND TO BE DEFICIENT IN THE FOLLOWING AREAS BASED ON | | | 2008 EDITION OF THE NEC AND THE 2010 FBC, FBC RES., FBC | | | ENERGY, SEE COMMENTS BELOW. | | | | | | 1) ELECTRICAL SERVICE RISER INDICATES A 300AMP | | | DISCONNECT SWITCH WITH A 2/0 FEEDER. THE MINIMUM SIZE | | | SERVICE ENTRANCE CONDUCTOR FOR A RESIDENTIAL SERVICE | | | ENTRANCE OR FEEDER IS A 250MCM CU. OR 350MCM AL. | | | | | | 2) THE DESIGN OF THE ELECTRICAL SERVICE RISER IS NOT IN | | | COMPLIANCE WITH NEC 310.15(B)(6), 240.21. PLEASE SHOW | | | OVER CURRENT PROTECTION AND APPROPRIATE FEEDER SIZE FOR | | | SUB-PANEL "B" | | | | | | 3) GROUNDING ELECTRODE CONDUCTOR APPEARS TO BE | | | IMPROPERLY SIZED FOR BONDING OF ALL SYSTEMS AND PROVIDE | | | BONDING OF ALL SYSTEMS AND BUILDING STEEL, AS | | | APPLICABLE 250.66, 250.104THE GROUNDING ELECTRODE | | | CONDUCTOR FOR A 300AMP SERVICE IS REQUIRED TO BE A #2CU | | | MINIMUM. | | | | | | 4) AN INTERSYSTEM BOND STRIP IS REQUIRED PER 250.94 | | | | | | 5) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES | | | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) | | | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION | | | FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE | | | SHALL BE GFCI PROTECTED. | | | | | | 6) LUMINAIRES IN CLOTHES CLOSETS. ARTICLE 410.16 (C)(3) | | | LOCATION. STATES IN PART , THE MINIMUM CLEARANCE | | | BETWEEN LUMINAIRES INSTALLED IN CLOTHES CLOSETS AND THE | | | NEAREST POINT OF A STORAGE SPACE SHALL BE AS FOLLOWS: | | | "150MM (6") FOR RECESSED INCANDESCENT OR LED LUMINAIRES | | | WITH A COMPLETELY ENCLOSED LIGHT SOURCE INSTALLED IN | | | THE WALL OR CEILING" OR (4) "150MM (6") FOR RECESSED | | | FLUORESCENT LUMINAIRES INSTALLED IN THE WALL OR | | | CEILING." PLEASE INDICATE COMPLIANCE WITH THIS SECTION | | | OF THE NEC WHERE INSTALLING RECESSED LIGHTING IN | | | CLOTHES CLOSETS | | | | | | 7) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT | | | ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. NEC 210.52 (A)(2). | | | THERE ARE SEVERAL AREAS THROUGHOUT THE HOME TO BE | | | ADDRESSED. | | | | | | 8) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED. AT | | | LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED LIGHT | | | FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 402.4.5, & | | | 404.1, | | | | | | 9) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC | | | 406.11 THOSE OUTLETS IN WET LOCATIONS SHALL BE WEATHER | | | RESISTANT NEC 406.8(B)(1) | | | | | | 10) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST | | | HAVE A RECEPTACLE OUTLET GFCI PROTECTED. NEC | | | 210.52(E)(3). | | | | | | 11) IN KITCHENS, PANTRIES, BREAKFAST ROOMS, DINING | | | ROOMS, AND SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE | | | OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN | | | ACCORDANCE WITH NEC 210.52(C)(1) THROUGH (C)(5). | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR AT [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-05-30 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-30 |
Time |
06:57 |
Sent To |
E |
|
| Notes |
| 2014-05-30 06:58:27 | TO DAH DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-30 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-23 |
Time |
11:02 |
Sent To |
Z |
|
| Notes |
| 2014-05-27 11:04:00 | PLEASE FORWARD TO DAVID HAYES DESK WHEN COMPLETE. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-05-19 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-05-19 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-07 |
Time |
07:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-30 |
Time |
06:37 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-30 |
Time |
06:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2014-05-18 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-18 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-18 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2014-05-18 08:26:02 | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. | | | AFTER APPROVAL, A SET OF THE PLANS ARE TO BE CHECKED | | | OUT AND TAKEN TO THE PBC IMPACT FEE OFFICE, STAMPED BY | | | THAT OFFICE, AND RETURNED WITH A RECEIPT PROVIDED. | | | CONTACT 561 233 5100. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-30 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-30 |
Time |
06:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-05-18 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-18 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-18 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2014-05-18 09:04:28 | 1ST REVIEW: | | | | | | 1) FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT THE | | | MASTER BEDROOM I DO NOT SEE A RAG OR JUMPER FOR THIS | | | ROOM ON THE PLAN. | | | | | | 2) FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION: PRVIDE | | | A SIZING CALCULATION THAT IS CONSISTENT WITH THE | | | INFORMATION ON THE PLAN. THE MANUAL J MODEL NUMBER FOR | | | SYSTEM 2 DOES NOT MATCH THAT SPECIFIED UPON THE PLAN. | | | PROVIDE THE SENSIBLE AND LATENT COOLING CAPACITY ON THE | | | EQUIPMENT SCHEDULE FOR EACH SYSTEM ON THE PLAN. | | | | | | 3) FBC-R M1305.1.3 APPLIANCES IN ATTICS. INDICATE ON | | | THE PLAN THE FOLLOWING, PARTICULARLY THE INTENT TO | | | PROVIDE SOLID DECKING: ATTICS CONTAINING APPLIANCES | | | SHALL BE PROVIDED WITH AN OPENING AND A CLEAR AND | | | UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO ALLOW REMOVAL | | | OF THE LARGEST APPLIANCE, BUT NOT LESS THAN 30 INCHES | | | (762 MM) HIGH AND 22 INCHES (559 MM) WIDE AND NOT MORE | | | THAN 6 FEET (1829 MM) LONG MEASURED ALONG THE | | | CENTERLINE OF THE PASSAGEWAY FROM THE OPENING TO THE | | | APPLIANCE. THE PASSAGEWAY SHALL HAVE CONTINUOUS SOLID | | | FLOORING IN ACCORDANCE WITH CHAPTER 5 NOT LESS THAN 24 | | | INCHES (610 MM) WIDE. A LEVEL SERVICE SPACE AT LEAST 30 | | | INCHES (762 MM) DEEP AND 30 INCHES (762 MM) WIDE SHALL | | | BE PRESENT ALONG ALL SIDES OF THE APPLIANCE WHERE | | | ACCESS IS REQUIRED. THE CLEAR ACCESS OPENING DIMENSIONS | | | SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES (508 MM BY | | | 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL OF THE | | | LARGEST APPLIANCE. | | | | | | 4) FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS. | | | A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE | | | REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN | | | ACCORDANCE WITH CHAPTER 34. | | | | | | 5) INDICATE UPON THE PLAN COMPLIANCE WITH #2 & #3 | | | BELOW: | | | FBC-R M1305.1.3.2 AIR-HANDLING UNITS AIR-HANDLING UNITS | | | SHALL BE ALLOWED IN ATTICS IF THE FOLLOWING CONDITIONS | | | ARE MET: | | | 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN | | | 6 FEET (1829 MM) OF AN ATTIC ACCESS. | | | 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE | | | UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING | | | PROPERLY. | | | 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO | | | REPLACE THE AIR HANDLER | | | 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL | | | INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS | | | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL | | | CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST | | | PARAGRAPH IN BOLD: | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-30 |
Time |
06:39 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-30 |
Time |
06:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-05-18 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-18 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-18 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2014-05-18 08:37:26 | 1ST REVIEW: | | | | | | 1) THE PLUMBING RISER DOES NOT MATCH THE SECOND FLOOR | | | PLAN. PLAN SHOWS A BATHROOM GROUP THAT IS NOT REFLECTED | | | IN THE RISER. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2014-05-30 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-18 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-18 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2014-05-18 10:11:11 | ROOFING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-05-27 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-05-30 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-05-27 |
Time |
15:11 |
Sent To |
E |
|
| Notes |
| 2014-05-27 15:11:28 | 5/27/14 ZONING PROVISO: | | | | | | SUBMIT SEPARATE PLAN FOR THE DRIVEWAY AND LANDSCAPING. | | | THE APPROACH CAN NOT BE 25',CONTACT MANNY GONZALES AT | | | 561-494-1050 TO GET THE ALLOWABLE ON DRIVEWAYS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-05-19 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-05-19 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-05-19 |
Time |
08:29 |
Sent To |
E |
|
| Notes |
| 2014-05-19 08:29:49 | 5/19/14 ZONING FAILED. | | | | | | 1. SURVERY AND PLOT PLAN MUST MATCH, PLEASE SUBMIT 2- | | | SURVERYS AND 2- PLOT PLANS THAT MATCH. | | 2014-05-12 17:25:42 | 5/12/14 |
|
|