Plan Review Details - Permit 14050264
Plan Review Stops For Permit 14050264
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-23 Cont ID  
Sent By rmcdouga Date 2014-07-23 Time 15:23 Rev Time 0.00
Received By rmcdouga Date 2014-07-23 Time 07:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-06 Cont ID  
Sent By rmcdouga Date 2014-06-06 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2014-06-05 Time 17:38 Sent To Z
Notes
2014-06-06 07:50:462010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE REQUIRED TRUSS DESIGN LOADS ON THE
 PLANS. FBC R802.1.6.1
  
 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 THREE ROOF ZONES ON THE PLANS. FBC R301.2.1.1 AND
 FIGURE R301.2(7)
  
 3) SPECIFY THE ROOF SHEATHING NAILING REQUIREMENTS ON
 THE PLANS. FBC R803.2.3.1
  
 4) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF
 VENTILATION.
  
 5) SHOW COMPLIANCE WITH FBC R807.1 FOR ATTIC ACCESS TO
 THE ADDITION.
  
 6) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE
 REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS, THE AWNING WINDOW (
 BATHROOM ) AND THE METAL ROOF. DCA RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-06 Cont ID  
Sent By rmcdouga Date 2014-06-06 Time 06:57 Rev Time 0.00
Received By rmcdouga Date 2014-06-05 Time 18:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-23 Cont ID  
Sent By rmcdouga Date 2014-07-23 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2014-07-16 Time 18:55 Sent To  
Notes
2014-07-16 18:55:50SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-06 Cont ID  
Sent By rmcdouga Date 2014-06-06 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2014-05-07 Time 07:58 Sent To  
Notes
2014-05-08 07:58:21R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-09-26 Cont ID  
Sent By rmcdouga Date 2014-09-26 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2014-09-26 Time 10:03 Sent To  
Notes
2014-09-26 10:13:51MU 2014-21169, NO IMPACT FEES WERE DUE. THE
 CONTRACTOR'S SET WITHOUT THE ENGINEER'S SEAL WAS
 STAMPED. A COPY OF THE STAMP WAS MADE AND PLACE WITH
 THE CONSTRUCTION DOCUMENTS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-06-05 Cont ID  
Sent By rmcdouga Date 2014-06-05 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2014-06-05 Time 17:38 Sent To  
Notes
2014-06-05 17:43:41IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
 PHONE 561-233-5525

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-06-05 Cont ID  
Sent By rmcdouga Date 2014-06-05 Time 18:02 Rev Time 0.00
Received By rmcdouga Date 2014-06-05 Time 18:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-05 Cont ID  
Sent By rmcdouga Date 2014-06-05 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2014-06-05 Time 17:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2014-12-24 Cont ID  
Sent By rmcdouga Date 2014-12-24 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 10:47 Sent To  
Notes
2014-12-24 10:48:51ENGLERT METAL ROOF , FL 11727.1 R6

Review Stop Z ZONING
Rev No 1 Status P Date 2014-06-06 Cont ID  
Sent By sgraham Date 2014-06-06 Time 08:55 Rev Time 0.00
Received By sgraham Date 2014-06-06 Time 08:55 Sent To B
Notes
***NONE***