Plan Review Details - Permit 14050254
Plan Review Stops For Permit 14050254
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-07-30 Cont ID  
Sent By jwitmer Date 2014-07-30 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2014-07-30 Time 05:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 15:39 Sent To  
Notes
2014-07-01 15:57:30BUILDING PLAN REVIEW
 PERMIT:14050254
 ADD: 109 S OLIVE AVE
 CONT: TRI-R CONSTRUCTION
 TEL: (772)336-6444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 01 /2014
 ACTION: DENIED
  
 NOTE: FAILED!!!!! DID NOT HAPPEN, CONTRACTOR IS TO
 INSERT NEW SHEETS INTO PLANS & REMOVE OLD SHEETS BEFORE
 RESUBMITTAL!!!!!!!!!!! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT.
  
 1) 2ND REQUEST, THE LIFE SAFETY SHEET A-0.00
 1A) CODE ANALYSIS INDICATES THIS BUILDING TO A TYPE V -
 ASSUMED, PLEASE PROVIDE THE HEIGHT OF THE BUILDING,
 THIS SPACE BEING TWO FLOORS AND HOW MANY ADDITIONAL
 FLOORS ONE OR TWO. PLEASE REVIEW TABLE 503, IT APPEARS
 IF THIS IS A 3 STORY BUILDING EITHER A III-B OR V-A OR
 IF A 4 STORY A III-A. TAKING INTO ACCOUNT A STORY
 INCREASE FOR FIRE SPRINKLERS. THE DESIGNER OF RECORD
 WILL HAVE TO DECIDE IF THIS BUILDING WAS DESIGNED TO A
 VA OR VB. NOT JUST A V UNDER THE 2001 FBC THERE WAS A
 TYPE V WHEN THE 2004 FBC AND SINCE THERE WAS NO LONGER
 ABUILDING TYPE VI, THE TYPE V IS CURRENTLY CONSIDERED A
 IIIA, SEE THE 2007 CODE COMMENTARY FIGURE 600 FOR
 CONSTRUCTION TYPE COMPARISONS.
  
 1B) SHEET A101 NOW HAS A NEW 1 HOUR CHASE, IT APPEARS
 TO BE IN THE STAIRWELL TO THE OTHER TENANTS. PLEASE
 PROVIDE ON THE PLANS THE UL LISTING U415 SYSTEM A SINCE
 THE INSPECTORS WILL NEED THE COMPONENTS OF THE ASSEMBLY
 TO BE ABLE TO ACCOMPLISH THEIR INSPECTIONS. FBC-B 708.4
 AND 708.5 CONTINUITY. 708.8 PENETRATIONS.
  
 1C) SHEET A-1.01 DOES HAVE A WALL TAG S2 WALL TYPE
 IDENTIFYING FIRE RATED WALLS. NONE OF THE TENANT
 SEPERATION WALLS ARE IDENTIFIED WITH THIS WALL TAG. FBC
 709.1.6.
  
 1D )2ND REQUEST. ONLY NEW SHEET IS P3 NOT FOUND ON THIS
 SHEET, CONTRACTOR FAILED TO COLATE PLANS INTO ONE SET
 OF PLANS. THE TENANT SEPARATION WALL WITHIN THE LADIES
 RESTROOM WILL HAVE VENTING THAT WILL PETRUDE OUT OF THE
 FIRE RATED WALL, WHAT TYPE OF FIRE STOPPING DESIGN IS
 TO BE SUBMITTED FOR THROUGH PENETRATIONS, 2010 FBC-B
 713.4.1.1.
  
 1E) COMPLIED.
  
 1F) SEMI COMPLIED MISSING THE NEW A4.01 AS INDICATED IN
 RESPONSE.
 2) SHEET A-1.01:
 2A-J)COMPLIED.
  
 3) 2ND REQUEST, SHEET M-4 INDICATES THE USE OF WALL
 LOUVERS AND PRE-MANUFACTURED A/C STANDS, PLEAS PROVIDE
 COMPLIANCE WITH : FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2ND REQUEST, 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2ND REQUEST, PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 PLEASE PROVIDE THE WIND DESIGN CRITERIA, PRESSURES FOR
 THE WALL LOUVER & ROOFTOP A/C STAND.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 6) SHEET M-1 NOTE # 3 INDICATES TO RUN THE REFRIGARANT
 LINES THROUGH CHASE TO ROOF. THERE IS NO DETAILS WITHIN
 THE PLANS INDICATING HOW THIS CHASE WILL BE BUILT,AND
 ACHIEVE FIRE RATINGS IN COMPLIANCE WITH 2010 FBC-B
 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
  
 6A) COMPLIED SEE SHEET M-5.
 PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR,
 FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A
 ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS
 713.4.1.1 THROUGH 713.4.1.4.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 15:58 Rev Time 0.00
Received By jwitmer Date 2014-05-23 Time 07:30 Sent To  
Notes
2014-05-23 13:28:08BUILDING PLAN REVIEW
 PERMIT:14050254
 ADD: 109 S OLIVE AVE
 CONT: TRI-R CONSTRUCTION
 TEL: (772)336-6444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY MAY 23/2014
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET A-0.00
 1A) CODE ANALYSIS INDICATES THIS BUILDING TO A TYPE V -
 ASSUMED, PLEASE PROVIDE THE HEIGHT OF THE BUILDING,
 THIS SPACE BEING TWO FLOORS AND HOW MANY ADDITIONAL
 FLOORS ONE OR TWO. PLEASE REVIEW TABLE 503, IT APPEARS
 IF THIS IS A 3 STORY BUILDING EITHER A III-B OR V-A OR
 IF A 4 STORY A III-A. TAKING INTO ACCOUNT A STORY
 INCREASE FOR FIRE SPRINKLERS.
  
 1B) SHEET A101 NOW HAS A NEW 1 HOUR CHASE, IT APPEARS
 TO BE IN THE STAIRWELL TO THE OTHER TENANTS. PLEASE
 PROVIDE ON THE PLANS THE UL LISTING U415 SYSTEM A SINCE
 THE INSPECTORS WILL NEED THE COMPONENTS OF THE ASSEMBLY
 TO BE ABLE TO ACCOMPLISH THEIR INSPECTIONS. FBC-B 708.4
 AND 708.5 CONTINUITY. 708.8 PENETRATIONS.
  
 1C) SHEET A-1.01 DOES HAVE A WALL TAG S2 WALL TYPE
 IDENTIFYING FIRE RATED WALLS. NONE OF THE TENANT
 SEPERATION WALLS ARE IDENTIFIED WITH THIS WALL TAG. FBC
 709.1.6.
  
 1D )2ND REQUEST. ONLY NEW SHEET IS P3 NOT FOUND ON THIS
 SHEET, CONTRACTOR FAILED TO COLATE PLANS INTO ONE SET
 OF PLANS. THE TENANT SEPARATION WALL WITHIN THE LADIES
 RESTROOM WILL HAVE VENTING THAT WILL PETRUDE OUT OF THE
 FIRE RATED WALL, WHAT TYPE OF FIRE STOPPING DESIGN IS
 TO BE SUBMITTED FOR THROUGH PENETRATIONS, 2010 FBC-B
 713.4.1.1.
  
 1E) COMPLIED.
  
 1F) SEMI COMPLIED MISSING THE NEW A4.01 AS INDICATED IN
 RESPONSE.
 2) SHEET A-1.01:
 2A-J)COMPLIED.
  
 3) 2ND REQUEST, SHEET M-4 INDICATES THE USE OF WALL
 LOUVERS AND PRE-MANUFACTURED A/C STANDS, PLEAS PROVIDE
 COMPLIANCE WITH : FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2ND REQUEST, 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2ND REQUEST, PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 PLEASE PROVIDE THE WIND DESIGN CRITERIA, PRESSURES FOR
 THE WALL LOUVER & ROOFTOP A/C STAND.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 6) SHEET M-1 NOTE # 3 INDICATES TO RUN THE REFRIGARANT
 LINES THROUGH CHASE TO ROOF. THERE IS NO DETAILS WITHIN
 THE PLANS INDICATING HOW THIS CHASE WILL BE BUILT,AND
 ACHIEVE FIRE RATINGS IN COMPLIANCE WITH 2010 FBC-B
 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
  
 6A) COMPLIED SEE SHEET M-5.
 PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR,
 FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A
 ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS
 713.4.1.1 THROUGH 713.4.1.4.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-07-28 Cont ID  
Sent By dhayes Date 2014-07-26 Time 07:37 Rev Time 0.00
Received By dhayes Date 2014-07-26 Time 13:11 Sent To  
Notes
2014-07-26 14:06:55DATE: 7/26/2014
 PROJECT: SHOUTE KARAOKE
 PERMIT#: 14050254
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 4TH ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE
 SUBMITTED ACCOMPANIED BY SHOP DRAWINGS, EQUIPMENT
 SUBMITTALS, PRODUCT APPROVALS FOR ALL OF THE FOLLOWING
 AS APPLICABLE:
 GENERATOR, SIGNAGE, NETWORK, DATA/COM, FIRE ALARM,
 SECURITY, CCTV, AND AUDIO/VIDEO.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-07-16 Cont ID  
Sent By dhayes Date 2014-07-16 Time 11:00 Rev Time 0.00
Received By dhayes Date 2014-07-15 Time 14:11 Sent To  
Notes
2014-07-16 11:00:23DATE: 7/14/2014
 PROJECT: SHOUTE KARAOKE
 PERMIT#: 14050254
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE CIRCUITRY WITH MEANS OF DISCONNECT ON THE
 FLOOR PLAN AND ON A PANELS SCHEDULE FOR EF-1, AND THE
 MOTORIZED DAMPERS FOR MECHANICAL SYSTEMS.
 A DISCONNECTING MEANS FOR THE MOTOR SHALL BE LOCATED IN
 SIGHT FROM THE MOTOR LOCATION AND THE DRIVEN MACHINERY
 LOCATION. 430.102(B)(1), .FBC 107.2.1.3, NEC 440.11
  
 2) PROVIIDE MANUFACTURERS'S DATA SHEET FOR ELEVATOR
 LIFT TO INDICATE CODE COMPLIANCE WITH NEC110.3, 110.58,
 430.102(B)(1), 620, FBC 107.2.1.3,
  
 3) PROVIDE MANUFACTURERS'S DATA SHEET FOR LED RIBBON
 LIGHTING AND ASSOCIATED REMOTE TRANSFORMERS. NEC110.3,
 110.58, 411
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) FIRE ALARM SYSTEM NOTES SHALL INDICATE COMPLIANCE
 WITH NFPA 72 WITH REGARDS TO: (A) SMOKE DETECTOR
 PLACEMENT NEAR THE ELEVATOR LOBBY AND ELEVATOR RECAL.
 (B) AUXILIARY AUDIO SYSTEMS SHALL BE AUTOMATICALLY
 MUTED BY THE FIRE ALARM CONTROL PANEL IN THE EVENT OF
 AN ALARM CONDITION.
  
 6) PLEASE INDICATE COMPLIANCE WITH THE FBC - ENERGY FOR
 INTERIOR AND EXTERIOR LIGHTING CONTROL. SEE THE
 FOLLOWING CODE REFERENCE:
  
 ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY)
 SECTION 505
 505.2.2 AUTOMATIC LIGHTING SHUTOFF.
 BUILDINGS LARGER THAN 5,000 SQUARE FEET (465 M2) SHALL
 BE EQUIPPED WITH AN AUTOMATIC CONTROL DEVICE TO SHUT
 OFF LIGHTING IN THOSE AREAS. THIS AUTOMATIC CONTROL
 DEVICE SHALL FUNCTION ON EITHER:
 1. A SCHEDULED BASIS, USING TIME-OF-DAY, WITH AN
 INDEPENDENT PROGRAM SCHEDULE THAT CONTROLS THE INTERIOR
 LIGHTING IN AREAS THAT DO NOT EXCEED 25,000 SQUARE FEET
 (2323 M2) AND ARE NOT MORE THAN ONE FLOOR; OR
 2. AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF
 WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE; OR
 3. A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT
 INDICATES THE AREA IS UNOCCUPIED.
  
 505.2.2.1 OCCUPANT OVERRIDE.
 WHERE AN AUTOMATIC TIME SWITCH CONTROL DEVICE IS
 INSTALLED TO COMPLY WITH SECTION 505.2.2, ITEM 1, IT
 SHALL INCORPORATE AN OVERRIDE SWITCHING DEVICE THAT:
 1. IS READILY ACCESSIBLE.
 2. IS LOCATED SO THAT A PERSON USING THE DEVICE CAN SEE
 THE LIGHTS OR THE AREA CONTROLLED BY THAT SWITCH, OR SO
 THAT THE AREA BEING LIT IS ANNUNCIATED.
 3. IS MANUALLY OPERATED BY AN OCCUPANT OR AUTOMATICALLY
 BY SENSING AN OCCUPANT.
 4.MEETS THE REQUIREMENTS OF SECTION 505.2.1.2.
  
 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS.
  
 A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE
 SUBMITTED ACCOMPANIED BY SHOP DRAWINGS, EQUIPMENT
 SUBMITTALS, PRODUCT APPROVALS FOR ALL OF THE FOLLOWING:
 NETWORK, DATA/COM, FIRE ALARM, SECURITY, CCTV, AND
 AUDIO/ VIDEO WORK.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WPCONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBMI
 TTAL_FORM_04132010.PDF.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-06-19 Cont ID  
Sent By albarran Date 2014-06-19 Time 16:24 Rev Time 0.00
Received By albarran Date 2014-06-19 Time 11:38 Sent To  
Notes
2014-06-19 16:52:19THESE PLANS FAILED THE SECOND ELECTRICAL REVIEW AS
 INDICATED BELOW:
 A) PAGE A-0.00
 1. UNDER THE BOX "APPLICABLE CODES" REFERENCE TO THE
 NON-EXISTENT 2010 NEC IS BEING MADE. CORRECT THAT TO
 THE CURRENTLY ADOPTED CODE: NEC 2008
 2. THERE IS NO WALL SCHEDULE OR LEGEND TO DESCRIBE THE
 DIFFERENT TYPES OF WALLS DRAWN.
 B) PAGE A-1.01
 1. DESCRIBE THE SHADED AREA BETWEEN STORAGE ROOM 010
 AND ROOM 006. IS THAT A CHASE, A VOID OR A SOLID
 COLUMN?
 C) PAGE A-2.01
 1. WHAT IS SUPPOSED TO BE AN OPEN AREA IN THE REFLECTED
 CEILING PLAN SHOW LIGHTING FIXTURES (D). THEY SHOULD BE
 ON THE SECOND FLOOR CEILING INSTEAD.
 D) PAGE E-2.1
 1. THE LOCATION OF THE EXISTING PANEL "B" IS NOT
 CLEARLY INDICATED. IT APPEARS TO BE INSIDE THE AREA IN
 WHICH I INQUIRED ABOVE. IF IS IS ON THE OTHER SIDE OF
 THE WALL BEHIND THE DOOR, THERE DOES NOT APPEAR TO BE
 ENOUGH LIGHTING THERE..
 2. WHAT HAPPENED TO THE FACP FROM STAIRWELL 011 AS
 SHOWN ON THE PREVIOUS DRAWING?
 E) PAGE E-4.1
 1. PANEL "B" CKT 14 SHALL BE MARKED IN RED AND BE
 MECHANICALLY PROTECTED.
 2. CARE SHOULD BE TAKEN ON HOW THE TRANSITION TO
 ALUMINUM CONDUIT IS MADE TO AVOID GALVANIC REACTION.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME
 AT (561) 805-6718 OR EMAIL: [email protected], OR
 DAVID HAYES AT: [email protected], OR (561) 805-6717.
 THANK YOU.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-22 Cont ID  
Sent By albarran Date 2014-05-22 Time 17:20 Rev Time 0.00
Received By albarran Date 2014-05-22 Time 15:30 Sent To  
Notes
2014-05-22 17:19:42FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS:
  
 1. NEC 110.26(D) REQUIRES THAT THEREE BE PROPER
 ILLUMINATION IN THE AREA ABOUT THE ELECTRICAL PANELS,
 THIS BEING BOTH PANEL "B" AND THE FACP
 2. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET BY EACH
 ENTRY DOOR.
 3. MISSING EMERGENCY LIGHTING IN THE BATHROOMS AS PER
 FBC-B1006.2.2
 4. STAIR 013 IS MISSING THE EMERGENCY LIGHT ON THE
 FIRST FLR.
 5. ELECTRIC ROOM IS MISSING AN EMERGENCY LIGHT
 6. AS PER THE SUBMITTED PLANS, THER IS NOT SUFFICIENT
 LIGHTING IN THE STAIRWAYS
 7. THOUGH A SEPARATE PLAN & SET OF SHOP DRAWINGS IS
 REQUIRED FOR THE FIRE ALARM, THE SUBMITTED PLANS SHOW
 THE FACP IN THE 011 STAIRWELL, THEREFORE A DEDICATED 20
 AMP CIRCUIT FOR THE FIRE ALARM SHALL BE PROVIDED.
 8. VERIFY THE FEEDER FOR CU1; TAKING INTO ACCOUNT ANY
 APPLICABLE VOLTAGE DROP AND EXPOSURE DERATIONS.
 9 IF PANEL RP1` IS A SINGLE PHASE 120/240, WHY DOES THE
 FEEDER SHOW FOUR 4/0 CONDUCTORS PLUS THE GRD.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-19 Cont ID  
Sent By pleduc Date 2014-05-19 Time   Rev Time 0.00
Received By pleduc Date 2014-05-19 Time 12:08 Sent To  
Notes
2014-05-19 12:27:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 17:20 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 17:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 16:01 Rev Time 0.00
Received By jwitmer Date 2014-05-23 Time 15:59 Sent To  
Notes
2014-05-23 16:01:35FUEL GAS PLAN REVIEW
 PERMIT:14050254
 ADD: 109 S OLIVE AVE
 CONT: TRI-R CONSTRUCTION
 TEL: (772)336-6444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY MAY 23/2014
 ACTION: DENIED
  
 INFORMATION SHALL BE SHOWN ON ALL GAS DRAWINGS
 SUBMITTED FOR PERMITTING IN THE CITY OF WEST PALM
 BEACH:
  
 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-30 Cont ID  
Sent By jwitmer Date 2014-07-30 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2014-07-24 Time 07:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-30 Cont ID  
Sent By jwitmer Date 2014-07-24 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2014-06-13 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-27 Cont ID  
Sent By hmoser Date 2014-05-27 Time 15:03 Rev Time 0.00
Received By hmoser Date 2014-05-07 Time 10:02 Sent To  
Notes
2014-05-08 10:02:42B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 15:58 Rev Time 0.00
Received By jwitmer Date 2014-05-23 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-07-28 Cont ID  
Sent By jsaez Date 2014-07-28 Time 09:15 Rev Time 0.00
Received By jsaez Date 2014-07-28 Time 09:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-05-27 Cont ID  
Sent By hmoser Date 2014-05-27 Time 15:03 Rev Time 0.00
Received By hmoser Date 2014-05-27 Time 13:29 Sent To  
Notes
2014-05-27 15:03:03PLAN DENIED
 1) PROVIDE A ENGINEER DETAIL ON THE A/C STAND OR CURB
 TIE DOWN TO ROOF PER SECTION 301.12 WIND RESISTANCE.
 2010 FBC (M) (PROVIDE THE TYPE AND SIZE OF SCREW OR
 ANCHOR USED)
 2) REFER TO SECTION 304.11 GUARDS.2010 FBC (M)
 3) REFER TO SECTION 401.3 ENERGY PERFORMANCE
 CARD 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-07-30 Cont ID  
Sent By jwitmer Date 2014-07-30 Time 06:46 Rev Time 0.00
Received By jwitmer Date 2014-07-30 Time 06:00 Sent To  
Notes
2014-07-30 06:46:55PLUMBING PLAN REVIEW
 PERMIT: 14050254
 ADD: 109 N OLIVE AVE
 CONT: TRI-R CONSTRUCTION
 TEL: (772)336-6444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. JULY 30/ 2014
  
 ACTION: PLUMBING PROVISO
  
 THE PLANS (P-3) INDICATES A NEW GREASE INTERCEPTOR.
 THIS INTERCEPTOR IS TO BE PERMITTED UNDER A SEPARATE.
 THE NEW GREASE INTERCEPTOR IS TO BE SIZED USING UNDER
 THE 2010 FBC-PLUMBING CODE SECTION 1003.3.4 TOTAL FLOW
 RATE WITH RATE OF FLOW CONTROL (1003.3.4.2) OR CONCRETE
 VAULT TYPE INTERCEPTORS (TABLE 1003.5.1).
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED
 DURING INSPECTIONS THE REQUIRED MAINTENANCE & PUMP-OUT
 SCHEDULE WILL BE INCREASED TO KEEP IN COMPLIANCE WITH
 THE CITY'S MUNICIPAL CODE OF ORDINANCES.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 17:40 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2014-07-01 17:27:03PLUMBING PLAN REVIEW
 PERMIT:14050254
 ADD: 109 S OLIVE AVE
 CONT: TRI-R CONSTRUCTION
 TEL: (772)336-6444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 01/2014
 ACTION: PLUMBING PROVISO:
  
  
 1) SHEET P-1 NOTE # 3 INDICATES THE REUSE OF THE
 EXISTING GREASE INTERCEPTOR. PLEASE CONTACT WEST PALM
 BEACH FOG (FATS, OILS & GREASE) INSPECTORS TO VERIFY
 THE EXISITNG INTERCEPTOR SIZE AS WELL AS CONDITION TO
 SEE IF THE EXISITNG INTERCEPTOR CAN BE REUSED. THE
 CONCRETE TYPE VAULT INTERCEPTORS ARE TO BE LOCATED ON
 THE EXTERIOR OF THE BUILDING.
 CONTACT INFO: JOCELYN BROWN 822-2170 PUBLIC UTILITIES
 DEPARTMENT.
  
 2) IF THE EXISITNG GREASE INTERCEPTOR CAN BE REUSED
 PLEASE PROVIDE THE CALCULATIONS TO VERIFY THE GREASE
 INTERCEPTOR IS SIZED PROPERLY. FOR THE HYDROCEMICAL
 TYPE OF GREASE INTERCEPTORS THERE ARE VARIOUS METHODS
 FOR SIZING. FOR THE CONCRETE TYPE VAULT INTERCEPTORS
 SEE SIZING TABLE 1003.5.1 2010 FBC-P SIZING FORMULA FOR
 RESTAURANTS.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 18:31 Rev Time 0.00
Received By jwitmer Date 2014-05-23 Time 15:58 Sent To  
Notes
2014-05-23 16:13:32PLUMBING PLAN REVIEW
 PERMIT:14050254
 ADD: 109 S OLIVE AVE
 CONT: TRI-R CONSTRUCTION
 TEL: (772)336-6444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY MAY 23/2014
 ACTION: DENIED
  
 1) 2010 FBC-P ) 315.1 REQUIREMENTS. PUBLIC FOOD SERVICE
 ESTABLISHMENTS AND FOOD ESTABLISHMENTS, AS DEFINED IN
 CHAPTER 381 FLORIDA STATUTES, CHAPTER 500 FLORIDA
 STATUTES AND CHAPTER 509 FLORIDA STATUTES, SHALL COMPLY
 WITH THE APPLICABLE CODE REQUIREMENTS FOUND IN THE
 FLORIDA BUILDING CODE, BUILDING, CHAPTER 4, SPECIAL
 DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY.
 PLEASE SEE DBPR WEBSITE FOR ADDITIONAL INFO:
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/
 PLANREVIEWINDEX.HTML
  
 2) SHEET A-0.00 & A-1.00 : THE UPCOMING COMMENT WILL OR
 WILL NOT BE RELEVENT DEPENDING ON HOW THIS PROJECT IS
 LOOKED AT. UNDER THE HEADING OF RESTAURANT THERE ARE
 MORE THAN ADEQUITE FIXTURES, THE 2010 FBC-PLUMBING CODE
 SECTION 403.5 DOES LOOK AT REQUIRED FIXTURES NOT IS
 PROVIDED, UNDER THE HEADING OF RESTARAUNT THE FIXTURE
 COUNT IS ABOVE THE CODE REQUIREMENTS.
  
 THE PROBLEM WE ARE HAVING IS UNDER A RESTAURANT YOU
 HAVE A COMMERCIAL KITCHEN FOR FIXING MEALS, THERE IS NO
 EQUIPMENT FOR THE HEATING AND PREPARING OF FOOD. THE
 SECOND ISSUE WITH THE CLASSIFICATION OF A RESTAURANT
 ,THERE IS NO TABLES AND CHAIRS THAT WOULD BE ASSOCIATED
 WITH A RESTAURANT. WE DO NOT SEE ANY TABLE AND CHAIRS
 ON THE LIFE SAFETY PLANS FOR FLOOR PLANS FOR THE FIRST
 OR SECOND FLOOR.
  
 IF THIS PROJECT IS REVIEWED UNDER THE NIGHTCLUB USAGE,
 NOT REQUIRING A FULL BLOWN KITCHEN, NOT REQUIRING TABLE
 AND CHAIRS THE REQUIRED 40 SQ FT/ OCC GOES TO 75 SQ FT/
 OCC ALMOST DOUBLING THE REQUIRED FIXTURE COUNT, THEN
 WITH THE COMBINED REQUIRED WATER CLOSET COUNT FOR MENS
 & LADIES RESTROOMS A SEPERATE UNISEX RESTROOM WILL BE
 REQUIRED. OUR PROBLEM IS THE PLANS APPEAR TO BE A
 NIGHTCLUB SETTING AND NOT THE RESTAURANT DECLARED BY
 THE DESIGN PROFESSIONAL.
  
 2A)IF CONSIDERED A NIGHTCLUB: CODE ANALYSIS UNDER THE
 HEADING USE & OCCUPANCY INDICATES THIS TO BE AN A2
 OCCUPANCY / RESTARAUNT. THE PLUMBING FIXTURE COUNT ALSO
 REFLECTS
 THE REQUIRED FIXTURES FOR A RESTARAUNT USE. THE
 REQUIRED WATER CLOSET COUNT OF 2 REQUIRED WATER CLOSETS
 ARE PROVIDED WITH A 3RD ACCESSIBLE RESTROOM FOR EACH
 THE MENS AND WOMENS RESTROOMS. THE ISSUE IS THERE IS NO
 UNISEX RESTROOM AS REQUIRED BY 2010 FL ACC CODE 403.5.
  
 2010 FL ACC CODE SECTION :2010 FL ACC CODE 403.1.2
 FAMILY OR ASSISTED-USE TOILET AND BATH FIXTURES.
 FIXTURES LOCATED WITHIN FAMILY OR ASSISTED-USE TOILET
 AND BATHING ROOMS REQUIRED BY THE FLORIDA BUILDING
 CODE, ACCESSIBILITY ARE PERMITTED TO BE INCLUDED IN THE
 NUMBER OF REQUIRED FIXTURES FOR EITHER THE MALE OR
 FEMALE OCCUPANTS IN ASSEMBLY AND MERCANTILE
 OCCUPANCIES. THIS IS A GENERAL CODE ARTICLE THAT ALLOWS
 THE FAMILY OR ASSITED- USE RESTROOMS TO BE COUNTED IN
 EITHER OR MALE OR FEMALE FIXTURE COUNT.
  
 SECTION 403.5 IS A SPECIFIC CODE ARTILE THAT DEALS ONLY
 WITH ASSEMBLY & MERCANTILE OCCUPANCIES. 403.5 UNISEX
 TOILET AND BATHING ROOMS. IN ASSEMBLY AND MERCANTILE
 OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET ROOM SHALL BE
 PROVIDED WHERE AN AGGREGATE OF SIX OR MORE MALE AND
 FEMALE WATER CLOSETS IS REQUIRED, AGAIN UNDER A
 NIGHTCLUB SETTING.
 WITH THE SINGLE MENS ACCESIBLE RESTROOM THE PLANS ARE
 MISSING THE REQUIRED UNISEX RESTROOM REQUIRED BY THE
 2010 FL ACCESSIBILITY CODE UNDER THE NIGHTCLUB SETTING.
  
 3) SHEET P-1 NOTE # 3 INDICATES THE REUSE OF THE
 EXISTING GREASE INTERCEPTOR. PLEASE CONTACT WEST PALM
 BEACH FOG (FATS, OILS & GREASE) INSPECTORS TO VERIFY
 THE EXISITNG INTERCEPTOR SIZE AS WELL AS CONDITION TO
 SEE IF THE EXISITNG INTERCEPTOR CAN BE REUSED. THE
 CONCRETE TYPE VAULT INTERCEPTORS ARE TO BE LOCATED ON
 THE EXTERIOR OF THE BUILDING.
 CONTACT INFO: JOCELYN BROWN 822-2170 PUBLIC UTILITIES
 DEPARTMENT.
  
 4) IF THE EXISITNG GREASE INTERCEPTOR CAN BE REUSED
 PLEASE PROVIDE THE CALCULATIONS TO VERIFY THE GREASE
 INTERCEPTOR IS SIZED PROPERLY. FOR THE HYDROCEMICAL
 TYPE OF GREASE INTERCEPTORS THERE ARE VARIOUS METHODS
 FOR SIZING. FOR THE CONCRETE TYPE VAULT INTERCEPTORS
 SEE SIZING TABLE 1003.5.1 2010 FBC-P SIZING FORMULA FOR
 RESTAURANTS.
  
 5) SHEET P-3.0 IN THE LADIES RESTROOM THE WATER CLOSETS
 NEED TO BE EITHER INDIVIDUALLY VENTED OR A CIRCUIT VENT
 AS DRAWN IT APPEARS TO BE A VET VENT SYSTEM,
 WET VENT SYSSTEMS ARE TO BE USED ON 1 & 2 FAMILY
 RESIDENCE.
 INFORMAL INTERPRETATION BOAF & FL DEPART COMMUNITY
 AFFAIRS
 DATE: MON APR 13 2009
 REPORT: 6090
 CODE: PLUMBING CODE YEAR: 2007
 SECTION: 909
 QUESTION:
 IS IT THE INTENT OF THE FLORIDA BUILDING CODE -
 PLUMBING SECTION 909 TO ALLOW A URINAL TO WET VENT A
 SINGLE COMMERCIAL
 WATER CLOSET OR TO DRAIN INTO THAT WATER CLOSET?S
 INDIVIDUAL VENT?
 COMMENT:
 ANSWER:
 NO. ONLY FIXTURES IN BATHROOM GROUPS AS DEFINED IN
 FLORIDA BUILDING CODE - PLUMBING CHAPTER 2 ARE
 PERMITTED TO
 CONNECT TO THE WET VENT. ANY ADDITIONAL FIXTURES MUST
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 COMMENTARY:
 A URINAL IS NOT INCLUDED IN THE DEFINITION OF A
 BATHROOM GROUP.
 NOTICE:
 THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN
 COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ICC, AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS
 INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE
 INTEREST OF CONSISTENCY IN THEIR APPLICATION
 STATEWIDE. THIS INTERPRETATION IS INFORMAL, NON-BINDING
 AND SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL
 BUILDING OFFICIAL.
  
 6) THE SAME SITUATION OCCURS WITHIN THE MENS RESTROOM
 WITH THE WATER CLOSETS, THEY SHOULD BE EITHER
 INDIVIDUALLY VENTED. 2010 FBC- P 907.1.
  
 7) THE PLANS DO NOT SHOW ANY VENTING THA TIES BACK INTO
 THE BUILDING TO THE OUTDOORS. 2010 FBC-P 903.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-06-27 Cont ID  
Sent By aaponte Date 2014-06-27 Time 12:55 Rev Time 0.00
Received By aaponte Date 2014-06-27 Time 12:55 Sent To  
Notes
2014-06-27 12:56:18PROVISO: ESTABLISHMENT SHALL OPERATE AS A RESTAURANT.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-06-11 Cont ID  
Sent By aaponte Date 2014-06-11 Time 09:51 Rev Time 0.00
Received By aaponte Date 2014-06-11 Time 09:50 Sent To  
Notes
2014-06-11 09:59:521.BASED ON THE INFORMATION PROVIDED IN THE SUBMITTAL,
 THE PROPOSED ESTABLISHMENT IS CLASSIFIED AS A BAR.
 BASED ON THE REQUIREMENTS OF CHAPTER 6 OF THE CITY
 CODE, THE LOCATION IS NOT AUTHORIZED FOR THE SALE OF
 ALCOHOL, AND THE PROPOSED KARAOKE BAR DOES NOT MEET THE
 REQUIREMENTS OF A BONA FIDE RESTAURANT. IF THE SALE OF
 ALCOHOL IS NOT PROPOSED IN THE ESTABLISHMENT PLEASE
 INCLUDE A NOTE IN THE DRAWINGS STATING SUCH CONDITION.
 2. IF THE SALE OF ALCOHOL IS INTENDED, THE
 ESTABLISHMENT SHALL COMPLY WITH THE REQUIREMENTS OF A
 BONA FIDE RESTAURANT IN SECTION 6-1 OF THE CITY CODE
 (CHAPTER 6, SECTION 6-1).
 3. PLEASE INCLUDE A FACADE OF THE EXISTING BUILDING,
 AND INDICATE ANY PROPOSED CHANGES TO THE ELEVATION.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.