Plan Review Details - Permit 14050223
Plan Review Stops For Permit 14050223
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By jwitmer Date 2014-05-28 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2014-05-28 Time 06:34 Sent To  
Notes
2014-05-28 07:27:12BUILDING PLAN REVIEW
 REVISION: 14050223
 PERMIT: 14021098
 ADD: 915 S DIXIE HWY
 CONT: DEALERSHIP SOLUTIONS LLC
 TEL: (727)465-4413
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 28/ 2014
 ACTION: PROVISO
  
 SHEET A201 NOTE # 1 INDICATES THE USE OF AUCOBOND
 PANELS, ACM WINGS FACIA ELEMENT, PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B 1407.3 ARCHITECTURAL TRIM
 AND EMBELLISHMENTS.
 MCM USED AS ARCHITECTURAL TRIM OR EMBELLISHMENTS SHALL
 COMPLY WITH SECTIONS 1407.7 THROUGH 1407.14.
  
 1407.4 STRUCTURAL DESIGN.
 MCM SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED TO RESIST
 WIND LOADS AS REQUIRED BY CHAPTER 16 FOR COMPONENTS AND
 CLADDING.
  
 1407.5 APPROVAL.
 RESULTS OF APPROVED TESTS OR AN ENGINEERING ANALYSIS
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO VERIFY
 COMPLIANCE WITH THE REQUIREMENTS OF CHAPTER 16 FOR WIND
 LOADS.
  
 1407.6 WEATHER RESISTANCE.
 MCM SYSTEMS SHALL COMPLY WITH SECTION 1403 AND SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST WIND AND RAIN IN
 ACCORDANCE WITH THIS SECTION AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
 1407.7 DURABILITY.
 MCM SYSTEMS SHALL BE CONSTRUCTED OF APPROVED MATERIALS
 THAT MAINTAIN THE PERFORMANCE CHARACTERISTICS REQUIRED
 IN SECTION 1407 FOR THE DURATION OF USE.
  
 1407.8 FIRE-RESISTANCE RATING.
 WHERE MCM SYSTEMS ARE USED ON EXTERIOR WALLS REQUIRED
 TO HAVE A FIRE-RESISTANCE RATING IN ACCORDANCE WITH
 SECTION 705, EVIDENCE SHALL BE SUBMITTED TO THE
 BUILDING OFFICIAL THAT THE REQUIRED FIRE-RESISTANCE
 RATING IS MAINTAINED.
  
 EXCEPTION: MCM SYSTEMS NOT CONTAINING FOAM PLASTIC
 INSULATION, WHICH ARE INSTALLED ON THE OUTER SURFACE OF
 A FIRE-RESISTANCE-RATED EXTERIOR WALL IN A MANNER SUCH
 THAT THE ATTACHMENTS DO NOT PENETRATE THROUGH THE
 ENTIRE EXTERIOR WALL ASSEMBLY, SHALL NOT BE REQUIRED TO
 COMPLY WITH THIS SECTION.
  
 1407.9 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE SPECIFIED, MCM SHALL HAVE A FLAME
 SPREAD INDEX OF 75 OR LESS AND A SMOKE-DEVELOPED INDEX
 OF 450 OR LESS WHEN TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723.
  
 1407.10 TYPE I, II, III AND IV CONSTRUCTION.
 WHERE INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS
 1407.10.1 THROUGH 1407.10.4, OR SECTION 1407.11.
  
 1407.10.1 SURFACE-BURNING CHARACTERISTICS.
 MCM SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 WHEN
 TESTED AS AN ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED
 FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 1407.10.2 THERMAL BARRIERS.
 MCM SHALL BE SEPARATED FROM THE INTERIOR OF A BUILDING
 BY AN APPROVED THERMAL BARRIER CONSISTING OF 1/2-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250?F (121?C) AFTER 15 MINUTES OF FIRE EXPOSURE IN
 ACCORDANCE WITH THE STANDARD TIME-TEMPERATURE CURVE OF
 ASTM E 119 OR UL 263. THE THERMAL BARRIER SHALL BE
 INSTALLED IN SUCH A MANNER THAT IT WILL REMAIN IN PLACE
 FOR NOT LESS THAN 15 MINUTES BASED ON A TEST CONDUCTED
 IN ACCORDANCE WITH UL 1715.
  
 1407.10.3 THERMAL BARRIER NOT REQUIRED.
 THE THERMAL BARRIER SPECIFIED FOR MCM IN SECTION
 1407.10.2 IS NOT REQUIRED WHERE:
  
 1. THE MCM SYSTEM IS SPECIFICALLY APPROVED BASED ON
 TESTS CONDUCTED IN ACCORDANCE WITH UL 1040 OR UL 1715.
 SUCH TESTING SHALL BE PERFORMED WITH THE MCM IN THE
 MAXIMUM THICKNESS INTENDED FOR USE. THE MCM SYSTEM
 SHALL INCLUDE SEAMS, JOINTS AND OTHER TYPICAL DETAILS
 USED IN THE INSTALLATION AND SHALL BE TESTED IN THE
 MANNER INTENDED FOR USE.
  
 2. THE MCM IS USED AS ELEMENTS OF BALCONIES AND SIMILAR
 PROJECTIONS, ARCHITECTURAL TRIM OR EMBELLISHMENTS.
  
 1407.10.4 FULL-SCALE TESTS.
 THE MCM SYSTEM SHALL BE TESTED IN ACCORDANCE WITH, AND
 COMPLY WITH, THE ACCEPTANCE CRITERIA OF NFPA 285. SUCH
 TESTING SHALL BE PERFORMED ON THE MCM SYSTEM WITH THE
 MCM IN THE MAXIMUM THICKNESS INTENDED FOR USE.
  
 1407.11 ALTERNATE CONDITIONS.
 MCM AND MCM SYSTEMS SHALL NOT BE REQUIRED TO COMPLY
 WITH SECTIONS 1407.10.1 THROUGH 1407.10.4 PROVIDED SUCH
 SYSTEMS COMPLY WITH SECTION 1407.11.1 OR 1407.11.2.
  
 1407.11.1 INSTALLATIONS UP TO 40 FEET IN HEIGHT.
 MCM SHALL NOT BE INSTALLED MORE THAN 40 FEET (12 190
 MM) IN HEIGHT ABOVE GRADE WHERE INSTALLED IN ACCORDANCE
 WITH SECTIONS 1407.11.1.1 AND 1407.11.1.2.
  
 1407.11.1.1 FIRE SEPARATION DISTANCE OF 5 FEET OR LESS.
 WHERE THE FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM)
 OR LESS, THE AREA OF MCM SHALL NOT EXCEED 10 PERCENT OF
 THE EXTERIOR WALL SURFACE.
  
 1407.11.1.2 FIRE SEPARATION DISTANCE GREATER THAN 5
 FEET.
 WHERE THE FIRE SEPARATION DISTANCE IS GREATER THAN 5
 FEET (1524 MM), THERE SHALL BE NO LIMIT ON THE AREA OF
 EXTERIOR WALL SURFACE COVERAGE USING MCM.
  
 1407.11.2 INSTALLATIONS UP TO 50 FEET IN HEIGHT.
 MCM SHALL NOT BE INSTALLED MORE THAN 50 FEET (15 240
 MM) IN HEIGHT ABOVE GRADE WHERE INSTALLED IN ACCORDANCE
 WITH SECTIONS 1407.11.2.1 AND 1407.11.2.2.
  
 1407.11.2.1 SELF-IGNITION TEMPERATURE.
 MCM SHALL HAVE A SELF-IGNITION TEMPERATURE OF 650?F
 (343?C) OR GREATER WHEN TESTED IN ACCORDANCE WITH ASTM
 D 1929.
  
 1407.11.2.2 LIMITATIONS.
 SECTIONS OF MCM SHALL NOT EXCEED 300 SQUARE FEET (27.9
 M2) IN AREA AND SHALL BE SEPARATED BY A MINIMUM OF 4
 FEET (1219 MM) VERTICALLY.
  
 1407.12 TYPE V CONSTRUCTION.
 MCM SHALL BE PERMITTED TO BE INSTALLED ON BUILDINGS OF
 TYPE V CONSTRUCTION.
  
 1407.13 FOAM PLASTIC INSULATION.
 MCM SYSTEMS CONTAINING FOAM PLASTIC INSULATION SHALL
 ALSO COMPLY WITH THE REQUIREMENTS OF SECTION 2603.
  
 1407.14 LABELING.
 MCM SHALL BE LABELED IN ACCORDANCE WITH SECTION 1703.5.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-30 Cont ID  
Sent By rlecky Date 2014-05-30 Time 14:58 Rev Time 0.00
Received By dhayes Date 2014-05-30 Time 13:01 Sent To FIRE
Notes
2014-05-30 14:57:55 
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-06-02 Cont ID  
Sent By pdeluca Date 2014-06-02 Time 08:25 Rev Time 0.00
Received By skennedy Date 2014-05-09 Time 08:24 Sent To  
Notes
2014-06-02 08:25:32REVIEW BY PLEDUC.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-02 Cont ID  
Sent By skennedy Date 2014-06-02 Time 08:30 Rev Time 0.00
Received By skennedy Date 2014-05-07 Time 11:17 Sent To  
Notes
2014-05-08 11:19:30B05

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-27 Cont ID  
Sent By hmoser Date 2014-05-27 Time 09:44 Rev Time 0.00
Received By hmoser Date 2014-05-27 Time 09:44 Sent To  
Notes
2014-05-27 09:45:45PLAN REVIEW BY JS. PX1328

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-05-28 Cont ID  
Sent By jwitmer Date 2014-05-28 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2014-05-28 Time 06:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2014-06-02 Cont ID  
Sent By ajones Date 2014-06-02 Time 08:29 Rev Time 0.00
Received By skennedy Date 2014-06-02 Time 08:29 Sent To  
Notes
***NONE***