Plan Review Details - Permit 14050183
Plan Review Stops For Permit 14050183
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-31 Cont ID  
Sent By jwitmer Date 2014-07-31 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2014-07-31 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-27 Cont ID  
Sent By jwitmer Date 2014-05-27 Time 07:46 Rev Time 0.00
Received By jwitmer Date 2014-05-27 Time 06:04 Sent To  
Notes
2014-05-27 07:07:56BUILDING PLAN REVIEW
 PERMIT: 14050183
 ADD: 2800 S DIXIE HWY
 CONT: VERITAS DEVELOPMENT
 TEL: (561)346-4330
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY MAY 27/2014
 ACTION: DENIED
  
 1) SHEET A1 ALSO INDICATES VARIOUS VENDORS WITHOUT
 TENANT SEPARATIONAND OPEN FRONT. THE CODE MAKES
 EXCEPTIONS FOR MINI STORAGE UNITS BUT NOT UNDER THE
 MERCANTILE OCCUPANCY. IF THE INTENT IS TO BE A MALL
 SETTING THEN YOU HAVE TO MEET THE REQUIREMENTS OF A
 ENCLOSED MALL UNDER 2010 FBC-B 402.5 MALL WIDTHS, AND
 402.4.5.
  
 2) A-3 SERVICE COUNTER PLEASE PROVIDE HEIGHT OF THE
 SERVICE COUNTER AND COMPLIANCE WITH 2010 FL
 ACCESSIBILTY CODE
 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
  
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 3) SHEET A1 SHOWS A PAIR OF NEW INSWING DOORS AS WELL
 AS 2 NEW FRONT ENRY DOORS PLEASE PROVIDE PRODUCT
 APPROVALS. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-08-12 Cont ID  
Sent By dhayes Date 2014-08-12 Time 11:47 Rev Time 0.00
Received By dhayes Date 2014-08-12 Time 11:31 Sent To  
Notes
2014-08-12 11:35:08DATE: 8/6/2014
 PROJECT: THE EXIT FACILITY
 PERMIT#: 14050183
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) FBC-ENERGY
 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
 AUTOMATIC LIGHTING SHUTOFF IS REQUIRED IN BUILDINGS
 LARGER THAN 5,000 SQUARE FEET AND SHALL BE EQUIPPED
 WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING
 IN THOSE AREAS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR
 SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO .
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-04 Cont ID  
Sent By dhayes Date 2014-06-04 Time 14:04 Rev Time 0.00
Received By dhayes Date 2014-06-04 Time 11:46 Sent To  
Notes
2014-06-04 14:05:14ADDRESS: 2800 S. DIXIE HIGHWAY WPB
 PERMIT#:14050183
 1ST ELECTRICAL REVIEW
 ACTION: DENIED.
 CODE: 2008 NEC AND 2010 FBC
  
 DEFICIENCIES:
  
 1) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE
 SUPPLIED BY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. NEC 230.2 PLEASE MAKE THE NECESSARY
 CORRECTIONS TO THIS CONDITION AND RE-SUBMIT.
  
 2) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
 3) LISTED SINGLE AND MULTIPLE STATION SMOKE ALARMS
 COMPLYING WITH UL 217 SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTIONS 907.2.11.1 THROUGH 907.2.11.4 AND NFPA
 72.
  
 4) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 701.11(G)
  
 5) ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE. FOR THE PURPOSE OF THIS REQUIRMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCELATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY. ADDITIONAL
 EMERGENCY BATTERY BACKED LIGHTING IS REQUIRED FOR
 ADAQUATE ILLUMINATION OF THE EGRESS PATH. FBC 1006.1.1
  
 6) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED
 IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE
 OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT
 DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT
 REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 7) FOR SHOW-WINDOW LIGHTING, A LOAD OF NOT LESS THAN
 200 VOLT-AMPS PER LINEAL FT. SHALL BE INCLUDED FOR A
 SHOW WINDOW MEASURED HORIZONTALLY ALONG ITS BASE. NEC
 220.43(A)
  
 8) FOR TRACK LIGHTING IN OTHER THAN DWELLING UNITS AN
 ADDITIONAL LOAD OF 150 VOLT-AMPS PER LINEAL FT. SHALL
 BE INCLUDED FOR EVERY 2 LINEAL FT. OF TRACK LIGHTING OR
 FRACTION THEREOF. WHERE MULTI-CIRCUIT TRACK IS
 INSTALLED THE LOAD SHALL BE DISTRIBUTED EQUALLY AMONG
 THE TRACK CIRCUITS.
  
 9) ALL COMPONENTS AND CABLES SHALL BE UL LISTED AND
 LABELED FOR USE IN THE MANNER INSTALLED. NEC 110.3
  
 10) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR
 SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO AND FOR THE
 INSTALLATION AND TERMINATION OF THE OUTDOOR MENU
 BOARDS, CANOPY, AND PRE-SALE BOARD.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-07-24 Cont ID  
Sent By pleduc Date 2014-07-24 Time   Rev Time 0.00
Received By pleduc Date 2014-07-24 Time 11:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-05-09 Cont ID  
Sent By pleduc Date 2014-05-09 Time   Rev Time 0.00
Received By pleduc Date 2014-05-09 Time 11:43 Sent To B
Notes
2014-05-09 12:46:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENT:
  
 SHEET A-1; THE FIRE RATING OF THE SEPARATION WALL OF
 UNIT #3 SHALL BE INDICATED ON THE PLAN. ANY
 RE-CONSTRUCTION ON THAT WALL SHALL NOT BE LESS THAN
 EXISTING AND INDICATED AND OUTLINED ON THE PLAN;SHEET
 A-3.
  
 SHEET A/C; THE HEIGHT FROM THE FLOOR TO THE BOTTOM OF
 THE A/C DUCT WORK SHALL BE INDICATED AND WITHIN THE
 REQUIREMENTS OF THE CODE FOR EXIT ROUTES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-12 Cont ID  
Sent By hmoser Date 2014-08-12 Time 13:25 Rev Time 0.00
Received By hmoser Date 2014-07-22 Time 14:13 Sent To  
Notes
2014-07-23 14:13:19C15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-04 Cont ID  
Sent By dhayes Date 2014-06-04 Time 14:05 Rev Time 0.00
Received By dhayes Date 2014-05-06 Time 10:27 Sent To  
Notes
2014-05-07 10:28:34INCOMING SENT TO C15. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-05-27 Cont ID  
Sent By jwitmer Date 2014-05-27 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2014-05-27 Time 08:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-08-12 Cont ID  
Sent By hmoser Date 2014-08-12 Time 13:24 Rev Time 0.00
Received By hmoser Date 2014-08-12 Time 13:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-05-27 Cont ID  
Sent By hmoser Date 2014-05-27 Time 13:17 Rev Time 0.00
Received By hmoser Date 2014-05-27 Time 12:52 Sent To  
Notes
2014-05-27 13:17:42PLAN DENIED
 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE 401.3
 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 3) PROVIDE ENERGY CALCULATIONS PER SECTION 503.2.1
 CALCULATION OF HEATING AND COOLING 2010 FLORIDA ENERGY
 CODE.
 4) PROVIDE A DETAIL FROM THE ENGINEER ON UNIT TIEDOWN
 TO ROOF.
 PER SECTION 301.12 WIND RESISTANCE FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-07-31 Cont ID  
Sent By jwitmer Date 2014-07-31 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2014-07-31 Time 07:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-05-27 Cont ID  
Sent By jwitmer Date 2014-05-27 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2014-05-27 Time 06:04 Sent To  
Notes
2014-05-27 08:51:31PLUMBING PLAN REVIEW
 PERMIT: 14050183
 ADD: 2800 S DIXIE HWY
 CONT: VERITAS DEVELOPMENT
 TEL: (561)346-4330
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY MAY 27/2014
 ACTION: DENIED
  
 1) PLEASE REVIEW THE 2010 FL ACCESSIBILITY CODE THERE
 IS ONLY ONE ACCESSIBLE RESTROOM AND NO FEES HAVE BEEN
 PUT FORTH FOR ACCESSBLE UPGRADES AS IN DISPROPORTIONATE
 COST 202.4.1. THERE SEAMS TO BE A ACCESSIBLE ENTRANCE
 AND A ACCESSIBLE ROUTETHE THIRD AREA TO PROVIDE
 ACCESSIBLE UPGRADES IS RESTROOMS (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS. THERE IS ONE ACCESSIBLE RESTROOM
 THAT IS CODE COMPLIANT UNDER THE 2007 FBC. THIS RESTROM
 DOES NOT NEED TO BE TOUCHED, IT IS THE OTHER RESTROOM.
 20% OF THE CONTRACT VALUE OR $12,000 NEEDS TO BE SPENT
 IN ACCESSIBLE UPGRADES, RESTROOMS, THEN A HIGH LOW
 DRINKING FOUNTAIN IF THE $12,000 DOLLARS HAS NOT BEEN
 USED UP INTHE RESTROOM REMODEL.
  
 2) THE PLANS ALSO SHOW A NEW MOP/ SERVICE SINK AND NO
 ISOMETRIC OF THE SANITARY, 2010 FBC-PLUMBING 907.1.
 WILL REQUIRE ITS OWN VENT IT CAN NOT BE ON A WET VENT
 SYSTEM, THESE ARE ONLY FOR SINGLE FAMILY RESIDENCES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2014-07-25 Cont ID  
Sent By llouie Date 2014-07-25 Time 14:15 Rev Time 0.00
Received By llouie Date 2014-07-25 Time 14:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-05-19 Cont ID  
Sent By llouie Date 2014-05-19 Time 11:16 Rev Time 0.00
Received By llouie Date 2014-05-19 Time 11:16 Sent To  
Notes
2014-05-19 11:17:31** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY. NEW A/C
 UNITS HAVE BEEN IDENTIFIED IN THE PLANS AND A SURVEY IS
 NEEDED TO DETERMINE THE DISTANCE OF THE A/C UNITS IN
 RELATIONSHIP TO THE PROPERTY LINES.
  
 2.) BANNERS AND PENNANTS ARE NOT PERMITTED ON THE
 BUILDING. PLEASE REMOVE THE PROPOSED FLAG POLE FOR THE
 BANNER. (ZLDR S.94-401(B)(2))
  
 3.) ANY PROJECTIONS INTO THE RIGHT-OF-WAY, INCLUDING
 THE ORNAMENTAL DISHES, WILL REQUIRE REVIEW AND A
 RIGHT-OF-WAY PERMIT FROM ENGINEERING SERVICES AND FDOT.
  
 4.) WHAT IS THE PROPOSED USE OF THE BUILDING?
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  