Plan Review Details - Permit 14050183
| Plan Review Stops For Permit 14050183 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-07-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-07-31 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-07-31 |
Time |
07:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-05-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-05-27 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-05-27 |
Time |
06:04 |
Sent To |
|
|
| Notes |
| 2014-05-27 07:07:56 | BUILDING PLAN REVIEW | | | PERMIT: 14050183 | | | ADD: 2800 S DIXIE HWY | | | CONT: VERITAS DEVELOPMENT | | | TEL: (561)346-4330 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUESDAY MAY 27/2014 | | | ACTION: DENIED | | | | | | 1) SHEET A1 ALSO INDICATES VARIOUS VENDORS WITHOUT | | | TENANT SEPARATIONAND OPEN FRONT. THE CODE MAKES | | | EXCEPTIONS FOR MINI STORAGE UNITS BUT NOT UNDER THE | | | MERCANTILE OCCUPANCY. IF THE INTENT IS TO BE A MALL | | | SETTING THEN YOU HAVE TO MEET THE REQUIREMENTS OF A | | | ENCLOSED MALL UNDER 2010 FBC-B 402.5 MALL WIDTHS, AND | | | 402.4.5. | | | | | | 2) A-3 SERVICE COUNTER PLEASE PROVIDE HEIGHT OF THE | | | SERVICE COUNTER AND COMPLIANCE WITH 2010 FL | | | ACCESSIBILTY CODE | | | 904.3.3 CHECK WRITING SURFACES. | | | WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY | | | WITH 902.3. | | | | | | 904.4 SALES AND SERVICE COUNTERS. | | | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH | | | 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE | | | COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR | | | SERVICE COUNTER TOP. | | | | | | 3) SHEET A1 SHOWS A PAIR OF NEW INSWING DOORS AS WELL | | | AS 2 NEW FRONT ENRY DOORS PLEASE PROVIDE PRODUCT | | | APPROVALS. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.41 COMPONENTS & CLADDING | | | | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-08-12 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-08-12 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-08-12 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2014-08-12 11:35:08 | DATE: 8/6/2014 | | | PROJECT: THE EXIT FACILITY | | | PERMIT#: 14050183 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) FBC-ENERGY | | | 505.2 LIGHTING CONTROLS (MANDATORY). | | | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS | | | REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND | | | 505.2.4. | | | AUTOMATIC LIGHTING SHUTOFF IS REQUIRED IN BUILDINGS | | | LARGER THAN 5,000 SQUARE FEET AND SHALL BE EQUIPPED | | | WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING | | | IN THOSE AREAS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR | | | SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO . | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-06-04 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-06-04 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-06-04 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2014-06-04 14:05:14 | ADDRESS: 2800 S. DIXIE HIGHWAY WPB | | | PERMIT#:14050183 | | | 1ST ELECTRICAL REVIEW | | | ACTION: DENIED. | | | CODE: 2008 NEC AND 2010 FBC | | | | | | DEFICIENCIES: | | | | | | 1) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE | | | SUPPLIED BY ONE SERVICE UNLESS PERMITTED IN 230.2(A) | | | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 | | | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND | | | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED | | | TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER | | | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING | | | ONE SERVICE. NEC 230.2 PLEASE MAKE THE NECESSARY | | | CORRECTIONS TO THIS CONDITION AND RE-SUBMIT. | | | | | | 2) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.22, 110.16, 110.22 | | | | | | 3) LISTED SINGLE AND MULTIPLE STATION SMOKE ALARMS | | | COMPLYING WITH UL 217 SHALL BE INSTALLED IN ACCORDANCE | | | WITH SECTIONS 907.2.11.1 THROUGH 907.2.11.4 AND NFPA | | | 72. | | | | | | 4) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY | | | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS | | | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND | | | CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 701.11(G) | | | | | | 5) ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN | | | ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND | | | STRUCTURE. FOR THE PURPOSE OF THIS REQUIRMENT, EXIT | | | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, | | | CORRIDORS, RAMPS, ESCELATORS, WALKWAYS AND EXIT | | | PASSAGEWAYS LEADING TO A PUBLIC WAY. ADDITIONAL | | | EMERGENCY BATTERY BACKED LIGHTING IS REQUIRED FOR | | | ADAQUATE ILLUMINATION OF THE EGRESS PATH. FBC 1006.1.1 | | | | | | 6) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED | | | IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE | | | OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT | | | DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT | | | REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. | | | | | | 7) FOR SHOW-WINDOW LIGHTING, A LOAD OF NOT LESS THAN | | | 200 VOLT-AMPS PER LINEAL FT. SHALL BE INCLUDED FOR A | | | SHOW WINDOW MEASURED HORIZONTALLY ALONG ITS BASE. NEC | | | 220.43(A) | | | | | | 8) FOR TRACK LIGHTING IN OTHER THAN DWELLING UNITS AN | | | ADDITIONAL LOAD OF 150 VOLT-AMPS PER LINEAL FT. SHALL | | | BE INCLUDED FOR EVERY 2 LINEAL FT. OF TRACK LIGHTING OR | | | FRACTION THEREOF. WHERE MULTI-CIRCUIT TRACK IS | | | INSTALLED THE LOAD SHALL BE DISTRIBUTED EQUALLY AMONG | | | THE TRACK CIRCUITS. | | | | | | 9) ALL COMPONENTS AND CABLES SHALL BE UL LISTED AND | | | LABELED FOR USE IN THE MANNER INSTALLED. NEC 110.3 | | | | | | 10) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR | | | SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO AND FOR THE | | | INSTALLATION AND TERMINATION OF THE OUTDOOR MENU | | | BOARDS, CANOPY, AND PRE-SALE BOARD. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2014-07-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-07-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-07-24 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-05-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-05-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-05-09 |
Time |
11:43 |
Sent To |
B |
|
| Notes |
| 2014-05-09 12:46:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENT: | | | | | | SHEET A-1; THE FIRE RATING OF THE SEPARATION WALL OF | | | UNIT #3 SHALL BE INDICATED ON THE PLAN. ANY | | | RE-CONSTRUCTION ON THAT WALL SHALL NOT BE LESS THAN | | | EXISTING AND INDICATED AND OUTLINED ON THE PLAN;SHEET | | | A-3. | | | | | | SHEET A/C; THE HEIGHT FROM THE FLOOR TO THE BOTTOM OF | | | THE A/C DUCT WORK SHALL BE INDICATED AND WITHIN THE | | | REQUIREMENTS OF THE CODE FOR EXIT ROUTES. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-08-12 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-08-12 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-07-22 |
Time |
14:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-06-04 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-06-04 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-06 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2014-05-07 10:28:34 | INCOMING SENT TO C15. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2014-05-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-05-27 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-05-27 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-08-12 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-08-12 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-08-12 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-05-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-05-27 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-05-27 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2014-05-27 13:17:42 | PLAN DENIED | | | 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE 401.3 | | | 2010 FBC (M) | | | 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | | 2010 FLORIDA ENERGY CODE. | | | 3) PROVIDE ENERGY CALCULATIONS PER SECTION 503.2.1 | | | CALCULATION OF HEATING AND COOLING 2010 FLORIDA ENERGY | | | CODE. | | | 4) PROVIDE A DETAIL FROM THE ENGINEER ON UNIT TIEDOWN | | | TO ROOF. | | | PER SECTION 301.12 WIND RESISTANCE FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-07-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-07-31 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-07-31 |
Time |
07:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-05-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-05-27 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-05-27 |
Time |
06:04 |
Sent To |
|
|
| Notes |
| 2014-05-27 08:51:31 | PLUMBING PLAN REVIEW | | | PERMIT: 14050183 | | | ADD: 2800 S DIXIE HWY | | | CONT: VERITAS DEVELOPMENT | | | TEL: (561)346-4330 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUESDAY MAY 27/2014 | | | ACTION: DENIED | | | | | | 1) PLEASE REVIEW THE 2010 FL ACCESSIBILITY CODE THERE | | | IS ONLY ONE ACCESSIBLE RESTROOM AND NO FEES HAVE BEEN | | | PUT FORTH FOR ACCESSBLE UPGRADES AS IN DISPROPORTIONATE | | | COST 202.4.1. THERE SEAMS TO BE A ACCESSIBLE ENTRANCE | | | AND A ACCESSIBLE ROUTETHE THIRD AREA TO PROVIDE | | | ACCESSIBLE UPGRADES IS RESTROOMS (III) AT LEAST ONE | | | ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX | | | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE | | | DRINKING FOUNTAINS. THERE IS ONE ACCESSIBLE RESTROOM | | | THAT IS CODE COMPLIANT UNDER THE 2007 FBC. THIS RESTROM | | | DOES NOT NEED TO BE TOUCHED, IT IS THE OTHER RESTROOM. | | | 20% OF THE CONTRACT VALUE OR $12,000 NEEDS TO BE SPENT | | | IN ACCESSIBLE UPGRADES, RESTROOMS, THEN A HIGH LOW | | | DRINKING FOUNTAIN IF THE $12,000 DOLLARS HAS NOT BEEN | | | USED UP INTHE RESTROOM REMODEL. | | | | | | 2) THE PLANS ALSO SHOW A NEW MOP/ SERVICE SINK AND NO | | | ISOMETRIC OF THE SANITARY, 2010 FBC-PLUMBING 907.1. | | | WILL REQUIRE ITS OWN VENT IT CAN NOT BE ON A WET VENT | | | SYSTEM, THESE ARE ONLY FOR SINGLE FAMILY RESIDENCES. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-07-25 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2014-07-25 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2014-07-25 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-05-19 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2014-05-19 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2014-05-19 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2014-05-19 11:17:31 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY. NEW A/C | | | UNITS HAVE BEEN IDENTIFIED IN THE PLANS AND A SURVEY IS | | | NEEDED TO DETERMINE THE DISTANCE OF THE A/C UNITS IN | | | RELATIONSHIP TO THE PROPERTY LINES. | | | | | | 2.) BANNERS AND PENNANTS ARE NOT PERMITTED ON THE | | | BUILDING. PLEASE REMOVE THE PROPOSED FLAG POLE FOR THE | | | BANNER. (ZLDR S.94-401(B)(2)) | | | | | | 3.) ANY PROJECTIONS INTO THE RIGHT-OF-WAY, INCLUDING | | | THE ORNAMENTAL DISHES, WILL REQUIRE REVIEW AND A | | | RIGHT-OF-WAY PERMIT FROM ENGINEERING SERVICES AND FDOT. | | | | | | 4.) WHAT IS THE PROPOSED USE OF THE BUILDING? | | | | | | PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS | | | MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE | | | @ (561) 822-1458 IF YOU HAVE QUESTIONS. | | | | | 2014-05-12 17:17:48 | 5/12/14 |
|
|
|