Plan Review Details - Permit 14050164
Plan Review Stops For Permit 14050164
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-05-28 Cont ID  
Sent By rmcdouga Date 2014-05-28 Time 14:31 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 14:31 Sent To  
Notes
2014-05-28 14:33:00PROVISO ITEMS HAVE BEEN ADDRESSED IN THE REVISED PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-24 Cont ID  
Sent By rmcdouga Date 2014-05-24 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2014-05-24 Time 09:26 Sent To  
Notes
2014-05-24 10:31:01APPROVED WITH EXCEPTIONS.
  
 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 FRENCH DOORS IN THE LIVING ROOM THAT WAS PREVIOUSLY THE
 GARAGE AREA. DCA RULE 9N-3
  
 2) EXISTING WINDOWS IN FORMER GARAGE AREA ARE REQUIRED
 TO HAVE LARGE MISSILE IMPACT PROTECTION. FBC R301.2.1.2
  
 3) THE BEDROOM IS REQUIRED TO HAVE AN EMERGENCY ESCAPE
 AND RESCUE OPENING THAT COMPLIES WITH FBC R310.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-09 Cont ID  
Sent By rmcdouga Date 2014-05-09 Time 10:54 Rev Time 0.00
Received By rmcdouga Date 2014-05-06 Time 18:23 Sent To  
Notes
2014-05-08 13:28:402010 FBC
  
 DENIED BY BUILDING
  
 1) THE PALM BEACH COUNTY PROPERTY APPRAISER RECORDS
 SHOW THAT THIS STRUCTURE IS A ONE STORY GARAGE
 APARTMENT. THE CITY OF WEST PALM BEACH DOES NOT HAVE
 ANY RECORDS THAT INDICATE THAT THE 16' X 22' GARAGE
 PORTION WAS CONVERTED TO LIVING AREA WITH THE REQUIRED
 PERMITS AND INSPECTIONS. IN ORDER TO BRING THE GUEST
 HOUSE INTO COMPLIANCE, THE AREA THAT WAS CONVERTED FROM
 GARAGE TO LIVING SPACE WILL HAVE TO BE MADE CODE
 COMPLIANT OR RETURNED TO A GARAGE. THE FOLLOWING REVIEW
 WILL BE WHAT IS REQUIRED TO BRING THE CONVERTED GARAGE
 INTO COMPLIANCE. 2010 FBC EXISTING BUILDING, 2010 FBC
 RESIDENTIAL AND 2008 NEC
  
 2) GENERAL NOTE #9 ON SHEET GH1 NEEDS TO BE CORRECTED.
 THE WINDSPEED IS 170 MPH VULT , THE EXPOSURE CATEGORY
 IS D AND THE APPLICABLE BUILDING CODE IS THE 2010
 FLORIDA BUILDING CODE.
  
 3) UNLESS YOU CAN SHOW THAT THE EXTERIOR FRENCH DOOR
 AND THE WINDOWS IN THE CONVERTED GARAGE WERE PERMITTED
 AND INSPECTED, PRODUCT APPROVALS WILL NEED TO BE
 SUBMITTED AS REQUIRED BY DCA RULE 9N-3.
  
 4) SHOW COMPLIANCE WITH FBCR 301.2.1.2 WHICH REQUIRES
 THE WINDOWS AND DOORS WITH GLAZED AREAS TO PROTECTED
 FROM LARGE MISSILE IMPACT. IMPACT RATED EXTERIOR DOORS
 AND WINDOWS OR STORM PANELS WILL BE REQUIRED.
  
 5) PRODUCT APPROVALS WILL BE REQUIRED FOR THE STORM
 PANELS. A KEY PLAN AND INSTALLATION SCHEDULE THAT
 PROVIDES COMPLETE INSTALLATION DETAILS IS REQUIRED. DCA
 RULE 9N-3, CITY AMENDMENTS 107.2.1 AND 107.2.1.3
  
 6) THE CONTINUOUS LOAD PATH FROM THE ROOF THE THE
 FOUNDATION WILL NEED TO BE EVALUATED. IF IT IS NOT CODE
 COMPLIANT, ADDITION STRAPS AND CONNECTORS MAY BE
 REQUIRED. FBC R301.1
  
 7) SMOKE ALARMS AS REQUIRED FOR NEW DWELLINGS WILL BE
 REQUIRED. FBC R314.3.1
  
 8)THE ELECTRICAL SYSTEM WILL NEED TO BE MADE CODE
 COMPLIANT. SEE ELECTRICAL REVIEW NOTES. 2008 NEC
  
 9) BECAUSE THE STRUCTURE IS HISTORIC PER FS 267.021, IT
 IS EXEMPT FROM THE 2010 FBC ENERGY CODE PER SECTION
 101.4.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-05-28 Cont ID  
Sent By rmcdouga Date 2014-05-28 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 14:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-05-24 Cont ID  
Sent By rmcdouga Date 2014-05-24 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2014-05-24 Time 09:26 Sent To  
Notes
2014-05-24 10:39:472010 FBC / 2008 NEC
  
 DENIED
  
 1) THE ELECTRIC PLAN DID NOT PRINT PROPERLY. PARTS OF
 IT ARE FADED OUT AND ARE NOT ACCEPTABLE FOR COPYING
 INTO THE BUILDING DEPARTMENT'S PUBLIC RECORDS. CITY
 AMENDMENTS 107.2.1.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-09 Cont ID  
Sent By rmcdouga Date 2014-05-09 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2014-05-06 Time 18:23 Sent To  
Notes
2014-05-09 11:37:032010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) SHOW THE LOCATION OF THE EXISTING METER AND CIRCUIT
 BREAKER PANEL. CITY AMENDMENTS 107.2.1 AND NEC
  
 2) SUBMIT LOAD CALCULATIONS AND A PANEL SCHEDULE. NEC
 220.40 AND NEC 408.4
  
 3) SHOW COMPLIANCE WITH NEC 210.11 (C) (3) FOR THE
 REQUIRED 20 AMP BATHROOM CIRCUIT.
  
 4) SHOW COMPLIANCE WITH NEC 210.8 (A) (1), (2) AND (3)
 FOR GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION.
  
 5) SHOW COMPLIANCE WITH NEC 210.12 FOR ARC-FAULT
 PROTECTION.
  
 6) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT
 RECEPTACLES.
  
 7) SHOW COMPLIANCE WITH NEC 210.52 (A) (1) FOR
 RECEPTACLE SPACING.
  
 8) SHOW COMPLIANCE WITH NEC 210.52 (D) AND (E) (1) FOR
 BATHROOM AND OUTDOOR RECEPTACLE OUTLETS.
  
 9) SHOW COMPLIANCE WITH NEC 210.70 (A) (1), (2) AND (3)
 FOR REQUIRED INTERIOR AND OUTDOOR LIGHTING OUTLETS.
  
 10) THE NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE
 ELECTRICAL PLANS. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-24 Cont ID  
Sent By rmcdouga Date 2014-05-24 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2014-05-23 Time 11:28 Sent To  
Notes
2014-05-23 11:28:31TO RMCDOUGA DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-09 Cont ID  
Sent By rmcdouga Date 2014-05-09 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2014-05-06 Time 16:13 Sent To  
Notes
2014-05-06 16:14:21EXPEDITED!!! INCOMING SENT TO ROBERT MC DOUGALS DESK .
 JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-05-30 Cont ID  
Sent By skennedy Date 2014-05-30 Time 11:24 Rev Time 0.00
Received By skennedy Date 2014-05-30 Time 11:24 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-05-24 Cont ID  
Sent By rmcdouga Date 2014-05-24 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2014-05-24 Time 10:40 Sent To  
Notes
2014-05-24 10:41:03SEE PREVIOUS COMMENT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-05-08 Cont ID  
Sent By rmcdouga Date 2014-05-08 Time 13:07 Rev Time 0.00
Received By rmcdouga Date 2014-05-08 Time 13:07 Sent To  
Notes
2014-05-08 13:13:33ONE SET OF PLANS IS REQUIRED TO BE SIGNED OUT AND TAKEN
 TO PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE
 PLANS WITH THE IMPACT FEE REVIEW ON THEM AND A COPY OF
 THE IMPACT FEE RECEIPT ARE TO BE SUBMITTED TO THE CITY
 BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE
 ISSUED. PBC IMPACT FEES PHONE # 561-233-5025

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-05-06 Cont ID  
Sent By rmcdouga Date 2014-05-06 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2014-05-06 Time 18:26 Sent To  
Notes
2014-05-06 18:27:42NO MECHANICAL WORK IS SHOWN ON THE PLANS. A SEPARATE
 PERMIT, APPLICATION AND REVIEW IS REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-06 Cont ID  
Sent By rmcdouga Date 2014-05-06 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2014-05-06 Time 18:25 Sent To  
Notes
2014-05-06 18:28:12A PLUMBING SUB-PERMIT IS REQUIRED.