| Notes |
| 2014-05-09 16:39:18 | GEC TO BE INCREASED TO #2CU PER ARTICLE 250.66 OF THE | | | 2008 EDITION OF THE NEC | | | | | | AN INTERSYSTEM BONDING TERMINATION IS REQUIRED PER | | | ARTICLE 250.94 OF THE 2008 EDITION OF THE NEC |
|
|