Plan Review Details - Permit 14050154
Plan Review Stops For Permit 14050154
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-20 Cont ID  
Sent By dhayes Date 2014-05-20 Time 15:52 Rev Time 0.00
Received By dhayes Date 2014-05-20 Time 15:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-05-07 Cont ID  
Sent By dhayes Date 2014-05-07 Time 15:51 Rev Time 0.00
Received By dhayes Date 2014-05-07 Time 15:51 Sent To  
Notes
2014-05-07 16:18:161) FBC- 107.3.5.3 ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. PLEASE CLARIFY RISER TO INDICATE WIRE SIZE
 AND TYPE.
  
 2) 2010 FBC RESIDENTIAL SECTION 314 AND 315 FLOOR PLAN
 INDICATING SMOKE DETECTORS IN REQUIRED LOCATIONS.
  
 3) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-20 Cont ID  
Sent By dhayes Date 2014-05-20 Time 15:53 Rev Time 0.00
Received By dhayes Date 2014-05-20 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-07 Cont ID  
Sent By dhayes Date 2014-05-07 Time 15:52 Rev Time 0.00
Received By dhayes Date 2014-05-06 Time 09:40 Sent To  
Notes
2014-05-06 09:40:49ROUTED TO ELECTRICAL $5000 & UNDER