Plan Review Details - Permit 14050133
Plan Review Stops For Permit 14050133
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-07-17 Cont ID  
Sent By rmcdouga Date 2014-07-17 Time 16:58 Rev Time 0.00
Received By rmcdouga Date 2014-07-17 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-05 Cont ID  
Sent By rmcdouga Date 2014-06-05 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2014-06-05 Time 09:52 Sent To E
Notes
2014-06-05 11:11:242010 FBC
  
 DENIED BY BUILDING
  
 1) THE TYPE OF CONSTRUCTION SPECIFIED ON SHEET CVR IS
 III - B. THIS IS INCORRECT. THIS STRUCTURE DOES NOT
 HAVE 2 HOUR FIRE RATED EXTERIOR WALLS. IT SHOULD BE
 TYPE V - B. FBC TABLE 601
  
 2) ON SHEET S-1 THE F1 FOOTING IN THE SCHEDULE IS 18"
 WIDE AND 16" IN DEPTH AND DETAIL 4 ON S-1 HAS 12" + 6"
 FOR A DEPTH OF 18". PLEASE CORRECT. CITY AMENDMENTS
 107.2.1
  
 3) ON SHEET S-2, THE WIND PRESSURES LISTED BELOW THE
 ROOF AREA DIAGRAM ARE NOT CORRECT FOR A STRUCTURE WITH
 A 5/12 SLOPE ROOF AND A 25' MRH LOCATED IN A 170 MPH
 VULT WINDSPEED AND EXPOSURE CATEGORY C. PLEASE CORRECT.
 FBCR 301.2.1
  
 4) THE UPLIFT CONNECTOR NOTES ON SHEET S-2 SPECIFY
 HUGHES CONNECTORS. THAT COMPANY IS NO LONGER IN
 EXISTENCE. IT WAS PURCHASED BY USP SEVERAL YEARS AGO.
 PLEASE UPDATE THE PLANS TO REFERENCE CONNECTORS WITH
 CURRENT PRODUCT
 APPROVALS. DCA RULE 9N-3.
  
 5) ON SHEET A-2 THE ID TAGS ON THE WINDOWS IN THE REAR
 OF THE ADDITION ARE INCORRECT. THE WINDOWS MARKED 'D'
 SHOULD BE 'B' AND THE HALF MOON WINDOW FIXED WINDOW
 SHOULD BE 'D' RATHER THAN 'F' IN ORDER TO CORRESPOND
 WITH THE WINDOW SCHEDULE. PLEASE CORRECT.
  
 6) THE ENERGY COMPLIANCE FORM 402 - 2010 CAN NOT BE
 USED FOR THIS PROJECT. THE GLASS AREA EXCEEDS 20
 PERCENT OF THE CONDITIONED FLOOR AREA. SEE NOTE 1 UNDER
 GENERAL INSTRUCTIONS. SHOW THAT ADDITION WILL COMPLY
 WITH 2010 FBC ENERGY CONSERVATION SECTION 401.2.
  
 7) SHOW COMPLIANCE WITH FBCR 806 FOR REQUIRED ROOF
 VENTILATION.
  
 8) SHOW COMPLIANCE WITH FBCR 807 FOR ATTIC ACCESS TO
 THE NEW ADDITION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-19 Cont ID  
Sent By dhayes Date 2014-07-19 Time 12:29 Rev Time 0.00
Received By dhayes Date 2014-07-19 Time 10:05 Sent To M
Notes
2014-07-19 12:29:11DATE: 7/19/2014
 PROJECT: 205 MONROE DR. ADDITION AND REMODEL
 PERMIT#: 14050133
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO SEE ADDITIONAL NOTES ON SHEET E-2
 RELATING TO WIRE SIZES ON FEEDERS AND BRANCH CIRCUITS.
  
 1) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 2) FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, AND
 BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE
 POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY
 TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED
 AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC
 210.70(3)
  
 3) THE PROVISIONS OF PART II ARE INTENDED TO REQUIRE
 DISCONNECTING MEANS CAPABLE OF DISCONNECTING
 AIR-CONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING
 MOTOR-COMPRESSORS AND CONTROLLERS FROM THE CIRCUIT
 CONDUCTORS. NEC 440.11
  
 4) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT
 FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING
 OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS
 SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
  
 5) AIR HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 SIX (6) FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
  PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER,
 EFFICIENT, AND ECONOMIC OPERATION OF THE AIR
 CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR
 MAINTENANCE IS PERFORMED.
 YOUR AIR CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING:
 1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION
 DRAIN IS NOT WORKING PROPERLY OR;
 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION. FBC-M 306.3.2
  
 6) NEW LAOD CALCULATION REQUIRED TO COMPLY WITH THE
 PROVISIONS THE NEC ARTICLE 220. SEE ANNEX D FOR
 EXAMPLES.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-06-06 Cont ID  
Sent By albarran Date 2014-06-06 Time 11:54 Rev Time 0.00
Received By albarran Date 2014-06-06 Time 10:51 Sent To I
Notes
2014-06-06 12:01:50FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS:
 1. INDICATE ON PAGE E1 THE LOCATION OF THE EXISTING
 SERVICE.
 2. CORRECT ELECTRICAL RISER DIAGRAM TO MATCH EXISTING
 CONDITIONS.
 3. PROVIDE A PANEL SCHEDULE FOR OF THE THE PANELS (A,
 B, C)
 4. REVISE THE LOAD CALCS. PROVIDE LOAD CALCS FOR EACH
 PANEL FOR CLARIFICATION.
 5. CORRECT THE ELECTRICAL NOTES ON PAGE A0 TO REFLECT
 THE 2008 EDITION OF THE NEC RATHER THAN THE NOT YET
 ADOPTED LATEST EDITION. THE SMOKE DETECTOR INSTRUCTIONS
 AS STATED ARE NOT CODE COMPLIANT AND DO NOT MATCH THOSE
 OF E1. SAME WITH THE ARC-FAULT REQUIREMENTS.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-05-23 Cont ID  
Sent By fmittner Date 2014-05-23 Time 10:44 Rev Time 0.00
Received By fmittner Date 2014-05-23 Time 10:44 Sent To  
Notes
2014-05-23 10:44:42UPDATED PRODUCT APPROVALS FOR MISSION BARREL TILE
 SUBMITTED.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-05-05 Cont ID  
Sent By fmittner Date 2014-05-05 Time 15:13 Rev Time 0.00
Received By fmittner Date 2014-05-05 Time 15:13 Sent To  
Notes
2014-05-05 15:18:47PRODUCT APPROVALS FOR ROOF MUST BE BARREL TILE TO MATCH
 PLANS SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2014-07-28 Time   Rev Time 0.00
Received By jwitmer Date 2014-07-25 Time 14:19 Sent To  
Notes
2014-07-25 14:20:07SENT TO H MOSER DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-21 Cont ID  
Sent By hmoser Date 2014-07-21 Time 11:18 Rev Time 0.00
Received By hmoser Date 2014-07-02 Time 10:26 Sent To  
Notes
2014-07-03 10:29:31INCOMING SENT TO R11 . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-06 Cont ID  
Sent By albarran Date 2014-06-06 Time 12:35 Rev Time 0.00
Received By albarran Date 2014-05-05 Time 17:32 Sent To  
Notes
2014-06-06 12:36:41CONTACTED BRYAN TURNER TO ADVISE OF STATUS. SENT FOLLOW
 UP EMAIL WITH INSTRUCTIONS AND ROUTED TO LARGE DENIED
 BIN "M".
2014-05-05 17:33:18R10

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-07-28 Cont ID  
Sent By jsaez Date 2014-07-28 Time 09:39 Rev Time 0.00
Received By jsaez Date 2014-07-28 Time 09:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-07-21 Cont ID  
Sent By hmoser Date 2014-07-21 Time 11:18 Rev Time 0.00
Received By hmoser Date 2014-07-21 Time 08:12 Sent To  
Notes
2014-07-21 11:18:37PLAN DENIED
 1) EQUIPMENT SCHEDULE SHOWS THREE UNITS PLAN SHOWS ONE.
 IF THE EQUIPMENT IS EXISTING REMOVE THEM FROM THE
 SCHEDULE.
 IF THEY ARE NOT EXISTING ADD THEM TO THE PLAN. PER
 SECTION
 107 FBC 2010.
 2) PLEASE EXPLAIN WHERE THE 14IN DUCT IN THE UPPER
 CHASE IS GOING.
 PER SECTION 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-06-03 Cont ID  
Sent By jsaez Date 2014-06-03 Time 15:38 Rev Time 0.00
Received By jsaez Date 2014-06-03 Time 15:31 Sent To  
Notes
2014-06-05 09:56:121. PROVIDE A.H.U./ C.U. DETAIL, SCHEDULES.
 2. CHASE OUT 14" DN. TO GRD. FLR.
 3. NO R/A THRU BED.RM # 2 FROM A.H.U.- 2
 4. MINI SPLIT SHON ON PLANS.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-06-05 Cont ID  
Sent By rmcdouga Date 2014-06-05 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2014-06-05 Time 09:36 Sent To  
Notes
2014-06-05 15:46:32THE FLOOR PLANS ON SHEET P-1 ARE MIS-LABELED AS
 MECHANICAL RATHER THAN PLUMBING.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-05 Cont ID  
Sent By fmittner Date 2014-05-05 Time 15:13 Rev Time 0.00
Received By fmittner Date 2014-05-05 Time 15:13 Sent To  
Notes
***NONE***