Plan Review Details - Permit 14050116
Plan Review Stops For Permit 14050116
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-06-27 Cont ID  
Sent By jwitmer Date 2014-06-27 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2014-06-27 Time 15:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-06-17 Cont ID  
Sent By jwitmer Date 2014-06-17 Time 11:46 Rev Time 0.00
Received By jwitmer Date 2014-06-17 Time 11:46 Sent To  
Notes
2014-06-17 11:47:47BUILDING PLAN REVIEW
 PERMIT: 14050116
 ADD: 610 CLEMATIS ST UNITS- 2, 3 &4
 CONT: PRETI CONSTRUCTION, INC
 TEL: (561)282-8860
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 17/2014
 ACTION: DENIED
  
 1) THE PLANS UNDICATE A SINGLE TENANT WITHIN 3 UNITS,
 CROSSES THE UNIT PROPERTY LINES, CONDOMINIUM. UNITY OF
 TITLE. THE PROPOSED BUILDING STRUCTURE TRANSGRESSES
 LEGAL BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO
 FORM 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED
 AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED
 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE. SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-06-06 Cont ID  
Sent By jwitmer Date 2014-06-06 Time 14:19 Rev Time 0.00
Received By jwitmer Date 2014-06-06 Time 14:01 Sent To  
Notes
2014-06-06 14:19:18BUILDING PLAN REVIEW
 PERMIT: 14050116
 ADD: 610 CLEMATIS ST UNITS- 2, 3 &4
 CONT: PRETI CONSTRUCTION, INC
 TEL: (561)282-8860
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 06/2014
 ACTION: DENIED
  
 1) THE PLANS UNDICATE A SINGLE TENANT WITHIN 3 UNITS,
 CROSSES THE UNIT PROPERTY LINES, CONDOMINIUM. UNITY OF
 TITLE. THE PROPOSED BUILDING STRUCTURE TRANSGRESSES
 LEGAL BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO
 FORM 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED
 AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED
 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE. SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-06-10 Cont ID  
Sent By dhayes Date 2014-06-10 Time 08:48 Rev Time 0.00
Received By dhayes Date 2014-06-10 Time 07:15 Sent To  
Notes
2014-06-10 08:47:566/10/14.
 PROJECT: UDKS TENANT IMPROVEMENT
 PERMIT#: 14050116
 CODE: 2008 EDITION OF THE NEC AND THE 2010 EDITION OF
 THE FBC
 ACTION: PROVISO
  
  
 THE VENTILATION SHALL BE ADEQUATE TO DISPOSE OF THE
 TRANSFORMER FULL-LOAD LOSSES WITHOUT CREATING A
 TEMPERATURE RISE THAT IS IN EXCESS OF THE TRANSFORMER
 RATING. NEC 450.9

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-05-09 Cont ID  
Sent By pleduc Date 2014-05-09 Time   Rev Time 0.00
Received By pleduc Date 2014-05-09 Time 12:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-17 Cont ID  
Sent By jwitmer Date 2014-06-17 Time 12:06 Rev Time 0.00
Received By jwitmer Date 2014-06-16 Time 17:43 Sent To  
Notes
2014-06-16 17:43:43TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-06-10 Cont ID  
Sent By dhayes Date 2014-06-10 Time 08:50 Rev Time 0.00
Received By dhayes Date 2014-05-05 Time 18:48 Sent To  
Notes
2014-05-05 18:50:33C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-06-17 Cont ID  
Sent By jwitmer Date 2014-06-17 Time 12:06 Rev Time 0.00
Received By jwitmer Date 2014-06-17 Time 12:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-20 Cont ID  
Sent By hmoser Date 2014-05-20 Time 14:55 Rev Time 0.00
Received By hmoser Date 2014-05-20 Time 14:55 Sent To  
Notes
2014-05-20 14:55:53PLAN REVIEW BY JS. PX1328

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-17 Cont ID  
Sent By jwitmer Date 2014-06-17 Time 11:27 Rev Time 0.00
Received By jwitmer Date 2014-06-17 Time 11:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-06-06 Cont ID  
Sent By jwitmer Date 2014-06-06 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2014-06-06 Time 14:01 Sent To  
Notes
2014-06-06 15:05:16PLUMBING PLAN REVIEW
 PERMIT: 14050116
 ADD: 610 CLEMATIS ST UNITS- 2, 3 &4
 CONT: PRETI CONSTRUCTION, INC
 TEL: (561)282-8860
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 06/2014
 ACTION: DENIED
  
 SHEET P2.1 INDICATES THE USE OF AIR ADMITTANCE VALVES
 ON THE 1ST FLOOR SINK OF A 8 STORY BUILDING. PLEASE
 PROVIDE COM,PLIANCE WITH 917.3.1 LOCATION OF BRANCH.
 THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE
 DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK.
  
 917.3.2 RELIEF VENT.
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR
 EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE
 STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED
 TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL
 BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL
 BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2014-05-12 Cont ID  
Sent By aaponte Date 2014-05-12 Time 13:34 Rev Time 0.00
Received By aaponte Date 2014-05-12 Time 13:34 Sent To  
Notes
2014-05-12 13:35:12OFFICE USE ALLOWED PER DAC VARIANCE (DAC CASE NO.
 13-06)